BEL LBM Series - Battery Charger Installation guide

Type
Installation guide
MODELS:
LBM10000-1110Sxxx
LBM12000-1110Sxxx
LBM15000-1110Sxxx
AC INPUT:
3 PHASE
VOLTAGE: 230-277 / 400-480 Vac 3W + PE
CURRENT: 18-12 A (LBM10000)
CURRENT: 21-14 A (LBM12000)
CURRENT: 26-18 A (LBM15000)
FREQUENCY: 50 / 60 Hz
DC OUTPUT:
VOLTAGE: adjustable 80 140 Vdc
CURRENT: max. 91 A @ 110 V (10000 W)
CURRENT: max. 110 A @ 110 V (12000 W)
CURRENT: max. 137 A @ 110 V (15000 W)
SAFETY APPROVALS
pending
pending
CAUTION
These component level power supplies are intended exclusively for installation within other equipment by an industrial assembly operation or by
professional installers. These are Class 1 power supplies; the unit must be properly connected to earth ground in end use. A component power supply
should be installed in end-use equipment according to the requirements of the safety standard used for that equipment. This power supply is not designed
to be operated outside of an enclosure which provides a means of mechanical, electrical, and fire protection.
PROTECTIVE EARTHING
The Power Supply must be properly grounded to mains protective earth termination at end use.
ENVIRONMENTAL CONDITIONS:
TRANSPORTATION & STORAGE:
Ambient Temperature Range -40 °C to +85 °C
Relative Humidity Range: 0% to 95% RH Non-Condensing
Altitude: to 12192 m asl (40 000 ft)
OPERATION:
Ambient Temp. Range -25°C to +55°C (at 100% load), to +70°C (at 75% load)
Relative Humidity Range: 0% to 95% RH Non-Condensing
Altitude (asl): to 2500 m (8200 ft) full power, to 5000 m (16 400 ft) derating 80% of full power
DISCLAIMER
It is the customer’s responsibility to check the suitability and qualify the product in their application. If any queries, please contact Bel
(at tech.support@psbel.com or website belfuse.com/home/contact-bel) to ensure product remains within specification at all time.
Supplier shall in no way be liable for use or installation of the product outside of the parameters of the specification.
INSTALLATION REQUIREMENTS
Hardware:
Recommended power wires dimensions you can find in charts below. The mate parts of connectors are also described below. For the air inlet
there is required to maintain a minimum open space 15 cm, for the output min. 10 cm. For chassis fastening you will need 4x screws M10. The preferred
mounting position is vertical, with connectors on top. The AC input line shall be fused by: Breaker ABB, S203MT, C30/C25, or similar. The output Battery
must be protected by following fusing: Breaker ABB 1SDA066809R1 (160/125/100 Adc), or similar. We highly recommend using fuses, e.g. 1 A / F, in series
with inputs 1, 2, 3, 4 of connector X3 (battery sections sensing).
Software:
In case the standard units are delivered to the customer with the Configuration file (.csv) in default (factory) settings, it is necessary for the
customer to upgrade the Configuration file (by the help of GUI graphical user interface) to the version, which corresponds with their specific project. The
same needs to be done, if the units are returned from the repair (RMA), since the units are shipped back to the customer with default Configuration setting.
WARNING
1. The equipment is for business use (Class A) and has acquired electromagnetic conformity registration. This product may cause interference if used
in residential areas. Such use must be avoided unless the user takes special measures to reduce electromagnetic emissions to prevent interference
to the reception of radio and television broadcasts.
2. Maximal Touch current measured according to IEC 62368-1 is 6.5 mA.
Except of connector X1 ground wire use also an additional grounding wire connected on the grounding screw on the chassis.
3. Maximal value of the Protective conductor current (leakage current) is 9.9 mA.
4. Do not touch the Output connector X2 during the operation. There is a hazard voltage present, up to 140 Vdc.
5. Caution, this is a heavy equipment, weight 17.5 kg.
SAFETY INSTRUCTIONS
Switch off the input power and disconnect battery (X2) together with connector X3, X1 and wait min. 2 minutes before doing any maintenance on the unit!
Do not turn-on the unit with removed mate part of the X2 connector!
