GVS K-BUS AMRW-24/10.1 User manual

Type
User manual
Guangzhou Video-star Electronics Industrial Co., Ltd
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
K-BUS
RSwitch Blind Actuator
User Manual-Ver. 1.2
AMRW-24/10.1
KNX/EIB Intelligent Installation Systems
K-BUS
RKNX/EIB Switch Blind Actuator
2
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
User manual update instructions
Ver.
Date
Edit contents
Edit position
1.0
2017.1.4
Published the first edition
1.1
2017.4.11
1. Add function of the parameter
“When blind is under end position,
up/down object function is”
Chapter 4.4.1 page 29
1.2
2017.5.25
Add connection diagram of blind
Chapter 3.2 page 8
K-BUS
RKNX/EIB Switch Blind Actuator
3
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Contents
1. General--------------------------------------------------------------------------------------------------------------------------------------4
2. Technical Data---------------------------------------------------------------------------------------------------------------------------- 6
3. Dimension and Connection Diagram------------------------------------------------------------------------------------------------7
3.1 Dimension diagram------------------------------------------------------------------------------------------------------------------- 7
3.2 Connection diagram------------------------------------------------------------------------------------------------------------------ 8
4. Parameter setting description in ETS--------------------------------------------------------------------------------------------- 10
4.1 Parameter window “General”----------------------------------------------------------------------------------------------------- 10
4.2 Parameter window “Channel function”----------------------------------------------------------------------------------------- 12
4.3 Switch outputs (A~L)---------------------------------------------------------------------------------------------------------------13
4.3.1 Parameter window “Channel X1,2”----------------------------------------------------------------------------------------- 13
4.3.2 Parameter window “X1,2: Time”-------------------------------------------------------------------------------------------- 17
4.3.2.1 Selection “Delay”------------------------------------------------------------------------------------------------------------------- 18
4.3.2.2 Selection “Flashing”----------------------------------------------------------------------------------------------------------------19
4.3.2.3 Selection “Staircase”--------------------------------------------------------------------------------------------------------------- 20
4.3.3 Parameter window “X1,2: Logic”--------------------------------------------------------------------------------------------21
4.3.4 Parameter window “X1,2: Scene”--------------------------------------------------------------------------------------------24
4.3.5 Parameter window “X1,2Forced"----------------------------------------------------------------------------------------- 25
4.3.6 Parameter window “X1,2Operation hours counter”------------------------------------------------------------------- 26
4.4 Shutter outputs (A~L)-------------------------------------------------------------------------------------------------------------- 27
4.4.1 Parameter window “Channel X: Shutter”--------------------------------------------------------------------------------- 27
4.4.1.1 Parameter window “X: Drive”---------------------------------------------------------------------------------------------------- 31
4.4.1.2 Parameter window “X: Auto.”---------------------------------------------------------------------------------------------------- 33
4.4.1.3 Parameter window“X: Scene”-----------------------------------------------------------------------------------------------------37
4.4.1.4 Parameter window “X: Safety”--------------------------------------------------------------------------------------------------- 38
4.4.2 Parameter window “Channel X: Blind”----------------------------------------------------------------------------------- 40
5. Communication Objects Description---------------------------------------------------------------------------------------------- 41
5.1 Communication objects of Switch outputs--------------------------------------------------------------------------------------41
5.2 Communication objects of Shutter outputs------------------------------------------------------------------------------------- 44
K-BUS
RKNX/EIB Switch Blind Actuator
4
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
1. General
The Switch Blind actuator is a multi-output module, providing 24 channels switch outputs or 12 channels
curtains outputs, you can configure the functions of the module according to your requirement, such as some
channels are used as switch outputs, other channels are used as curtains outputs. The curtain type can be selected
for the blind and the shutter, the curtain control motor type can be selected for the AC motor or dry contact motor.
The Switch Blind actuator is a modular installation device for fast installation in the distribution board on 35
mm DIN rails to DIN EN 60 715. The electrical connection is implemented by using screw terminals . The
connection to the KNX/EIB bus is implemented using the supplied bus connection terminal, with the system
power input of 21-30V DC. Only bus power supply are required.
This manual provides detailed technical information about the Switch Blind actuator for users as well as
assembly and programming details, and explains how to use the Switch Blind actuator by the application
examples.
The function of the Switch Blind actuator is summarized as follows:
——Switch output, which can connect some electrical loads, such as lighting, sockets. There are 24 outputs,
the power of the load is 230V AC 10A output with manual button controlling in front of the device. The module
offers the following functions:
Switch
Time function: on/off delay
Time function: flashing switch, for lamps of aging test
Time function: staircase lighting, for switch on the staircase lighting and after the duration time the
lighting can be turned off automatically. It is better if the function is used together with motion
detector.
Provide 8 scenes, recall and storing via a 1byte object
Logic operation: AND, OR, XOR, GATE function, up to three logic inputs
Status response, for know the current output state in the visualization
Forced operation, two data types: 1bit/2bit, for force action on or off, with the highest priority
Set the relay contact position after bus voltage recovery
Set the relay contact position after bus voltage failure
Manual switch outputs
Operation hours counter
K-BUS
RKNX/EIB Switch Blind Actuator
5
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
——Shutter output, which can connect with motor blinds, awnings, roller blinds, vertical blind, etc. There are
12 outputs with 230V AC 1000W motor or dry contact controlling motor. The output contacts for the directions UP
and DOWN. The pause on change in direction can be set via the parameters. One output can be also used as 2
channels switch when they are not used as shutter/blind output . The shutter/blind output offers the following
functions:
Movement UP/DOWN
Stop/Louvre adjustment
Move to position 0……100%
Adjustment louvre to position 0……100%(only “Shutter” working mode)
Set 8 scenes, store or recall via a 1byte object
Automatic sun protection
Safety function
Status response, query and reply the current shutter/blind position and operation mode to the bus,
thereby indicating the status in the visualization device
Two working mode: Blind and Shutter
Programmers are able to use the Engineering Tool Software ETS (ETS4 version or above) with a .knxprod file
to allocate the physical address and set the parameters.
To make sure that all the programmable functions are used correctly, you must check the connection of the
loads before use and note technical characteristic of loading equipment, particularly shutter driver, they refer more
technical characteristics, some characteristics are inherent, if not properly set them, it is likely to cause the load
device damage or not operating correctly.
K-BUS
RKNX/EIB Switch Blind Actuator
6
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
2. Technical Data
Power Supply
Bus VoltageEIB
21~30V DC, from EIB bus
Current consumption, EIB
<12mA
Power consumption, EIB
<360mW
Power consumption 10A
<1W
Capacitor charge current
Max. 24mA
Output
24 channels
Can be individually set (including switch, shutter )
Unrated voltage
230/400V AC50/60Hz
Inrated current capacity
10A/105uF
Max. switching current
16A/240V AC
Mechanical endurance
> 2 x 106
Electrical endurance
>5 x104
Max. DC current switching
capacity (resistive load)
16A/30V DC
Connection
EIB/KNX
Via bus connection terminalsred/blackØ0.8 mm
Outputs A/B/C1
Screw terminals
Wire Range0.5-4mm2
Torque 0.8N-m
Other outputs
Screw terminals
Wire Range 0.5-2.5mm2
Torque0.5N-m
Operation/
display
Programming button/ red LED
For assignment of the physical address
Green LED flashing
The application layer works normally
Temperature
range
Operation
-5……+45
Storage
-25……+55
Transport
-25……+70
Ambient
conditions
Max. air humidity
<93%except dewing
Design
Modular installation device (MDRC)
K-BUS
RKNX/EIB Switch Blind Actuator
7
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Housing/color
Plastic housing, gray
Installation
On 35mm DIN-Rail
To EN 60 715
Dimension
216mm ×90 mm ×64mm
Weight
0.8KG
Note: The above load is only for single lamps. In the case of several lamps in parallel, the load will be
reduced, although the power is unchanged, but the instantaneous impact of current will increase, and easy to
make the relay contacts melted. So, in normal use, subject to the measured current, the measured maximum
inrush current must be within the allowable range.
Application program
Max. number of
communication objects
Max. number of group
addresses
Max. number of
associations
212
254
254
3. Dimension and Connection Diagram
3.1Dimension diagram
K-BUS
RKNX/EIB Switch Blind Actuator
8
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
3.2 Connection diagram
K-BUS
RKNX/EIB Switch Blind Actuator
9
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
①③ Output terminals A~L, such as A1,A2 of them can be as two channel switch outputs or one channel curtain output. As curtain
output, A1 corresponds to A↑, A2 corresponds to A↓. The other channels have the same usage.
Manual operation buttons and status indicating light for outputs A~L, manual/auto. operation (Man.)switch button and status
indicating light.
Manual/Auto. switch button (Man.):
Switch the manual/Auto. Operation via a long operation. In the manual operation, switch the output channels via a short
operation.
When the indicator LED near the button is RED(R), the output of operation buttons can be used to control A,B,C,D.
When the indicator LED is GREEN(G), the output of operation buttons can be used to control E,F,G,H.
