User’s&InstallationManual
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[2]
TABLEOFCONTENTS
INTRODUCTION...................................................................................................................................................... 7
PRODUCTDESCRIPTION ..................................................................................................................................... 7
DETERMININGTHEPOWERREQUIREMENTSOFYOUREQUIPMENT.............................................. 13
HARDWAREINSTALLATIONGUIDE ............................................................................................................. 13
USER’SOPERATIONS.......................................................................................................................................... 21
BATTERIES ............................................................................................................................................................ 26
REPLACINGTHEBATTERY .............................................................................................................................. 26
TROUBLESHOOTING .......................................................................................................................................... 27
SPECIFICATIONS.................................................................................................................................................. 28
OBTAININGSERVICE.......................................................................................................................................... 31
XTREMEPOWERCONVERSION™(XPC)CORPORATIONLIMITEDWARRANTY ............................ 32
APPENDIXA:BATTERYPACKUSERGUIDE ............................................................................................... 33
APPENDIXB:SNMPCONFIGURATIONGUIDE ........................................................................................... 42
INTRODUCTION
Thankyouforselectingthisuninterruptiblepowersupply(UPS).Itprovidesyouwithprotectionfor
connectedequipment.PleasereadthismanualbeforeinstallingtheXPRTSeriesUPSmodelsXPRT
1000,XPRT1500,XPRT2000andXPRT3000asitprovidesimportantinformationthatshouldbe
followedduringinstallationandmaintenanceoftheUPSandbatteries,allowingyoutocorrectlysetup
yoursystemforthemaximumsafetyandperformance.Includedisinformationoncustomersupport
andservice,ifitisrequired.IfyouexperienceaproblemwiththeUPS,pleaserefertothe
Troubleshootingsectioninthismanualtocorrecttheproblem.Iftheproblemisnotcorrected,please
collectinformationsothattheTechnicalSupportpersonnelcanmoreeffectivelyassistyou.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[3]
EMCStatements‐FCCPart15
Notice:Pursuanttosection15oftheFCCrules,thisproducthasbeentestedandtherebycomplies
totheconditionsofaClassB(XPRT1000,XPRT1500)andClassA(XPRT2000,XPRT3000)digitaldevice,
whichhavebeenestablishedforofferingsufficientprotectionagainstdangerousinterferencefor
installationinaresidentialarea.Installationanduseoftheequipmentshouldcomplywiththe
instructionsprovidedinordertoavoidsuchinterferenceduetotheamountofradiofrequencyenergy
thatisradiatedandgeneratedbytheequipment.Inspiteofthis,wecannotassurethatacertain
amountofinterferencemaynotoccurinsomeinstallations.If,byturningonandoff,itcanbededuced
thatyourradioortelevisionreceptionisfoundtobeinfluencedbyharmfulinterferencefromthe
equipment,itisrecommendedtouseoneofthefollowingpreventivemeasures.
Placethereceivingantennainaseparatelocationororientation.
Ensureagreaterdistanceisachievedbetweenthereceiverandtheequipment.
Ensurethatyourequipmentisconnectedtoanoutletonaseparatecircuitthanthe
receiver.
ContactatechnicianexperiencedwithradioandTVoradealerforfurtherassistance.
ICES003
ThisClassBInterferenceCausingEquipmentmeetsallrequirementsoftheCanadianInterference
CausingEquipmentRegulationsICES003.CetappareilnumeriquedelaclasseBrespectetoutesles
exigenciesduReglementsurlematerielbrouilleurduCanada.
DeclarationofConformityRequest
UnitslabeledwithaCEmarkcomplywiththefollowingstandardsanddirectives:
HarmonicStandards:EN5009111andEN500912
EUDirectives73/23/EEC,CouncilDirectiveonequipmentdesignedforusewithincertain
voltagelimits.
o 96/68/EEC,AmendingDirective73/23/EEC
o 89/336/EEC,CouncilDirectiverelatingtoelectromagneticcompatibility
o 92/31/EEC,AmendingDirective89/336/EECrelatingtoEMC
TheECDeclarationofConformityisavailableuponrequestforproductswithaCEmark.