2
INSTALLATION INSTRUCTIONS
SERVICING
In case of failure, the unit must be returned to the Bel Power Solutions Authorized Service Center. There are no user serviceable parts inside, except of the
fan replacement. In case of failure of the fan this can be replaced without the whole chassis opening. The procedure is described below.
CORROSION PROTECTION
The unit outside is protected by painting with Durpol epoxide 6L series, RAL9005. Inside all PC boards are protected by lacquering with AVR 80.
LIMITED WARRANTY
Bel Power Solutions warrants each power supply of its manufacture for a period of two years from the date of original shipment. This warranty applies to
defects in materials and workmanship that result in non-performance to published specifications. The product(s) must be returned to a Bel Power Solutions
Authorized Service Center for repair with a Bel Power Solutions pre-assigned RMA number.
Bel Power Solutions assumes no liabilities for consequential damages of any kind through the use or misuse of its products by any user. No other obligations
are expressed or implied. Please note that the specifications, terms, and conditions stated are subject to change without notice.
MAINTENANCE - FAN REPLACEMENT PROCEDURE
In the unit there are no user replaceable parts, except of the fans. Fan failure is reported in data sent to the train control unit.
In case of regular maintenance or fan failure, the front panel with fans (Bel order Nr. YGA.F0G03.0, 1.2kg) can be simply removed for cleaning / replacement:
1) Turn-off the charger (disconnect AC and battery), wait min. 2 minutes after the unit completely shuts down. By the hand simply unscrew the six
screws holding the panel (signed by the red circles see Fig. 1 below) and pull out the panel from the chassis.
2) Replace the whole panel with the original part YGA.F0G03.0. Contact our Sales Center for the part order.
3) Proceed with the mounting in reverse order. Gently push the new panel straight in the chassis. By screws tightening first push on the screws
and at the same time twist them clockwise (by hand).
The panel with fans contains also the addresses for power modules, so do not exchange the positions of fans.
Life expectance: 70 000 hours @ 40 °C, continuous operation (8.0 years or 2.4 mil km, whichever occurs first). This value can be added in the regular
maintenance scheduler of the vehicle (W-class C). For cleaning and checking (outside the chassis) use a shorter period, depending on the pollution of the
flowing air and if Tamb > 40°C.
Figure 1: Area of maintenance and Fans replacement screws to release at YGA.F0G03.0
NUCLEAR AND MEDICAL APPLICATIONS
Bel Power Solutions products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in
hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Bel Power Solutions.
TECHNICAL REVISIONS
The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are
subject to change without notice.
OPERATION
Before turning-on the charger make sure the pins 7, 8 of connector X3 are outside reconnected (by a wire jumper >0.5mm², or by a switch / relay). This
jumper can be used for a complete disconnection of the charger controller from battery (if AC is not present and the battery breaker remains still in ON
position), to minimize the battery discharging when the train is out of service for a long time, more than one week. Note that only the controller power
supply will be disconnected, not the battery power input. So, in this case battery will be still connected to consumers, but the charger controller will not
work. In the case pins 7, 8 are disconnected, the AC must not be present, because the power modules would deliver power (in Safe mode), but the battery
charging current would be not controlled!
It is recommended first turn-on the battery breaker and only then turn-on the AC input voltage breaker. The charger will start in a Safe mode = constant
voltage, e. g. 105 Vdc, the value is configurable. In this state the current into Consumer output will flow either from charger or from battery, which one of
the voltages will be higher.
30 seconds after the first AC start-up the charger performs the battery test, by decreasing the output voltage. During battery test the output voltage can go
down to 80 V, if the battery is not connected. In this case, after the test, the charger will remain in the Safe mode. In the other case (battery connected /
OK), or if the battery will be connected afterwards, the charger will start to work in a Charge mode, to keep the maximal charging current and to supply the
consumers. The voltage will be set to value which corresponds to the measured battery temperature (battery charge curve). The actual state can be seen
by LED-s on the connector panel or by communication SW / GUI. For the LED-s meaning and for details see the Datasheet BCD.20200.
LBM Series
3
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
© 2023 Bel Fuse Inc.