When the indicator LED is R&G, the output of operation buttons can be used to control I,J,K,L.
The output of operation button:
When control switch output via the button, the indicator LED near the button indicates the output state, the LED on is
output, off is no output.
When control curtain output, to move up/down the curtain via a long operation, and slat adj./stop via a short operation.
When curtain is running, the indicator LED will flash; If both of blinds and slat arrive at minimum or maximum position,
the LED will be on.
Note: The manual operation is set via the parameter “Manual operation” in window “General”. If disable, these buttons and LED are
not work.
EIB/KNX bus terminal
Programming button and LED: Red LED indicates physical address programming; Green LED indicates the normal working of
application layer.
K-BUS
RKNX/EIB Switch Blind Actuator
10
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
4. Parameter setting description in ETS
The parameters will be described in the form of the function interfaces.
4.1 Parameter window “General”
Parameter window “General” can be shown in fig.4.1. Here set some general parameters, that applies to the
curtain output, also applies to the switch output.
Fig. 4.1 Parameter Window “General”
Parameter “Operation delay after power voltage recovery [5…250s]”
The parameter defined the delay time that scan and relay operation after bus voltage recovery. No operation
will be executed before the scan and relay operation delay finished, the operation during this process will be
recorded and executed after the delay over. Meanwhile, telegrams sent during the scan delay will be recorded and
executed after the delay.
The delay time here does not include the initiation time of the device, normally it will take 3 seconds to
re-initiate the device after power voltage recovery. I.e the delay will start counter after the initiation time.
Note: During delay, the programming LED is on green , and the device can not be operated. After delay over,
the LED will flash green, and the device can be operated.
Parameter “Sending cycle of ‘in operation’ telegram (1...240s, 0 = inactive):
The parameter determines the time interval to send the telegram which shows the actuator is working normally
or not via the bus. With the setting 0”, the actuator doesn’t send the telegram; if the setting is not “0”, a telegram
K-BUS
RKNX/EIB Switch Blind Actuator
11
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
with the value “1” will be sent cyclically according to the setting to the bus.
Options: 0…240s, 0=cyclical send inactive
It is suggested to select the maximum time interval according to the application to keep the bus load as low as
possible.
Note: it is starting to count the time after power up, instead of the operation delay after recovery of bus
voltage.
Parameter Limit number of send telegram
This parameter is used to set the number limit of sending telegrams sent to the bus in order to decrease the load
of bus, options
Yes
No
When select “Yes”, the parameter “Period” and “Max. Number of send telegram within a period[1…255]” will
be visible.
Parameter Period
This is to set the limit time of sending telegrams. Options:
100ms
500ms
……
10min
After bus voltage recovery, when the initialization time and the scan and relay operation delay have been
completed, the set period begins and counting the telegrams also begins. Once the max. number of telegrams has
reached during the set period, the device will not send telegram to the bus until the next set period start, and the
telegrams that have not been sent will be stored in buffer and send in the next set period. The buffer can store up to
20 telegrams, if there are repetitive telegrams, the telegrams will be only sent once in the next set period.
Parameter Max. Number telegram within a period[1255]
This is to set the Max. number of telegrams being sent within the setting monitored period.
Option: 1…255
Note: the above two parameters only affect the telegrams sent to the bus, they don’t affect the operation
action.
Parameter “Central control for switch function”
This parameter sets the central control for switch function. Options:
Disable
K-BUS
RKNX/EIB Switch Blind Actuator
12
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Enable
If enablethe objectCentral control for all of switchis visibleall channels with central control enabled can
be switched together via the object.
Parameter “Manual operation”
The parameter defines whether the manual operation enables. Options
Disable
Enable
If the enable is selected, the Man. /Auto Button has been enabled. And the follow parameter is visible.
Parameter “Manual to automatic by”
Options:
Only long press
Both long press and automatic delay time
If set “only long press, the manual/auto”. Operation only can be switched via long press the Man. Button.
If set “both long press and automatic delay time”, the manual/auto. Operation can be switched via long press
the Man. Button. or the set time for the manual to automatic has elapsed.
Parameter “Delay time *1s[10...60000]”
The parameter appears when “both long press and automatic delay time” is selected in the parameter “manual
to automatic by”. It is used for setting the time for an automatic reset from the “manual operation” to “automatic
operation” state after the last push button operation.
Options: 10……60000s
Note: The operation buttons that are located at the front of the device is invalid in the safety functions.
