Xtreme Power Conversion XPRT?1500, XPRT?1000, XPRT?2000 User and Installation Manual

  • Hello! I am an AI chatbot trained to assist you with the Xtreme Power Conversion XPRT?1500 User and Installation Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!

XtremePowerConversion®Corporation
XtremePerformanceRackTowerSeries
(XPRT)
User’s&InstallationManual
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[2]
TABLEOFCONTENTS
INTRODUCTION...................................................................................................................................................... 7
PRODUCTDESCRIPTION ..................................................................................................................................... 7
DETERMININGTHEPOWERREQUIREMENTSOFYOUREQUIPMENT.............................................. 13
HARDWAREINSTALLATIONGUIDE ............................................................................................................. 13
USER’SOPERATIONS.......................................................................................................................................... 21
BATTERIES ............................................................................................................................................................ 26
REPLACINGTHEBATTERY .............................................................................................................................. 26
TROUBLESHOOTING .......................................................................................................................................... 27
SPECIFICATIONS.................................................................................................................................................. 28
OBTAININGSERVICE.......................................................................................................................................... 31
XTREMEPOWERCONVERSION™(XPC)CORPORATIONLIMITEDWARRANTY ............................ 32
APPENDIXA:BATTERYPACKUSERGUIDE ............................................................................................... 33
APPENDIXB:SNMPCONFIGURATIONGUIDE ........................................................................................... 42
INTRODUCTION
Thankyouforselectingthisuninterruptiblepowersupply(UPS).Itprovidesyouwithprotectionfor
connectedequipment.PleasereadthismanualbeforeinstallingtheXPRTSeriesUPSmodelsXPRT
1000,XPRT1500,XPRT2000andXPRT3000asitprovidesimportantinformationthatshouldbe
followedduringinstallationandmaintenanceoftheUPSandbatteries,allowingyoutocorrectlysetup
yoursystemforthemaximumsafetyandperformance.Includedisinformationoncustomersupport
andservice,ifitisrequired.IfyouexperienceaproblemwiththeUPS,pleaserefertothe
Troubleshootingsectioninthismanualtocorrecttheproblem.Iftheproblemisnotcorrected,please
collectinformationsothattheTechnicalSupportpersonnelcanmoreeffectivelyassistyou.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[3]
EMCStatements‐FCCPart15
Notice:Pursuanttosection15oftheFCCrules,thisproducthasbeentestedandtherebycomplies
totheconditionsofaClassB(XPRT1000,XPRT1500)andClassA(XPRT2000,XPRT3000)digitaldevice,
whichhavebeenestablishedforofferingsufficientprotectionagainstdangerousinterferencefor
installationinaresidentialarea.Installationanduseoftheequipmentshouldcomplywiththe
instructionsprovidedinordertoavoidsuchinterferenceduetotheamountofradiofrequencyenergy
thatisradiatedandgeneratedbytheequipment.Inspiteofthis,wecannotassurethatacertain
amountofinterferencemaynotoccurinsomeinstallations.If,byturningonandoff,itcanbededuced
thatyourradioortelevisionreceptionisfoundtobeinfluencedbyharmfulinterferencefromthe
equipment,itisrecommendedtouseoneofthefollowingpreventivemeasures.
Placethereceivingantennainaseparatelocationororientation.
Ensureagreaterdistanceisachievedbetweenthereceiverandtheequipment.
Ensurethatyourequipmentisconnectedtoanoutletonaseparatecircuitthanthe
receiver.
ContactatechnicianexperiencedwithradioandTVoradealerforfurtherassistance.
ICES003
ThisClassBInterferenceCausingEquipmentmeetsallrequirementsoftheCanadianInterference
CausingEquipmentRegulationsICES003.CetappareilnumeriquedelaclasseBrespectetoutesles
exigenciesduReglementsurlematerielbrouilleurduCanada.
DeclarationofConformityRequest
UnitslabeledwithaCEmarkcomplywiththefollowingstandardsanddirectives:
HarmonicStandards:EN5009111andEN500912
EUDirectives73/23/EEC,CouncilDirectiveonequipmentdesignedforusewithincertain
voltagelimits.
o 96/68/EEC,AmendingDirective73/23/EEC
o 89/336/EEC,CouncilDirectiverelatingtoelectromagneticcompatibility
o 92/31/EEC,AmendingDirective89/336/EECrelatingtoEMC
TheECDeclarationofConformityisavailableuponrequestforproductswithaCEmark.
CAUTION:AshieldedtypepowercordisrequiredinordertomeetFCCemissionlimitsandto
preventinterferencetothenearbyradioorTVreception.Itisessentialthatonlythesuppliedpower
cordbeused.UseonlyshieldedcablestoconnectI/Odevicestothisequipment.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[4]
WARNING:Anychangesormodificationsnotexpresslyapprovedbythemanufacturerofthis
devicecouldvoidtheuser’sauthoritytooperatetheequipment.
IMPORTANTSAFETYINSTRUCTIONS:
(SAVETHESEINSTRUCTIONS)
CAUTION!(UPShavingInternalBatteries):RiskofelectricalshockHazardouslive
partsinsidethisunitareenergizedfromthebatterysupplyevenwhentheinputACpoweris
disconnected.
CAUTION!(NoUserserviceableParts):Riskofelectricalshock,donotremovecover.
Nouserserviceablepartsinside.Referservicingtoqualifiedservicepersonnel.
CAUTION!(NonisolatedBatterysupply):Riskofelectricshock,batterycircuitisnot
isolatedfromACinput,hazardousvoltagemayexistbetweenbatteryterminalsandground.Testbefore
touching.
WARNING!(Fuses):Toreducetheriskoffire,replaceonlywiththesametypeandsizeoffuse.
WARNING!Unitintendedforinstallationinacontrolledenvironment.
CAUTION!Donotdisposeofbatteriesinafire,thebatterymayexplode.
CAUTION!Donotopenormutilatethebattery,releasedelectrolyteisharmfultotheskinandeyes.
CAUTION!Abatterycanpresentariskofelectricshockandhighshortcircuitcurrent.Thefollowing
precautionshouldbeobservedwhenworkingonbatteries:
Removewatches,ringsorothermetalobjects.
Usetoolswithinsulatedhandles.
Toreducetheriskofelectricshock,disconnecttheUPSfromthemainsupplybeforeinstallinga
computerinterfacesignalcable.Reconnectthepowercordonlyaftersignalinginterconnectionshave
beenmade.
Servicingofbatteriesshouldbeperformedorsupervisedbypersonnelwithknowledgeofbatteriesand
therequiredprecautions.Keepunauthorizedpersonnelawayfrombatteries.
TheseUPSunitsareextremelyheavy.DonotinstalltheUPSinarackorenclosurebyitsfronttwoears
only.Adjustablerackrailsarerequiredforthistypeofinstallation(Part#XPRTRR1)
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[5]
Theinstructionscontainedwithinthissafetymanualaredeemedimportantandshouldbeclosely
followedatalltimesduringinstallationandfollowupmaintenanceoftheUPSandbatteries.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[6]
 CAUTION
Theunithasadangerousamountofvoltage.IftheUPSindicatorison,theunit’soutletsmayhavea
dangerousamountofvoltageevenwhennotpluggedintothewalloutletbecausethebatterymay
continuetosupplypower.
Careshouldbetakentoundertakeinstallationindoors,freefromelectricallyconductiveparticles
whichareundertemperatureandhumiditycontrol,inordertoreducetheriskofelectricshock.
Itisbesttodisconnectthedeviceusingthepowersupplycord.Ensurethattheequipmentisplacedin
apositionneartheoutletwhereeasilyaccessible.
Exceptforreplacingthebatteries,allservicingonthisequipmentmustbecarriedoutbyqualified
servicepersonnel.
Beforeconductinganymaintenance,repair,orshipment,firstensurethateverythingisturnedoff
completelyanddisconnected.
Foradditionalsafetyinstructions,pleaseusetheSafetyManualasareference.
SpecialSymbols
ThefollowingsymbolsusedontheUPSwarnyouofprecautions:
RISKOFELECTRICSHOCK‐Pleaseobservethewarningthatariskofelectricshockispresent
CAUTION:REFERTOOPERATOR’SMANUAL‐Refertotheoperator’smanualforadditional
information,suchasimportantoperatingandmaintenanceinstructions.
SAFEGROUNDINGTERMINAL‐Indicatesprimarysafeground
LOADON/OFFPressingthebuttonturnson/offtheoutputreceptaclesandtheindicator
light.
RJ45RECEPTACLEThereceptacleprovidesnetworkinterfaceconnectionsandtelephoneor
telecommunicationsequipmentshouldnotbepluggedintoit.
PleasedonotdiscardoftheUPSortheUPSbatteriesastheUPSmayhavevalveregulated
leadacidbatteries.Pleaserecyclebatteriesappropriately.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[7]
INTRODUCTION
Theinformationprovidedinthismanualcoverssinglephase10003000VAuninterruptiblepower
systems,theirbasicfunctions,operatingprocedures,optionsavailableandemergencysituations.Italso
includesinformationonhowtoship,store,handle,andinstalltheequipment.Onlydetailed
requirementsoftheUPSunitsaredescribedherein,andinstallationmustbecarriedoutinaccordance
withthismanual.Electricalinstallationmustalsocarefullyfollowlocallegislationandregulations.Only
qualifiedpersonnelshouldconducttheseinstallationsasfailuretoacknowledgeelectricalhazardscould
provetobefatal.
PRODUCTDESCRIPTION
ManydifferentkindsofsensitiveelectricalequipmentcanbeprotectedbyanUninterruptiblePower
Supply(UPS)includingcomputers,workstations,processcontrolsystems,telecommunicationssystems,
salesterminals,othercriticalinstrumentation,etc.ThepurposeoftheUPSistoprotectthesesystems
frompoorqualityutilitypower,completelossofpower,orotherassociatedproblems.
Electricalinterferenceexistsinmanyforms,causingproblemsinACpower,fromlightning,power
companyaccidentsandradiotransmissionmotors,airconditioners,andvendingmachines.Protection
ofsensitiveelectricalequipmentisvitaltoprotectagainstpoweroutages,loworhighvoltage
conditions,slowvoltagefluctuations,frequencyvariations,differentialandcommonmodenoise,
transients,etc.
Topreventpowerlineproblemsfromreachingcriticalsystemscausingdamagetosoftware,hardware,
andequipmentmalfunctions,theUPSmaintainsconstantvoltage,isolatingcriticalloadoutputand
cleaningtheutilityACpower.
DoubleConversionOnLineTechnology
AdoubleconversiononlinetechnologyUPSprovidescompletelyisolated,clean,uninterruptedsingle
phasepowertoyourcriticalsystems,whilemaintainingthebatteriesfortheirmaximumpotential.In
theeventthatthepowerfailurelastslongerthantheUPSbackuptime,theUPSwillshutdownavoiding
batterydamage.WhentheinputACvoltagereturns,theUPSwillautomaticallyreturnonlineto
rechargethebatteries.
Asshowninfig.1blockdiagram:
Aninputfilterreducestransientsontheincomingutility.
Tomaintainfullbatterycharge,theACinputpowerisrectifiedandregulatedintherectifier
feedingpowertothebatteryconverterandinverter.
DCpowerisconvertedtoACintheinverter,passingitontotheload.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[8]
Powerismaintainedfromthebatteryduringapowerfailure.
Theconverterincreasesvoltageappropriatelyfortheinverter.
EfficiencyOptimizerFunction
TheEfficiencyOptimizerFunctionisanewfeaturefortheUPS,addingcosteffectiveness,minimizing
powerlossandreducingpowerconsumption.Alternatingbetweenbypassandonlinemodesis
achievedautomaticallyandinaccordancewiththeconditionsoftheutilitypower.Onlinemodemaybe
usedduringtimesofintermittentpower,andbypassmodeusedwhenpowerflowssmoothly,inorder
toobtaingreatestefficiency.Irregularitiescanbedetectedinlessthanasecond,andonlinemode
reactivatesimmediately.Switchingbacktoonlinemodeoccurswheninputvoltageisoutside±10%of
nominal(±15%selectable),wheninputfrequencyisoutsideof±3Hzorwhennoinputlineisavailable.
Althoughhighefficiencyisstandard,thedefaultoperationisinonlinemode.Bypasscanbeactivatedin
theLCDpanel,thoughonlinecanberunpermanentlyifpreferred.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[9]
FreeRunMode
TheUPSoperatesinFreeRunModewheninputfrequencyisoutsideoftheselectedinputfrequency
range.FreeRunModeiswhenoutputfrequencydoesnotmatchinputfrequency.Whenstartingthe
UPS,thefrequencyregulationdetectedis50or60Hz±0.25Hz.
DiagnosticTests
WhentheUPSisstarted,adiagnostictestisautomaticallyexecuted,checkingtheelectronicsand
batteries,reportinganyproblemsontheLCDdisplay.
AnXtremeBatteryManagementsystemalwaysmonitorstheconditionsofthebatteries,sendingany
forewarningsifreplacementofbatteriesisrequired.Every30daysofnormalmodeoperation,abattery
dischargetestisautomaticallyperformed,reportinganyproblemsontheLCDdisplay.
Exceptduringthefirst24hoursafterstartupwhiletheUPSisinchargingmode,diagnostictestscanbe
performedmanuallyfromthefrontpanelatanytime.
SystemConfiguration
TheUPSdeviceandtheinternalbatteriesmakeupthesystem.Dependingonthesiteandload
requirementsoftheinstallation,certainadditionaloptionsareavailableforthesolution.
PlanningaUPSsystem,thefollowingshouldbetakenintoconsideration:
Thetotaldemandoftheprotectedsystemshalldictatetheoutputpowerrating(VA).Allowa
marginforfutureexpansionorcalculationinaccuraciesfrommeasuredpowerrequirements.
Backuptimerequiredwillindicatethebatterysizeneeded.IftheloadislessthantheUPS
nominalpowerrating,thenactualbackuptimeislonger.
Thefollowingoptionsareavailable:
o ExtendedBatteryPacks(maximumof2batterypacksofsamemodel)
XPRTBP1for1000/1500
XPRTBP2for1000/1500
XPRTBP3for2000/3000
o ConnectivityOptions–SNMP/WEBcard
SeetheSpecificationsectionofthismanualforadditionmodelinformation.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[10]
Note:XPRT2000has(1)L520R+(2)520R;XPRT3000has(1)L530R+(2)520R
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[11]
“UPSON”Indicator
ThisLEDisgreenwhentheUPShasbeenturnedonandnormalutilitypowerisavailable.
“ONLINE”Indicator
ThisLEDisgreenwhentheUPSisinnormalorstaticbypassmodes,andthereisvoltageattheoutput
receptacles.
“ONBATTERY”Indicator
ThisLEDisredwhentheUPSisoperatinginbatterymode.
“ONBYPASS”Indicator
ThisLEDisyellowwhentheUPSisinbypassmode.
“FAULT”Indicator
ThisLEDisredifanyinternalerroroccursintheUPS.Anaudiblealarmwillalsobepresent.Pressanyof
thebuttonsonthefrontpaneltosilencethealarm.
FUNCTIONBUTTON
PressthisbuttontochoosewhichfunctionyouwantontheLCDdisplay.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[12]
ENTERBUTTON
PressthisbuttontocheckthecontentoftheUPSLDCdisplay.
ON/OFFBUTTON
Pressthisbuttonandholdfor3secondstoturntheUPSon.
RS232StandardInterface
TheRS232interfaceusesa9pinfemaleDsubconnector.Informationprovidedincludesdataabout
utility,loadandtheUPS.Theinterfaceportpinsandtheirfunctionsareidentifiedinthefollowingtable:
PIN#SIGNALNAMEDIRECTION(RE:UPS)FUNCTIONS
2TxDOUTPUTTxDOUTPUT
3RxDINPUTRxD/INVERTEROFFINPUT
5COMMON COMMON
6 OUTPUTACFAILOUTPUT
8 OUTPUTLOWBATTERYOUTPUT
9 OUTPUT12VDCPOWER
CAUTION:MAXRATEDVALUES12VDC
USBPort
ConnectingtheUPStoyourcomputerisaccomplishedthroughtheUSBportonthebackofyour
computer.USBcomplianthardwareandoperatingsystemwillbenecessary,includinginstallationofa
UPSdriver.TheserialportcannotbeusedwhenusingtheUSBport.TheUSBcableisastandardcable
included.
EmergencyPowerOff(EPO)Port
AcustomersuppliedswitchlocatedremotelycanbeusedtoopentheEPOconnectionandallowsthe
UPSoutputreceptaclestobeswitchedoff.SincetheEPOshutsdowntheequipmentimmediately,
orderlyshutdownproceduresarenotfollowedbyanypowermanagementsoftware.TheUPSwillhave
tobemanuallyrestartedinordertoregainpowertotheoutletsontheUPS.
NetworkTransientProtector
ThenetworktransientprotectorlocatedonthebackpaneloftheUPS,hasbothanINandOUTjacks,
housingasingleRJ45(10BaseT)networkconnector.ConnecttheinputconnectortothejacklabeledIN
andtheoutputconnectortothejacklabeledOUT.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[13]
LoadSegments
Thepowermanagementsoftwarecontrolsthesetsofreceptaclesknownasloadsegments,whichcan
provideorganizedshutdownandstartupoftheequipmentconnectedtotheUPS.Lesscritical
equipmentcanbeturnedoffduringpoweroutagessavingbatterypowerforcriticalloads.Thepower
managementsoftwareinstructionsprovidemoredetailregardingoperationofthisfeature.Theload
groupstatuscanbeviewedfromtheLCDdisplayandcanbechangedifrequired.
DETERMININGTHEPOWERREQUIREMENTSOFYOUR
EQUIPMENT
1. MakesurethetotalVoltAmp(VA)requirementsofyourconnectedequipmentdoesnotexceed
themaximumVAratingfortheUPS.ThemaximumVAratingsareshownintheSpecifications
sectionofthisdocument.
2. EnsurethattheequipmentpluggedintothebatterypoweredoutletsdoesnotexceedtheUPS
ratedcapacity.IfUPSratedcapacitiesareexceeded,anoverloadconditionmayoccurandcause
theUPStoshutdownandtripthecircuitbreaker.
3. IfthepowerrequirementsofyourequipmentarelistedinvaluesotherthanVoltAmps(VA),
convertWatts(W)orAmps(A)intoVAbydoingthecalculationsbelow.Note:Theequation
belowonlycalculatesthemaximumamountofVAthattheequipmentcanuse,notwhatis
typicallyusedbytheequipmentatanygiventime.Usersshouldexpectusagerequirementsto
beapproximately60%ofthevaluetoestimatepowerrequirements:
verifyWatts(W)x1.43=_____VAor_____Amps(A)x120=_____VA
Addthetotalsforalloftheequipmentandmultiplythistotalby0.65tocalculateactualpower
requirements.
Note:Manyfactorscanaffecttheamountofpowerthatyourcomputersystemwillrequire.The
totalloadthatyouwillbeplacingonthebatterypoweredoutletsshouldnotexceed85%ofthe
UPScapacity.
HARDWAREINSTALLATIONGUIDE
InspecttheUPSuponreceipt.Thepackagingisrecyclable;keepitforreuseordisposeofproperly.
SafetyInformation
Informationpresentedhereisvitaltoallpersonnel.PleasereadallSafetyinformation.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[14]
StorageandTransportation
PleasehandletheUPSandassociatedequipmentwithextremecautionsinceahighamountofenergyis
containedinthebatteries.Alwayskeeptheunitinanuprightpositionasmarkedonthepackaging,and
neverdroptheunit.
PleaseadheretothefollowinginstructionsiftheUPSisnotinstalledimmediately:
Storetheequipmentasisinitsoriginalpackingandshippingcarton.
Donotstoreintemperaturesoutsidetherangeof‐15°Cto+25°C
Ensurethattheequipmentisfullyprotectedfromwetordampareasandfrommoistair.
Inordertomaintainthebatteries,theUPSshouldberechargedevery6monthsforatleast8hours.
Ifflammablesubstancessuchasgasesorfumesarepresent,oriftheroomisairtight,ahazardous
situationmayexistinwhichnoelectricalequipmentshouldbeoperated.
TheinstructionsinthismanualexplainhowtoinstalltheUPSsafely.Notacknowledgingsuchelectrical
hazardsmaybefatalkeepthismanualforfuturereference.
WARNING!
ItisstronglyrecommendedthattheUPScabinetnotbeopenedascomponentshavevery
highvoltageandtouchingthosecomponentsmaybefatal.Onlyaqualifiedtechnicianor
authorizedagentmayservicetheunit.
TheUPSunit’soutputreceptaclescarrylivevoltageevenwhennotconnectedtoaninput
voltagesource.TheUPShasitsowninternalenergysource.
Environment
Ensurethatallenvironmentalconcernsandrequirementsaremetaccordingtospecificationslistedin
thisdocument,otherwisethesafetyofinstallationpersonnelcannotbeguaranteed,andtheunitmay
malfunction.
EnsurethatyourememberthefollowingwhenlocatingtheUPSsystemandbatteryoptions:
Avoidextremesoftemperatureandhumidity.Maximumbatterylifecanbeattainedwitha
recommendedtemperaturerangeof+15°Cto+25°C.
Provideprotectionfortheequipmentfrommoisture.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[15]
Spaceandventilationrequirementsmustbemet.Ensurethereis100mmbehindand50mmon
thesidesoftheUPSforproperventilation.
EnsurethatthefrontoftheUPSremainsclearforuseroperation.
INSTALLATION
VerticalInstallationSteps

XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[16]
WallmountedInstallationSteps

XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[17]
StackedInstallationSteps
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[18]
RackmountInstallationSteps
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[19]
Note:AnyexternalBatteryPacksmustbeinstallednexttoorundertheUPS.PleaserefertotheBattery
PackUserGuideincludedintheBatteryPackboxformoreinformationwheninstallingthese.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[20]
InitialConnectionandStartup:
EnsurethattheUPSandoptionalbatterypacksaremountedcorrectly,andtheUPSisdisconnected
frominputpowerbeforeproceeding.
1. Connectexternalbatterypacks(option).
UsethecablefromtheExternalBatteryPacktoconnecttotheUPSintheappropriate
location.IfasecondExternalBatteryPackisbeingused,connectthecablefromthe
secondExternalBatteryPacktotheappropriateconnectorintherearofthe1stExternal
BatteryPack.Donotclosethebatterybreaker(s)onthebatterypack(s).
RefertotheBatteryPackUserManualincludedintheBatterypackboxformoredetails
2. ConnectSNMPcard(option)
RemovethetwoscrewssecuringtheSNMPcoverplateontherearoftheUPS,andslide
theSNMPcardintotheslot.Securethecardintotheslotwiththetwoscrews
previouslyremoved.
3. ConnecttheUPStoACpower
EnsuretheUPSlinecordisconnectedtotheappropriategroundedreceptacle.The
batterieswillautomaticallychargewhenconnectedtoACinput.Pleasenotethateven
thoughyoumaystartusingtheUPSimmediately,maximumbatterybackuptimemay
notbeavailableuntilthebatterieshavechargedforaminimumof8hours.
4. StartandconfiguretheUPS
StarttheUPSbypushingtheON/OFFBUTTONonthecontrolpanel.
TheUPSwillcommenceastartupselftestofinternalfunctionsincludingmain
synchronization,andinverterstartup.Duringthestartupselftest,theLCDwilldisplay:
“Readyon”,“BatteryMode”,and“LineMode”inthatorder.TheUPSwillremainin
“LineMode”andwillbeprovidingpowertotheoutputreceptacles.
ProgramtheUPSforsystemandsitespecificparameters.Thesearethefactoryfunction
settingslistedonpage23andshouldonlybechangedifneeded.Forexample,if
optionalbatterypacksareutilized,thisiswhereyouchangethenumberofbattery
packsforruntimeaccuracy.Thisisonlychangedfrom“0”ifexternalbatterypacksare
beingused.See“ButtonOperation”onpage21toenterconfigurationmodeviathe
functionbuttonandmakechangestodefaultparameters.
Configurethelocalmonitoringsoftwareifdesired.
1. InserttheUPSMONCD(includedwithUPSpackaging)intotheCDROMofthelocal
computer.
2. SelecttheappropriateinstallationfromtheAutorunmenu.
3. Followthesetupinstructions.Clickfinishwhenprompted.Ensurethecheckboxto
startUPSMONischeckedbeforeclickingfinish.
4. TheUPSMONiconwillappearinthesystemtrayofthedesktopnearthesystem
clock.Doubleclickthisicontoenlargetheprogramwindow.
/