BCM.20061_2
When no temperature sensor is connected to the connector X7 (and no temp. value from the superior system will be available), or any other fail will be
detected, the charger will remain to work in the Safe mode. In this mode the output voltage is set below the value allowed for Tmax (specific charging
curve dependent), e. g. to 105 Vdc. If this mode will remain for longer time, please note that the battery will be not fully charged. When no battery voltage
sensing is connected to the connector X3, the charger will also stay in the Safe mode and the battery voltage symmetry cannot be evaluated and reported
by communication. All error conditions are reported to the parent system.
The charger does not have the possibility to disconnect the battery if battery undervoltage occurs (e. g. without AC, when the load is supplied from battery
only). So, the battery undervoltage must be controlled externally and when it happens, the consumers must be disconnected (the typical turn-off should be
under 80 V, the value depends on battery type).
Inside, in series with the Consumer output, there is connected an OR-ing diode (MOSFET), so two or more LBM systems (preferably each one with his own
separate battery pack) can be at these outputs connected in parallel (to supply the load in redundancy, if the size of the load was chosen appropriately).
In the case more BC are working in parallel in one battery or when the connection to battery is long (more than 3m), please contact the Bel support to
agree the details of the installation.
This equipment can be (AC) powered by a generator in the vehicle, or by public grid while train in the depot. The charger complies with IEC 61000-3-12
provided that the short-circuit power Ssc is greater than or equal to 2,9x106 at the interface point between the user’s supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 2,9x106.
Figure 2: Connectors placement
INPUT AC CONNECTOR X1 PINOUT
SIGNAL NAME
PIN #
TYPE
RECOMMENDED WIRES
V MAX
I MAX
Earth
Earth / Chassis
6 mm2
528 Vrms (line to line)
26/21/18 Arms (per line)
AC Line 1
L1
Input Power AC Fused
6 mm2
AC Line 2
L2
Input Power AC Fused
6 mm2
AC Line 3
L3
Input Power AC Fused
6 mm2
Connector type:
DFK-PC16/4-STF-10,16 - 1703470 (Phoenix Contact)
Mating part:
PC16/4-STF-10,16 - 1967472 (Phoenix Contact), torque 1.7-1.8 Nm
Nr. of cycles: 50
OUTPUT and BATTERY CONNECTOR X2 - PINOUT
SIGNAL NAME
PIN #
TYPE
RECOMMENDED WIRES
V MAX
I MAX
CONSUMER +
1, 2
Output Power DC
2x 16 mm2
140 VDC,
137/110/91 A
BATTERY +
3, 4
Output Power DC
2x 16 mm2
COMMON -
5, 6
Output Power DC_return
Isolated from Earth
2x 16 mm2
Connector type:
PC35HC/6-GF-15,00 - 1762783 (Phoenix Contact)
Mating part:
PC35HC/6-STF-15,00 - 1762631(Phoenix Contact), torque 25mm² = 2.5 Nm; >25mm² = 4.5 Nm
Nr. of cycles: 50
NOTE: Do not apply excessive forces on the connector, do not bend the wires close to the connector, keep the required torque!
4
INSTALLATION INSTRUCTIONS
SIGNAL CONNECTOR X3 PINOUT
SIGNAL NAME
PIN #
TYPE
SIGNAL
REFERENCE
LOW LEVEL
HIGH LEVEL
V MAX
I MAX
VBsense1
1
Battery Voltage Sense 1 ***
GRD
0 - 140 V
140 V
VBsense2
2
Battery Voltage Sense 2 ***
GRD
0 - 105 V
140 V
VBsense3
3
Battery Voltage Sense 3 ***
GRD
0 - 70 V
140 V
VBsense4
4
Battery Voltage Sense 4 ***
GRD
0 - 35 V
140 V
GRD
5
Return
Isolated from Common -
N.C.
6
Vaux_in
7
Controller supplying
Common -
140 V
+110Vdc
8
Battery voltage input connected internally
Common -
140 V
Common -
9
Return ****
ADR0
10
Unit Address 0 *, floating = 0 **
Common -
< 12 V / > 80 V
140 V
ADR1
11
Unit Address 1 *, floating = 0 **
Common -
< 12 V / > 80 V
140 V
INH_IN
12
Inhibit input *, floating = 0 **
Common -
< 12 V / > 80 V
140 V
P_LIM
13
Power Limitation *, floating = 0 **
Common -
< 12 V / > 80 V
140 V
FA
14
Output floating relay contact (normally open)
Open when in fault condition *
0.4A@140Vdc
FB
15
Connector type: MSTB2.5/15-GF - 1776825 (Phoenix Contact)
Mating part: MSTB2.5/15-STF - 1786967 or FKCN2.5/15-STF - 1733084 (Phoenix Contact), wires max. 2.5 mm2, torque max. 0.6 Nm
* defined by the Configuration file (a part of the firmware)
** for log.1 connect by a jumper/relay the relevant pin to pin 1, VBsense1 (where the BAT+ is connected)
*** for a description of the connection to battery see Fig.8 in the Datasheet BCD.20200
**** connected internally to Common- via a PTC resistor, not necessary to connect externally
ETHERNET CONNECTOR X4 PINOUT
SIGNAL NAME
PIN #
TYPE
SIGNAL REFERENCE
NOTE
V MAX
I MAX
TxData+
1
Communication Data
10/100 Mbit
RxData+
2
Communication Data
10/100 Mbit
TxData-
3
Communication Data
10/100 Mbit
RxData-
4
Communication Data
10/100 Mbit
Connector type:
4-pin M12 D-coded - 1534630 (Phoenix Contact)
Mating part:
4-pin M12 D-coded - 1521258 (Phoenix Contact)
CAN-BUS CONNECTOR X5, X6 PINOUT
SIGNAL NAME
PIN #
TYPE
SIGNAL REFERENCE
NOTE
V MAX
I MAX
CAN +
7
Communication Data
CAN-
250 kbit *
CAN -
2
Communication Data
CAN+
250 kbit *
GRC
3
Power Supply_Return
Isolated from Common -
Do not use-only for servicing
+5V
9
Power Supply
GRC
Do not use-only for servicing
5.5V / 100 mA
Connector type:
X5: 9-pin D-SUB male (Amphenol) X6: 9-pin D-SUB female (Amphenol)
Mating part:
9-pin D-SUB female / male
* defined by the Configuration file
NOTE: CAN and Ethernet (TRDP) communication commands are described in a separate document Communication Interface.
LBM Series
5
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
© 2023 Bel Fuse Inc.
BCM.20061_2
SIGNAL CONNECTOR X7 PINOUT
SIGNAL NAME
PIN #
TYPE
SIGNAL REFERENCE
NOTE
V MAX
I MAX
TB1H
1
Temperature sensor 1 High
TB1L
For 103AT-11, Semitec *
3.3 V
TB1L
2
Temperature sensor 1 Low
3.3 V
TB2H
3
Temperature sensor 2 High
TB2L
For 103AT-11, Semitec *
3.3 V
TB2L
4
Temperature sensor 2 Low
3.3 V
N.C.
5
Common -
6
Can be used to connect the
cable shielding
Do not connect the cable
shielding to earth (chassis)
Figure 3: Output voltage characteristic (model 12/15kW)
6
INSTALLATION INSTRUCTIONS
MECHANICAL DIMENSIONS
Figure 4: Main dimensions with bent holders (standard)
Figure 5: Main dimensions with flat holders (optional). The second fixation option requires to unmount the BC before replacing the fans
LBM Series
7
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
© 2023 Bel Fuse Inc.
BCM.20061_2
MOUNTING REQUIREMENTS
The four holders and related screws are placed separately in the package. Please, mount them on the chassis, to the desired position as shown in Fig. 4
or 5 above. It is necessary to use only the original screws (or new screws of the same length as the original !)
Recommended tightening torque min. 40 Nm.
Charger shall be mounted securely on the supporting frame by all 4pcs of holders, by self-locking screws. Mounting holders are designed to support
charger only and cannot be used to support other assemblies. The charger can be installed vertically on the wall or horizontally, by keeping minimal 10
cm of free space around all ventilation openings and at least 15 cm of free space for fans panel replacement. It can be mounted also in a 19” rack, size
3U. Recommended mounting screws are M10 with washer, Bossard 1001361 and 1729314 (not included). Recommended tightening torque 40 Nm.
BC weight: 17.5 kg
Figure 6: The possible mounting positions and distances from the surroundings
g
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

BEL LBM Series - Battery Charger Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI