Emerson 37-6585C Owner's manual

Category
Thermostats
Type
Owner's manual

This manual is also suitable for

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
Your new White-Rodgers Digital Thermostat uses the technology
of a solid-state microcomputer to provide precise temperature
control.
Features:
• Simultaneousheatandcoolsetpointstorage
• Pre-settemperaturecontrol
• Backlitdisplay
• LCDcontinuouslydisplayssetpointandroomtemperature
• °F/°Cconvertibility
• Temperaturerange45°to90°F
• RC,RH,C,W,Y,G,OandBterminals
• OptionalCterminal(DualPoweroption)
• BandOterminalsforsinglestageheatpumps(noauxiliary
heat)ordamperoperation
• Setpointstorageincaseofpowerloss
• 2"AA"alkalinebatteriesincluded
SPECIFICATIONS
ELECTRICAL DATA
Electrical Rating:
8to30VAC50/60Hz.orD.C.
0.05to1.0Amps(Loadperterminal)
1.5 Amps Maximum Total Load(Allterminalscombined)
THERMAL DATA
Setpoint Temperature Range:
45°Fto90°F(7°Cto32°C)
Operating Ambient Temperature Range:
32°Fto105°F
Operating Humidity Range:
0to90%RH(non-condensing)
Shipping Temperature Range:
-4°Fto150°F
APPLICATIONS
Forusewith:
• Standardheat/coolorheatonlysystems
• Electricheatsystems
• Gasoroilredsystems
• Gassystemswithintermittentignitiondevices(I.I.D.)
and/orventdampers
• Hydronic(hotwaterorsteam)systems
• Single-stageheatpumpsystems(noauxiliaryheat)
• Millivoltsystems
DO NOT USE WITH:
• Multi-stagesystems
• Systemsexceeding30VACand1.5amps
• 3-wirezonedhydronicheatingsystems
1F86-344
Non-ProgrammableElectronicDigitalThermostat
PART NO. 37-6585C
Replaces37-6585B
1123
INSTALLATION AND
OPERATION INSTRUCTIONS
PRECAUTIONS
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
This thermostat is intended for use with a low voltage system;
donotusethisthermostatwithalinevoltagesystem.Ifindoubt
aboutwhetheryourwiringismillivolt,line,orlowvoltage,have
itinspectedbyaqualiedheatingandairconditioningcontrac-
tor or electrician.
Donotexceedthespecicationratings.
Allwiringmustconformtolocalandnationalelectricalcodes
and ordinances.
Thiscontrolisaprecisioninstrument,andshouldbehandled
carefully. Rough handling or distorting components could cause
the control to malfunction.
WARNING
!
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.
Thermostat installation and all components of the sys-
tem shall conform to Class II circuits per the NEC code.
Operator: Save these instructions for future use!
www.white-rodgers.com
www.emersonclimate.com
2
INSTALLATION
REMOVE OLD THERMOSTAT
1. Shutoffelectricityatthemainfuseboxuntilinstallationis
complete.Ensurethatelectricalpowerisdisconnected.
2. Removethefrontcoveroftheoldthermostat.With wires
still attached, removewallplatefromthewall.Iftheold
thermostathasawallmountingplate,removethethermostat
andthewallmountingplateasanassembly.
3. Identify each wire attached to the old thermostat using
the labels enclosed with the new thermostat.
4. Disconnectthewiresfromoldthermostatoneatatime.DO
NOT LET WIRES FALL BACK INTO THE WALL.
5. Installnewthermostatusingthefollowingprocedures.
ATTENTION!
Thisproductdoesnotcontainmercury.However,thisproduct
may replace a unit which contains mercury.
Donotopenmercurycells.Ifacellbecomesdamaged,donot
touchanyspilledmercury.Wearingnonabsorbentgloves,take
upthespilledmercurywithsandorotherabsorbentmaterialand
placeintoacontainerwhichcanbesealed.Ifacellbecomes
damaged,theunitshouldbediscarded.
Mercurymustnotbediscardedinhouseholdtrash.Whenthe
unitthisproductisreplacingistobediscarded,placeinasuit-
ablecontainer.Refertowww.white-rodgers.comforlocationto
send product containing mercury.
ELECTRIC HEAT OR SINGLE-STAGE
HEAT PUMP SYSTEMS
Thisthermostatisconguredfromthefactorytooperateaheat/
cool,fossilfuel(gas,oil,etc.),forcedairsystem.Itiscongured
correctlyforanysystemthatDOESNOTrequirethethermostat
toenergizethefanonacallforheat.Ifyoursystemisanelectric
heatorheat-pumpsystemthatREQUIRESthethermostatto
turnonthefanonacallforheat,locatetheGAS/ELECTRIC
switch onthebackofthethermostat(seeg.1)andswitchitto
the ELECTRIC position.Thiswillallowthethermostattoenergize
thefanimmediatelyonacallforheat.Ifyouareunsureifthe
heating/coolingsystemrequiresthethermostattocontrolthefan,
contactaqualiedheatingandairconditioningserviceperson.
ATTACH THERMOSTAT BASE TO WALL
1. Removethepackingmaterialfromthethermostat.Gentlypullthe
coverstraightoffthebase.Forcingorpryingonthethermostat
willcausedamagetotheunit.Ifnecessary,movetheelectric
heatswitch(seeELECTRIC HEAT SYSTEMS,above).
2. Connectwiresbeneathterminalscrewsonbaseusingap-
propriatewiringschematic(seegs.2through7).
3. Placebaseoverholeinwallandmarkmountingholeloca-
tionsonwallusingbaseasatemplate.
4. Movebaseoutoftheway.Drillmountingholes.
5. Fastenbaselooselytowall,asshowning.1,usingtwo
mounting screws. Place a level against bottom of base,
adjustuntillevel,andthentightenscrews.(Levelingisfor
appearanceonlyandwillnotaffectthermostatoperation.)
Ifyouareusingexistingmountingholes,orifholesdrilled
aretoolargeanddonotallowyoutotightenbasesnugly,
useplasticscrewanchorstosecuresubbase.
6. Pushexcesswireintowallandplugholewithare-resistant
material(suchasberglassinsulation)topreventdraftsfrom
affecting thermostat operation.
BATTERY LOCATION
2"AA"alkalinebatteriesareincludedinthethermostatatthe
factorywithabatterytagtopreventpowerdrainage.You must
remove the battery tag to engage the batteries.
If"LO BATTERY"isdisplayed,thebatteriesarelowandshould
bereplaced.Forbestresults,replaceallbatterieswithnewpre-
miumbrandalkalinebatteriessuchasDuracell
®
orEnergizer
®
.
Toreplacebatteries,installthebatteriesalongthetopofthe
base(seeFig.1).Thebatteriesmustbeinstalledwiththeposi-
tive(+)endtotheleft.
HYDRONIC (HOT WATER OR STEAM)
HEATING SYSTEMS
This thermostat is set to operate properly with a forced-air heat-
ingsystem.Ifyouhaveahydronicheatingsystem(asystem
thatheatswithhotwaterorsteam),youmustsetthethermostat
tooperateproperlywithyoursystem.Changethesecondop-
tioninthecongurationmenutoSL(seeCONFIGURATION
MENU,page4).
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate
properly,contactaqualiedserviceperson.
Turn on power to the system.
Fan Operation
Ifyoursystemdoes not have a Gterminalconnection,skipto
Heating System.
1. MoveFANswitchto ONposition.Theblowershouldbegin
to operate.
2. MoveFANswitchtoAUTOposition.Theblowershouldstop
immediately.
Mounting
holes
Mounting
holes
Electric/Gas
switch
Screw anchors
Figure 1. Thermostat Base
3
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 5. Typical wiring diagram for
heat/cool, 5-wire, two-transformer systems
HEATING
TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
24 VAC
120 VAC
Hot
Neutral
COOLING TRANSFORMER
OBC
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 4. Typical wiring diagram for
heat/cool, 4-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
JUMPER
WIRE
OC
B
RED jumper wire (provided with thermostat) must be
connected between thermostat RH and RC terminals
for proper thermostat operation with this system.
NOTE
RH
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 2. Typical wiring diagram for
heat only, 3-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
YC
RC
JUMPER
WIRE
OB
For 2-wire Heat only,
attach to RH and W
NOTE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 7. Typical wiring diagram for heat pump
with reversing valve energized in HEAT
TRANSFORMER
Reversing
Valve*
RCO
B
C
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
system switch is in the HEAT position
Fan
Relay
RH
Y
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
THERMOSTAT
SYSTEM
G W
Figure 3. Typical wiring diagram for
cool only, 3-wire, single transformer systems
Cooling
System
Fan
Relay
RCOB
C
JUMPER
WIRE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 6. Typical wiring diagram for heat pump
with reversing valve energized in COOL
TRANSFORMER
Reversing
Valve*
RCOBC
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
system switch is in the COOL position
Fan
Relay
Heating System
1. MoveSYSTEMswitchtoHEATposition.Iftheheatingsystem
hasastandingpilot,besuretolightit.
2. Press
toadjustthermostatsettingaboveroomtempera-
ture.Theheatingsystemshouldbegintooperate.
3. Press
toadjusttemperaturesettingbelowroomtem-
perature. The heating system should stop operating.
Cooling System
1. MoveSYSTEMswitchtoCOOL position.
2. Press
toadjustthermostatsettingbelowroomtempera-
ture.Theblowershouldcomeonimmediatelyonhighspeed,
followedbycoldaircirculation.
3. Press
toadjusttemperaturesettingaboveroomtem-
perature. The cooling system should stop operating.
CAUTION
!
To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a
year with fresh premium brand alkaline batteries.
WIRING
4
CONFIGURATION MENU
Thecongurationmenuallowsyoutosetcertainthermostatop-
eratingcharacteristicstoyoursystemorpersonalrequirements.
MoveSYSTEMswitchtotheOFFposition,thenpress
and
atthesametimetoenterthecongurationmenu.Thedisplay
willshowtherstiteminthecongurationmenu.
Thecongurationmenuchartbelowsummarizesthecongura-
tionoptions.Anexplanationofeachoptionfollows.
Press
and tochangetothenextmenuitem.Toexitthe
menu,movetheSYSTEMswitchtoHEAT or COOL.Ifnokeys
arepressedwithinfteenminutes,thethermostatwillexitthe
congurationmenu.
1
Step Press Button(s) Displayed (Factory Default) Press or to select: COMMENTS
Set SYSTEM
switch to OFF
Set SYSTEM
switch to HEAT
or COOL
2
(FA)
SL
SYSTEM switch must be OFF to configure thermostat
options
8
LOC
(OFF)
ON
0 HI
(0)
4 LO to
4 HI
(F) C
Returns to normal operation
Select Compressor lockout OFF or ON
Select temperature display adjustment higher or lower
Select temperature display to F or C
and
3
d-L
(ON)
OFF
Select display backlight OFF or ON
Select FA or SL (Fast or Slow) heating cycle rate
Configuration Menu
* Press and
to advance to next item
and
and
and
and
4
5
6
7
FILTER
(000)
0 to 1950 hours
(in 50 hour increments)
Select Filter replacement run time
and
Beforeyoubeginusingyourthermostat,youshouldbefamiliar
with its features and with the display and the location and op-
erationofthethermostatbuttons.Yourthermostatconsistsof
twoparts:thethermostat cover and the base. To remove the
cover,pullitstraightoutfromthebase.Toreplacethecover,
lineupthecoverwiththebaseandpressuntilthecoversnaps
ontothebase.
The Thermostat Buttons and Switches
(see fig. 8)
1
Raises temperature setting.
2
Lowerstemperaturesetting.
3
FANswitch(ON,AUTO).
4
SYSTEMswitch(COOL,OFF,HEAT).
The Display
5
Flame icon(
) is displayed when the SYSTEM switch
is in the HEAT position. Snowflake icon( )isdisplayed
(non-ashing)whentheSYSTEMswitchisintheCOOL
position. Snowflakeisdisplayed(ashing)ifthethermostat
isinlockoutmodetopreventthecompressorfromcycling
tooquickly.
6
Displays current temperature.
7
Displays "FILTER" when the system has run for the selected
ltertimeperiodasaremindertochangeorcleanyourair
lter.
8
Displayssetpointtemperature(thisisblankwhenSYSTEM
switch is in the OFFposition).
9
Displays "BATTERY" and "LO" in the current temperature
locationwhenthe2"AA"batteriesarelowandshouldbe
replaced.
5
8 79
56
Figure 8. Thermostat display, buttons, and switches
FC
RETLIFYRETTAB
OPERATION
5
2) Select FA or SL (Fast or Slow) Heating Cycle Rate - The
FAsettingisfrequentlyusedforgas,oilorelectricheat.The
SLsettingproducesalongerheatingcyclewhichisnormally
for hot water or steam(hydronic) systems. Both settings
produceveryaccuratetemperaturecontrolandcanbeset
toyourpersonalpreference.FAcyclesthesystemjustunder
1°FandtheSLsettingcyclesatapproximately1.5°F.