4.2 Parameter window “Channel function”
Parameter window “Channel function” can be shown in fig.4.2. Here set channel function, as switch outputs or
curtain output, one channel can be used as two switch outputs or a curtain output. Whether it is switch output or
curtain output, Each switch or curtain output can be set separately, and parameters and objects which are assigned to
each output are the same. The follow using a output as an example described the switch output and curtain output.
K-BUS
RKNX/EIB Switch Blind Actuator
13
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Fig. 4.2 Parameter Window“Channel function”
When the channel is enabled, the corresponding parameters can be set.
4.3 Switch outputs (A~L)
There are max. 24 outputs. Each output can be set separately, and parameters and objects which are assigned to
each output are the same. Using output A1 as an example described.
4.3.1 Parameter window “Channel X1,2
Parameter window “Channel X1,2” can be shown in fig.4.3. which applies to a whole output. In addition to
setting general switching function, but also set position of switch on the bus power on and power down , reports of
switch status, etc..
K-BUS
RKNX/EIB Switch Blind Actuator
14
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Fig. 4.3 parameter window “Channel X1,2
Parameter “Central control of channel
The parameter sets whether the central control of the channel is enabled. Options
Disable
Enable
If enablethe channel can be controlled via the object Central control for all of switch.
Parameter If bus recoverycontact is
The output can adopt a defined status on bus voltage recovery via this parameter. Options:
unchange
Open
Closed
As before as bus fail
When selecting “Unchanged”, the contact of the relay will remain the same as the last status on the power on.
When selecting open”, the contact will be open; while it is closed when selecting closed”.
The contact position after voltage recovery is the same as that before power off with “As before bus voltage
fail”.
Parameter “If bus fail, contact is”
The output can adopt a defined status after the bus voltage failure via this parameter. Options:
Unchange
open
closed
When selecting “Unchange”, the contact of the relay will remain the same as the last status before power off;
K-BUS
RKNX/EIB Switch Blind Actuator
15
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
when selecting “open”, the contact will be open; while it is closed when selecting “closed.
Parameter “After downloading, contact is”
This parameter set the contact position of the output after downloading. Options:
Open
As bus recovery
If “open”, the output is open after downloading.
If “As bus recovery”, the output adopts the defined status of the parameter “If bus recovery, contact is”
Parameter "Object Value of Switchafter bus recovery
This parameter will be used when enabling the logic function “input 0” to define the default value of the
communication object Switch” after bus voltage recovery, which can be 0” or “1”. Options:
0
1
Parameter Set the reply mode of switch status
This parameter defines how to respond the current switch status to the bus. There are three options to select.
Options:
Respond after read only
respond after change
respond always
If selecting “respond after read only”, the status telegram will not be sent out until receiving a read request
telegrams via the object “reply switch status” from the bus.
If selecting “respond after change”, it will send the status immediately via the object “reply switch status”
when there are any changes on the output.
If selecting “respond always”, no matter it’s reading, or there is change for the status, as long as the controlling
telegram can be received, the object will send the current status to the BUS.
Parameter "Object value of switch status :
Options:
0=contact close; 1=contact open
0=contact open; 1=contact close
It means the contact of the relay will be closed when the value of the communication object reply switch
statusis 0 when setting 0=contact close; 1=contact open, while it is open when the value is 1.
It means the opposite with setting 0=contact open; 1=contact close.
Parameter Contact position if tele. Value is 1(0is opposite of 1if changed)
K-BUS
RKNX/EIB Switch Blind Actuator
16
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
This parameter defines the contact position when switch on the switch, which will be triggered by the
communication object “switch, X”. When enabling “input 0” in the logic function, it will use the communication
object “switch, X” to modify the value of “input 0”, rather than triggering the switch operation. In this case, this
parameter is no significance to the switch. Options:
Open
Close
The parameter only works after the object “Switch x” receiving value, and defines the direction of the contact
after receiving it. The details can be found in the below form:
Parameter options
“Switch, X” object value =1
“Switch, X” object value =0
Open
Contact open(OFF)
Contact close (ON)
close
Contact close (ON)
Contact open (OFF)
Since the switch and logic functions share the same object switch, X, thus need to understand the
relationship between them, the control sequence shown below (the logic functions, please refer to the
following chapter describe):
Object “Switch, X”
Object “Input 1 of logic, X”
Object “Input 2 of logic, X”
OutputRelay to perform an action
Fig. 4.4 switch and logical function diagram
Switch function
Is logic “Input 0”enable?
Logic
function
Result
No
“switch” object value
Yes
“switch” object value
AND, OR, XOR,
GATE
AND, OR, XOR,
GATE
K-BUS
RKNX/EIB Switch Blind Actuator
17
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
When the logic function “input 0” enables, the object “switch, X” used as input of “input 0”, the operation
of general switch will become invalid.
Parameter Special functions of switch actuator mode
This parameter defines whether enable the special functions of the switch actuator. The parameter window
“X1,2: Function” will be seen with “enable”, and able to set the special functions individually in Fig. 4.5. Enable or
disable the special function in “X1,2: Function”.
Options:
Disable
Enable
Fig. 4.5 the special function enable window “X1,2: Function”
4.3.2 Parameter window “X1,2: Time”
This parameter window will become visible when selecting “enable” in the parameter “Function of “time” ”
in the window “X:Function” shown in Fig. 4.5. See Fig. 4.6. And the object “enable time function” will be also
visible, which is used to disable the time function. After disabled, previous operation is still carried out completely.
Such as delay switch on, the function is disabled during delay, and then the switch is still switched on once the
delay has been finished.
K-BUS
RKNX/EIB Switch Blind Actuator
18
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
Fig. 4.6 parameter window “X1,2: Time-Delay ”
Parameter Type of time function
The parameter defines the type of the time function, there are three options for the mode of work. Options
Delay
Flashing
Staircase
4.3.2.1 Selection “Delay”
The parameter window of the delay switch in Fig. 4.6 will be shown when selecting “Delay”. The delay switch
can be started via the object “Delay function”.
Parameter Delay for switch on: (0...240 min)/ (0...59 s)
This parameter defines the delay time of switching on.
Options:
0…240 min
0…59s
After receiving the delay ON telegram, the switch is on once the delay over.
Parameter Delay for switch off: (0...240 min) / (0...59 s)
This parameter defines the delay time of switching off.
Options:
0…240 min
0…59 s
After receiving the delay off telegram, the switch is off once the delay over.
If receiving the relevant telegram again during delay, the delay will be reset.
K-BUS
RKNX/EIB Switch Blind Actuator
19
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
4.3.2.2 Selection “Flashing”
The parameter window in Fig. 4.7 “X: Time-flashing” will be shown up when selecting “flashing” in the
parameter “Type of time function”. The flashing switch function is mainly used for lamp aging test.
Fig. 4.7 parameter window “X1,2: Time-flashing”
The flashing switch can be started via the object “Flashing function”. It is able to set the flashing time in
“Delay for switch on” or “Delay for switch off”, which will restart the flashing when receiving the start flashing
telegram, and define the contact position after flashing.
Parameter Delay for switch on: (0...240Min), (0...59s)
The parameter defines the duration time of switch on the output when flashing.
Options:
0...240 min
0...59 s
Note: it will not be executed unless the time is lower than the relay threshold switch frequency. Since there
will be not sufficient energy to do it because of the frequent relay switching, and it may cause the time delay. The
same situation will happen after the bus voltage recovery.
Parameter Delay for switch off: (0...240Min), (0...59s)
The parameter defines the duration time of switch off the output when flashing. Options:
0...240 min
0...59 s
Note: it will not be executed unless the time is lower than the relay threshold switch frequency. Since there
will be not sufficient energy to do it because of the frequent relay switching, and it may cause the time delay. The
same situation will happen after the bus voltage recovery.
Parameter Number of ON-impulses (1...2550=no limited)
K-BUS
RKNX/EIB Switch Blind Actuator
20
www.video-star.com.cn marketing@video-star.com.cn Tel.:(862039338986
Fax:(862039338465
This parameter sets the flashing times.0 means no limited. A flashing includes an on and an off actions.
Options:0...255
Parameter Contact position after flashing
This parameter defines the relay contact position after flashing. Options:
Unchanged
Open
Close
ParameterControl mode of flashing
The parameter is used to select the control mode of the flashing output. Options:
Start with“1”, stop with “0”
Start with “0”, stop with “1”
Startwith “1/0”, can not be stopped
It will start flashing with value “1” when selecting “star with “1”, stop with “0” ”; it will stop flashing with “0”.
The stop position is defined via last parameter.
It will start flashing with value “0” when selecting “star with “0”, stop with “1” ”; it will stop flashing with “1”.
The stop position is defined via last parameter.
It will start flashing with either “1” or “0” when selecting “star with “1/0”, can not be stopped”; Under this
circumstance it cannot terminate the flashing by value until operation over or it is blocked by other operation.
4.3.2.3 Selection “Staircase”
The parameter window of the staircase lighting function in Fig. 4.8 will be visible when selecting “Staircase”
in the parameter “Type of time function”.
Fig. 4.8 parameter window “X1,2: Time-staircase”
The staircase lighting can be started via the object “staircase function”. The value that switches on the staircase
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47