CAUTION:AshieldedtypepowercordisrequiredinordertomeetFCCemissionlimitsandto
preventinterferencetothenearbyradioorTVreception.Itisessentialthatonlythesuppliedpower
cordbeused.UseonlyshieldedcablestoconnectI/Odevicestothisequipment.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[4]
WARNING:Anychangesormodificationsnotexpresslyapprovedbythemanufacturerofthis
devicecouldvoidtheuser’sauthoritytooperatetheequipment.
IMPORTANTSAFETYINSTRUCTIONS:
(SAVETHESEINSTRUCTIONS)
CAUTION!(UPShavingInternalBatteries):RiskofelectricalshockHazardouslive
partsinsidethisunitareenergizedfromthebatterysupplyevenwhentheinputACpoweris
disconnected.
CAUTION!(NoUserserviceableParts):Riskofelectricalshock,donotremovecover.
Nouserserviceablepartsinside.Referservicingtoqualifiedservicepersonnel.
CAUTION!(NonisolatedBatterysupply):Riskofelectricshock,batterycircuitisnot
isolatedfromACinput,hazardousvoltagemayexistbetweenbatteryterminalsandground.Testbefore
touching.
WARNING!(Fuses):Toreducetheriskoffire,replaceonlywiththesametypeandsizeoffuse.
WARNING!Unitintendedforinstallationinacontrolledenvironment.
CAUTION!Donotdisposeofbatteriesinafire,thebatterymayexplode.
CAUTION!Donotopenormutilatethebattery,releasedelectrolyteisharmfultotheskinandeyes.
CAUTION!Abatterycanpresentariskofelectricshockandhighshortcircuitcurrent.Thefollowing
precautionshouldbeobservedwhenworkingonbatteries:
Removewatches,ringsorothermetalobjects.
Usetoolswithinsulatedhandles.
Toreducetheriskofelectricshock,disconnecttheUPSfromthemainsupplybeforeinstallinga
computerinterfacesignalcable.Reconnectthepowercordonlyaftersignalinginterconnectionshave
beenmade.
Servicingofbatteriesshouldbeperformedorsupervisedbypersonnelwithknowledgeofbatteriesand
therequiredprecautions.Keepunauthorizedpersonnelawayfrombatteries.
TheseUPSunitsareextremelyheavy.DonotinstalltheUPSinarackorenclosurebyitsfronttwoears
only.Adjustablerackrailsarerequiredforthistypeofinstallation(Part#XPRTRR1)
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[5]
Theinstructionscontainedwithinthissafetymanualaredeemedimportantandshouldbeclosely
followedatalltimesduringinstallationandfollowupmaintenanceoftheUPSandbatteries.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[6]
 CAUTION
Theunithasadangerousamountofvoltage.IftheUPSindicatorison,theunit’soutletsmayhavea
dangerousamountofvoltageevenwhennotpluggedintothewalloutletbecausethebatterymay
continuetosupplypower.
Careshouldbetakentoundertakeinstallationindoors,freefromelectricallyconductiveparticles
whichareundertemperatureandhumiditycontrol,inordertoreducetheriskofelectricshock.
Itisbesttodisconnectthedeviceusingthepowersupplycord.Ensurethattheequipmentisplacedin
apositionneartheoutletwhereeasilyaccessible.
Exceptforreplacingthebatteries,allservicingonthisequipmentmustbecarriedoutbyqualified
servicepersonnel.
Beforeconductinganymaintenance,repair,orshipment,firstensurethateverythingisturnedoff
completelyanddisconnected.
Foradditionalsafetyinstructions,pleaseusetheSafetyManualasareference.
SpecialSymbols
ThefollowingsymbolsusedontheUPSwarnyouofprecautions:
RISKOFELECTRICSHOCK‐Pleaseobservethewarningthatariskofelectricshockispresent
CAUTION:REFERTOOPERATOR’SMANUAL‐Refertotheoperator’smanualforadditional
information,suchasimportantoperatingandmaintenanceinstructions.
SAFEGROUNDINGTERMINAL‐Indicatesprimarysafeground
LOADON/OFFPressingthebuttonturnson/offtheoutputreceptaclesandtheindicator
light.
RJ45RECEPTACLEThereceptacleprovidesnetworkinterfaceconnectionsandtelephoneor
telecommunicationsequipmentshouldnotbepluggedintoit.
PleasedonotdiscardoftheUPSortheUPSbatteriesastheUPSmayhavevalveregulated
leadacidbatteries.Pleaserecyclebatteriesappropriately.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[7]
INTRODUCTION
Theinformationprovidedinthismanualcoverssinglephase10003000VAuninterruptiblepower
systems,theirbasicfunctions,operatingprocedures,optionsavailableandemergencysituations.Italso
includesinformationonhowtoship,store,handle,andinstalltheequipment.Onlydetailed
requirementsoftheUPSunitsaredescribedherein,andinstallationmustbecarriedoutinaccordance
withthismanual.Electricalinstallationmustalsocarefullyfollowlocallegislationandregulations.Only
qualifiedpersonnelshouldconducttheseinstallationsasfailuretoacknowledgeelectricalhazardscould
provetobefatal.
PRODUCTDESCRIPTION
ManydifferentkindsofsensitiveelectricalequipmentcanbeprotectedbyanUninterruptiblePower
Supply(UPS)includingcomputers,workstations,processcontrolsystems,telecommunicationssystems,
salesterminals,othercriticalinstrumentation,etc.ThepurposeoftheUPSistoprotectthesesystems
frompoorqualityutilitypower,completelossofpower,orotherassociatedproblems.
Electricalinterferenceexistsinmanyforms,causingproblemsinACpower,fromlightning,power
companyaccidentsandradiotransmissionmotors,airconditioners,andvendingmachines.Protection
ofsensitiveelectricalequipmentisvitaltoprotectagainstpoweroutages,loworhighvoltage
conditions,slowvoltagefluctuations,frequencyvariations,differentialandcommonmodenoise,
transients,etc.
Topreventpowerlineproblemsfromreachingcriticalsystemscausingdamagetosoftware,hardware,
andequipmentmalfunctions,theUPSmaintainsconstantvoltage,isolatingcriticalloadoutputand
cleaningtheutilityACpower.
DoubleConversionOnLineTechnology
AdoubleconversiononlinetechnologyUPSprovidescompletelyisolated,clean,uninterruptedsingle
phasepowertoyourcriticalsystems,whilemaintainingthebatteriesfortheirmaximumpotential.In
theeventthatthepowerfailurelastslongerthantheUPSbackuptime,theUPSwillshutdownavoiding
batterydamage.WhentheinputACvoltagereturns,theUPSwillautomaticallyreturnonlineto
rechargethebatteries.
Asshowninfig.1blockdiagram:
Aninputfilterreducestransientsontheincomingutility.
Tomaintainfullbatterycharge,theACinputpowerisrectifiedandregulatedintherectifier
feedingpowertothebatteryconverterandinverter.
DCpowerisconvertedtoACintheinverter,passingitontotheload.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[8]
Powerismaintainedfromthebatteryduringapowerfailure.
Theconverterincreasesvoltageappropriatelyfortheinverter.
EfficiencyOptimizerFunction
TheEfficiencyOptimizerFunctionisanewfeaturefortheUPS,addingcosteffectiveness,minimizing
powerlossandreducingpowerconsumption.Alternatingbetweenbypassandonlinemodesis
achievedautomaticallyandinaccordancewiththeconditionsoftheutilitypower.Onlinemodemaybe
usedduringtimesofintermittentpower,andbypassmodeusedwhenpowerflowssmoothly,inorder
toobtaingreatestefficiency.Irregularitiescanbedetectedinlessthanasecond,andonlinemode
reactivatesimmediately.Switchingbacktoonlinemodeoccurswheninputvoltageisoutside±10%of
nominal(±15%selectable),wheninputfrequencyisoutsideof±3Hzorwhennoinputlineisavailable.
Althoughhighefficiencyisstandard,thedefaultoperationisinonlinemode.Bypasscanbeactivatedin
theLCDpanel,thoughonlinecanberunpermanentlyifpreferred.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[9]
FreeRunMode
TheUPSoperatesinFreeRunModewheninputfrequencyisoutsideoftheselectedinputfrequency
range.FreeRunModeiswhenoutputfrequencydoesnotmatchinputfrequency.Whenstartingthe
UPS,thefrequencyregulationdetectedis50or60Hz±0.25Hz.
DiagnosticTests
WhentheUPSisstarted,adiagnostictestisautomaticallyexecuted,checkingtheelectronicsand
batteries,reportinganyproblemsontheLCDdisplay.
AnXtremeBatteryManagementsystemalwaysmonitorstheconditionsofthebatteries,sendingany
forewarningsifreplacementofbatteriesisrequired.Every30daysofnormalmodeoperation,abattery
dischargetestisautomaticallyperformed,reportinganyproblemsontheLCDdisplay.
Exceptduringthefirst24hoursafterstartupwhiletheUPSisinchargingmode,diagnostictestscanbe
performedmanuallyfromthefrontpanelatanytime.
SystemConfiguration
TheUPSdeviceandtheinternalbatteriesmakeupthesystem.Dependingonthesiteandload
requirementsoftheinstallation,certainadditionaloptionsareavailableforthesolution.
PlanningaUPSsystem,thefollowingshouldbetakenintoconsideration:
Thetotaldemandoftheprotectedsystemshalldictatetheoutputpowerrating(VA).Allowa
marginforfutureexpansionorcalculationinaccuraciesfrommeasuredpowerrequirements.
Backuptimerequiredwillindicatethebatterysizeneeded.IftheloadislessthantheUPS
nominalpowerrating,thenactualbackuptimeislonger.
Thefollowingoptionsareavailable:
o ExtendedBatteryPacks(maximumof2batterypacksofsamemodel)
XPRTBP1for1000/1500
XPRTBP2for1000/1500
XPRTBP3for2000/3000
o ConnectivityOptions–SNMP/WEBcard
SeetheSpecificationsectionofthismanualforadditionmodelinformation.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[10]
Note:XPRT2000has(1)L520R+(2)520R;XPRT3000has(1)L530R+(2)520R
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[11]
“UPSON”Indicator
ThisLEDisgreenwhentheUPShasbeenturnedonandnormalutilitypowerisavailable.
“ONLINE”Indicator
ThisLEDisgreenwhentheUPSisinnormalorstaticbypassmodes,andthereisvoltageattheoutput
receptacles.
“ONBATTERY”Indicator
ThisLEDisredwhentheUPSisoperatinginbatterymode.
“ONBYPASS”Indicator
ThisLEDisyellowwhentheUPSisinbypassmode.
“FAULT”Indicator
ThisLEDisredifanyinternalerroroccursintheUPS.Anaudiblealarmwillalsobepresent.Pressanyof
thebuttonsonthefrontpaneltosilencethealarm.
FUNCTIONBUTTON
PressthisbuttontochoosewhichfunctionyouwantontheLCDdisplay.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[12]
ENTERBUTTON
PressthisbuttontocheckthecontentoftheUPSLDCdisplay.
ON/OFFBUTTON
Pressthisbuttonandholdfor3secondstoturntheUPSon.
RS232StandardInterface
TheRS232interfaceusesa9pinfemaleDsubconnector.Informationprovidedincludesdataabout
utility,loadandtheUPS.Theinterfaceportpinsandtheirfunctionsareidentifiedinthefollowingtable:
PIN#SIGNALNAMEDIRECTION(RE:UPS)FUNCTIONS
2TxDOUTPUTTxDOUTPUT
3RxDINPUTRxD/INVERTEROFFINPUT
5COMMON COMMON
6 OUTPUTACFAILOUTPUT
8 OUTPUTLOWBATTERYOUTPUT
9 OUTPUT12VDCPOWER
CAUTION:MAXRATEDVALUES12VDC
USBPort
ConnectingtheUPStoyourcomputerisaccomplishedthroughtheUSBportonthebackofyour
computer.USBcomplianthardwareandoperatingsystemwillbenecessary,includinginstallationofa
UPSdriver.TheserialportcannotbeusedwhenusingtheUSBport.TheUSBcableisastandardcable
included.
EmergencyPowerOff(EPO)Port
AcustomersuppliedswitchlocatedremotelycanbeusedtoopentheEPOconnectionandallowsthe
UPSoutputreceptaclestobeswitchedoff.SincetheEPOshutsdowntheequipmentimmediately,
orderlyshutdownproceduresarenotfollowedbyanypowermanagementsoftware.TheUPSwillhave
tobemanuallyrestartedinordertoregainpowertotheoutletsontheUPS.
NetworkTransientProtector
ThenetworktransientprotectorlocatedonthebackpaneloftheUPS,hasbothanINandOUTjacks,
housingasingleRJ45(10BaseT)networkconnector.ConnecttheinputconnectortothejacklabeledIN
andtheoutputconnectortothejacklabeledOUT.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[13]
LoadSegments
Thepowermanagementsoftwarecontrolsthesetsofreceptaclesknownasloadsegments,whichcan
provideorganizedshutdownandstartupoftheequipmentconnectedtotheUPS.Lesscritical
equipmentcanbeturnedoffduringpoweroutagessavingbatterypowerforcriticalloads.Thepower
managementsoftwareinstructionsprovidemoredetailregardingoperationofthisfeature.Theload
groupstatuscanbeviewedfromtheLCDdisplayandcanbechangedifrequired.
DETERMININGTHEPOWERREQUIREMENTSOFYOUR
EQUIPMENT
1. MakesurethetotalVoltAmp(VA)requirementsofyourconnectedequipmentdoesnotexceed
themaximumVAratingfortheUPS.ThemaximumVAratingsareshownintheSpecifications
sectionofthisdocument.
2. EnsurethattheequipmentpluggedintothebatterypoweredoutletsdoesnotexceedtheUPS
ratedcapacity.IfUPSratedcapacitiesareexceeded,anoverloadconditionmayoccurandcause
theUPStoshutdownandtripthecircuitbreaker.
3. IfthepowerrequirementsofyourequipmentarelistedinvaluesotherthanVoltAmps(VA),
convertWatts(W)orAmps(A)intoVAbydoingthecalculationsbelow.Note:Theequation
belowonlycalculatesthemaximumamountofVAthattheequipmentcanuse,notwhatis
typicallyusedbytheequipmentatanygiventime.Usersshouldexpectusagerequirementsto
beapproximately60%ofthevaluetoestimatepowerrequirements:
verifyWatts(W)x1.43=_____VAor_____Amps(A)x120=_____VA
Addthetotalsforalloftheequipmentandmultiplythistotalby0.65tocalculateactualpower
requirements.
Note:Manyfactorscanaffecttheamountofpowerthatyourcomputersystemwillrequire.The
totalloadthatyouwillbeplacingonthebatterypoweredoutletsshouldnotexceed85%ofthe
UPScapacity.
HARDWAREINSTALLATIONGUIDE
InspecttheUPSuponreceipt.Thepackagingisrecyclable;keepitforreuseordisposeofproperly.
SafetyInformation
Informationpresentedhereisvitaltoallpersonnel.PleasereadallSafetyinformation.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[14]
StorageandTransportation
PleasehandletheUPSandassociatedequipmentwithextremecautionsinceahighamountofenergyis
containedinthebatteries.Alwayskeeptheunitinanuprightpositionasmarkedonthepackaging,and
neverdroptheunit.
PleaseadheretothefollowinginstructionsiftheUPSisnotinstalledimmediately:
Storetheequipmentasisinitsoriginalpackingandshippingcarton.
Donotstoreintemperaturesoutsidetherangeof‐15°Cto+25°C
Ensurethattheequipmentisfullyprotectedfromwetordampareasandfrommoistair.
Inordertomaintainthebatteries,theUPSshouldberechargedevery6monthsforatleast8hours.
Ifflammablesubstancessuchasgasesorfumesarepresent,oriftheroomisairtight,ahazardous
situationmayexistinwhichnoelectricalequipmentshouldbeoperated.
TheinstructionsinthismanualexplainhowtoinstalltheUPSsafely.Notacknowledgingsuchelectrical
hazardsmaybefatalkeepthismanualforfuturereference.
WARNING!
ItisstronglyrecommendedthattheUPScabinetnotbeopenedascomponentshavevery
highvoltageandtouchingthosecomponentsmaybefatal.Onlyaqualifiedtechnicianor
authorizedagentmayservicetheunit.
TheUPSunit’soutputreceptaclescarrylivevoltageevenwhennotconnectedtoaninput
voltagesource.TheUPShasitsowninternalenergysource.
Environment
Ensurethatallenvironmentalconcernsandrequirementsaremetaccordingtospecificationslistedin
thisdocument,otherwisethesafetyofinstallationpersonnelcannotbeguaranteed,andtheunitmay
malfunction.
EnsurethatyourememberthefollowingwhenlocatingtheUPSsystemandbatteryoptions:
Avoidextremesoftemperatureandhumidity.Maximumbatterylifecanbeattainedwitha
recommendedtemperaturerangeof+15°Cto+25°C.
Provideprotectionfortheequipmentfrommoisture.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[15]
Spaceandventilationrequirementsmustbemet.Ensurethereis100mmbehindand50mmon
thesidesoftheUPSforproperventilation.
EnsurethatthefrontoftheUPSremainsclearforuseroperation.
INSTALLATION
VerticalInstallationSteps

XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[16]
WallmountedInstallationSteps

XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[17]
StackedInstallationSteps
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[18]
RackmountInstallationSteps
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[19]
Note:AnyexternalBatteryPacksmustbeinstallednexttoorundertheUPS.PleaserefertotheBattery
PackUserGuideincludedintheBatteryPackboxformoreinformationwheninstallingthese.
XPRT1000,XPRT1500,XPRT2000,XPRT3000USER’SMANUALUNINTERRUPTIBLEPOWERSUPPLY(UPS)
[20]
InitialConnectionandStartup:
EnsurethattheUPSandoptionalbatterypacksaremountedcorrectly,andtheUPSisdisconnected
frominputpowerbeforeproceeding.
1. Connectexternalbatterypacks(option).
UsethecablefromtheExternalBatteryPacktoconnecttotheUPSintheappropriate
location.IfasecondExternalBatteryPackisbeingused,connectthecablefromthe
secondExternalBatteryPacktotheappropriateconnectorintherearofthe1stExternal
BatteryPack.Donotclosethebatterybreaker(s)onthebatterypack(s).
RefertotheBatteryPackUserManualincludedintheBatterypackboxformoredetails
2. ConnectSNMPcard(option)
RemovethetwoscrewssecuringtheSNMPcoverplateontherearoftheUPS,andslide
theSNMPcardintotheslot.Securethecardintotheslotwiththetwoscrews
previouslyremoved.
3. ConnecttheUPStoACpower
EnsuretheUPSlinecordisconnectedtotheappropriategroundedreceptacle.The
batterieswillautomaticallychargewhenconnectedtoACinput.Pleasenotethateven
thoughyoumaystartusingtheUPSimmediately,maximumbatterybackuptimemay
notbeavailableuntilthebatterieshavechargedforaminimumof8hours.
4. StartandconfiguretheUPS
StarttheUPSbypushingtheON/OFFBUTTONonthecontrolpanel.
TheUPSwillcommenceastartupselftestofinternalfunctionsincludingmain
synchronization,andinverterstartup.Duringthestartupselftest,theLCDwilldisplay:
“Readyon”,“BatteryMode”,and“LineMode”inthatorder.TheUPSwillremainin
“LineMode”andwillbeprovidingpowertotheoutputreceptacles.
ProgramtheUPSforsystemandsitespecificparameters.Thesearethefactoryfunction
settingslistedonpage23andshouldonlybechangedifneeded.Forexample,if
optionalbatterypacksareutilized,thisiswhereyouchangethenumberofbattery
packsforruntimeaccuracy.Thisisonlychangedfrom“0”ifexternalbatterypacksare
beingused.See“ButtonOperation”onpage21toenterconfigurationmodeviathe
functionbuttonandmakechangestodefaultparameters.
Configurethelocalmonitoringsoftwareifdesired.
1. InserttheUPSMONCD(includedwithUPSpackaging)intotheCDROMofthelocal
computer.
2. SelecttheappropriateinstallationfromtheAutorunmenu.
3. Followthesetupinstructions.Clickfinishwhenprompted.Ensurethecheckboxto
startUPSMONischeckedbeforeclickingfinish.
4. TheUPSMONiconwillappearinthesystemtrayofthedesktopnearthesystem
clock.Doubleclickthisicontoenlargetheprogramwindow.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49