3) Select Display Backlight (d-L OFF or ON) - The display
backlightimprovesdisplaycontrastinlowlightingconditions.
SelectingbacklightONwillkeepthelightonforashortperiod
oftimeafteranykeyispressed.SelectingOFFwillkeepthe
light off.
4) Select filter replacement run time - The thermostat will
display "FILTER" after the selected time of operation. This is
aremindertochangeorcleanyourairlter.Thistimecanbe
setfrom0to1950hoursin50hourincrements.A selection
of 000 will cancel this feature. When "FILTER"isdisplayed,
youcanclearitbypressing
and at the same time.
This resets the timer and starts counting the hours until the
nextlterchange.
5) Select Compressor Lockout (LOC OFF or ON)-Selecting
LOCONwillcausethethermostattowait5minutesbefore
turning on the compressor if the heating and cooling system
losespower.Itwillalsowait5minutesminimumbetween
cooling cycles. This is intended to help protect the compres-
sorfromshortcycling.Somenewercompressorsalready
haveatimedelaybuiltinanddonotrequirethisfeature.
Your compressor manufacturer can tell you if the feature is
already present in their system. When the compressor time
delayoccursitwillashthe(snowakeicon)foraboutve
minutes then turn on the compressor.
6) Select Temperature Display Adjustment (4 LO to 4
HI)-Allowsyoutoadjusttheroomtemperaturedisplay4°
higherorlower.Yourthermostatwasaccuratelycalibrated
atthefactorybutyouhavetheoptiontochangethedisplay
temperature to match your previous thermostat.
7) Select Temperature DIsplay (°F or °C) -Changesthedisplay
readouttoCelsiusorFahrenheitasrequired.
OPERATING FEATURES
Nowthatyouarefamiliarwiththethermostatbuttonsanddisplay,
readthefollowinginformationtolearnaboutthemanyfeatures
of the thermostat.
• SIMULTANEOUS HEATING/COOLING SETPOINT STOR-
AGE —Youcanenterbothyourheatingandcoolingset
points at the same time. There is no need to change the
thermostatatthebeginningofeachseason.
• CONFIGURATION MENU — Allows you to customize
certain thermostat options.
SETTING THE THERMOSTAT
This thermostat is very easy to operate. Set the SYSTEM
switch to either HEAT or COOL then press
or until the
temperature you want to maintain is shown on the right side
ofthedisplay.Ifyouwanttoturnthesystemoff,justmovethe
SYSTEMswitchtoOFF.
The FAN switch controls the fan operation. When the FAN
switch is set to AUTO,thefanwillcyclewiththefurnaceorair
conditioner.WhentheFANswitchissettoON,thefanwillrun
continuously,regardlessofSYSTEMswitchposition.
TROUBLESHOOTING
No Heating
With the SYSTEM switch set to HEAT, when the setpoint
temperatureisraisedorloweredpasttheroomtemperature,
thethermostatwillmakeasoftclicksound.Usually,thesound
indicatesthe thermostat isoperating correctly.If thesystem
doesnotcomeon,checkthesystemorcontactyourheating/
coolingserviceperson.Ifthethermostatdoesnotclicktrythe
ResetOperationlistedbelow.
No Cooling
SameprocedureasheatingexceptsetSYSTEMswitchtoCOOL.
Therecanbeuptoa5minutecompressorlock-outtimedelay
beforethethermostatclicksinCOOL.
Blank Display
A blank digital display usually indicates the thermostat has
receivedavoltagespike,staticdischargeorrequiresnewbat-
teries.Ifthedisplayremainsblankafterreplacingthebatteries,
seeResetOperationbelow.
Reset Operation
Ifavoltagespikeorstaticdischargeblanksoutthedisplayor
causes erratic thermostat operation you can reset the thermostat
bypressing
, andmovetheSYSTEMswitchfromOFF to
HEAT at the same time. This also resets the factory defaults
to the configuration menu.Ifthethermostathaspower,has
beenreset andstill doesnot functioncorrectly contactyour
heating/coolingservicepersonorplaceofpurchase.
OPERATION
HOMEOWNER HELP LINE: 1-800-284-2925
www.white-rodgers.com
www.emersonclimate.com
White-Rodgers is a division
ofEmersonElectricCo.
TheEmersonlogoisa
trademarkandservicemark
ofEmersonElectricCo.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Emerson 37-6585C Owner's manual

Category
Thermostats
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages