TA Series of Temperature Controller
Instruction Manual
Thanks a lot for selecting the product!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Applications
TA series temperature controller is available for many TC & RTD
input. It adopts some advanced techonology such as multi digital
filter circuit, autotune PID, fuzzy PID that make it much more precise,
stable. It’s widely used in strong anti-interference and automation
systems of mechanism, chemical industrial, chinaware, light industrial,
metallurgy and petroleum chemical industrial. It is also applied to the
production line of foodstuff, packing, printing, dry machine, metal
heat process equipment to control the temperature. simple operation.
Panel
Parameter Setting
MYPIN
Indication lamp: On: active Off: inactive
AT: the auto-tuning operation
AL: the 1st alarm
OUT1: Heating/Main control output
OUT2/AL2: the 2nd control output or the 2nd alarm
<</AT UNDER DISPLAY MODE,
a. Access/Quite auto-tuning estate (press>3s ,AT lamp ON/OFF)
b. Access output preset value modification (press shortly)
UNDER PROGRAMMING MODE,
shift the digit for modification
Increment selected parameter value or selections
Decrement selected parameter value or selections
SET UNDER DISPLAY MODE, Access programming mode
UNDER PROGRAMMING MODE,
a. Store selected parameter and index to next parameter (press shortly)
b. Quite programming mode (press>3s)
>>
>
>
Power supply 90-260V AC/DC 50/60Hz
UNDER DISPLAYING MODE
PV displays current temperaturein F /C
SV displays preset output value
UNDER PRAGRAMMING MODE
PV displays parameter
SV displays parameter preset value
Safety Cautions
★ Make sure the power is off before connecting the wires to avoid
electric shock and strickly follow the connection diagram given out
by the factory.
★ Make sure the power is off when cleaning the instrument.
★ Make sure the instrument works under rated voltage to avoid dam
-age or cause fire.
★ Make sure the OUTPUT RELAY works at the rated load and elec
trical life.The relay may melt or burned or even cause fire if it works
agains its electrical life.
Instalation Notice
★ The instrument should be installed in domestic environment.Please
pre-heat for 15 munites before use.
★ Ambient environment: temp: 0℃(32F)~50℃(122F), humidity:
35%~85%RH.
★ To avoid using the instrument in such environment that full of dust,
explosive gas, vapor, or oil.
★To avoid using the instrument in such environment that full of strong
shock,high interference or other factor.
★ The power cable shoudn’t put together with big current cable to
avoid electronmagnetic interference, or use another pip or shield cable.
★ A surge suppressor or noice filter should be installed in case of
noice caused by equipment as motor/transformer/spiral pipe/farrite
cores,etc..
★ The output is active after the power ON fr 10s,please consider this
when configuring cotrol loop.
★The instrument has built-in recoverable fuse to pretect from damage
caused by short-cut circuit. It starts work automatically when
mulfunction is removed.
RELAY: normal open AC 250V/3A DC 30V/3A COS¢=1
Specifications
K 0~999℃/0~1200℃
J 0~999℃ /0~1200℃
T -150~400℃ (Special order)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Input
T/C
Withstand voltage strength
Others
Please mention when ordering
1500V Rms
(Between power terminal and the housing)
Min 50M Ω(500V DC)
(Between power terminal and the housing)
Environment temperature
Save temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
≤ 350g
E 0~1000℃
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle ≤ 300ms
Main output RELAY:normal open AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC: 24V DC± 2V/ 20mA
Alarm
SSR/LOGIC: 24V DC± 2V/ 20mA
OUT1: R: RELAY S: SSR/Logic
I: 4-20mA V: 0-10V N: None
Power Supply: Default: 90-260V AC/DC
E: 24VDC or 18-30V AC/DC
TA
□□ - □□□□
Models
Input signals:
Default:TC( K,J,E, S) RTD (Pt100,Cu50)
1: 4-20mA 0-10V 0-75mV
2: 4-20mA 0-10V Pt100
F: others (indicate when ordering)
AL1: R: RELAY S: SSR/Logic N: None
Dimension: 4: 48H× 48W 6: 48H × 96W
TA series of temperature controller
7: 72H× 72W 8: 96H × 48W 9: 96H× 96W
OUT2/AL2:
R: RELAY S: SSR/Logic N: None
>
>
Press SET or and >3s to enter the parameter setting menu.
A: Press SET to select the parameter to be changed,
B: Press <</AT key to select one of the digits of the setting(value) for
change.
C: Press / to make a change.
D: Press SET to save and move to the next parameter.
NOTE: SV window display convertsion. Under display mode, press
SET to convert display value for OUT or AL1.
>>
>>
↓
↓
↓
↓
Press >3S
SET
↓
↓
↓
↓
AL1(Alarm setting)
range: –1999-9999
AL2 mode: The same as AL1.
Range: ± 100.Display value
PV = Measured value - PVF
Integral time range 0.1-3600. I=OFF means
cancel integral time.
①
AM1(Alarm mode):
0: Deviation HI alarm 1: Deviatian
LO alarm 2: Absolute value HI alarm
3: Absolute value LO alarm 4: Section
outside alarm 5: Section inside alarm
6: TC broken alarm ,The factory setting is 2
Input signal selection TC: K, J, T,E, S
RTD: Pt100, Cu50 The factory setting is K
AL2 set range: –1999-9999.
SET
SET
3S
Shift and flashes
Modify
Stop flashing
Confirm
Self-check
All LED on
>>
>
>
/AT
Temp. unit
Input type
Current Temp
Preset output value
Max input limit
Min input limit
Power on
-
↓
↓
↓
3S
3S
↓
↓
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
↓
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
OUT1
AT
AL
SET
TA
/AT
PV
SV
>>
>
>
>>
OUT2/AL2
Mounting and Sizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
G
H
Sizes
Model
TA4
TA6
TA9
TA7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
67.5+0.5 67.5+0.5 95 95 72 72 12 100
91+0.5 91+0.5 115 115 96 96 12 100
A B C D E F G H
TA8
91+0.5 43.5+0.5 65 115 96 48 12 80
F
+
↑
↑
↑