INSTALLATION AND MAINTENANCE INSTRUCTIONS
MAGDUOCPIP65 MAGDUO Manual Call Point IP65
General Description
The MAGDUO Manual Call Point (MCP) allows for user
activation of the fire alarm system. Once operated the
device latches into the alarm position and requires
manually resetting via a special key. This device is
compatible with the MAGDUO 2-wire Fire Alarm Control
Panel and comprises a 2-wire zone-powered MCP. This
device may be installed on the same zone as the MAGDUO
FlexiPoint detector/sounder and other associated
MAGDUO devices. An optional clear front cover is available
if required.
Before Installation
The MCP must be installed in compliance with the control panel installation manual. The installation must also
meet the requirements of any local authority. For maximum performance the MCP should be installed in
compliance with BS5839 Pt1 : 2017.
Spacing
It is recommended spacing of call points in accordance with BS5839 Pt1. For more specific information
regarding MCP spacing, placement and special applications please refer to BS5839 Pt1 : 2017.
Device Installation
All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2017 as well as
any special recommendations documented in the control panel installation manual. The cabling used should be
of a 2-core 1.5mm
2
screened, fire resistant type (e.g. MICC or FP200 equivalent), and is to be wired in the form
of a screened 2-core radial circuit (with no spurs) from the control panel, terminating at the last (“End of Line”)
device.
Fix the wall mounting plate in a suitable position using the holes / slots. Drill out 20mm holes in back box in the
required positions for cable glands.
Note: Holes must be clean and free of burrs and surface imperfections. This is critical for seal integrity. IP68
cable glands suitable for cable diameter used must be fitted in accordance with manufacturer’s instructions to
maintain the IP rating of the unit.
Fit the back box onto the wall mounting plate and terminate site cables into the connectors, as shown overleaf.
Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections are
secure. Improper connections will prevent a system from responding properly in the event of a fire.
Please remember that all high voltage testing must be carried out before the installation of the MCP front unit
otherwise the electronics will be damaged. Once all testing has been carried out on the cabling and continuity
& insulation has been proven, the MCP can be connected.
Connect the wires from the MCP front into the appropriate terminals in the back box according to the wire
colours. The MCP front can then be fitted by pushing the front Interface Plate onto the back box and tightening
the four long fixing screws, before locating the upper mounting hook of the MCP front unit onto Interface Plate
and then pushing the unit gently home. The single fixing screw may then be tightened.
https://www.espuk.com/technical_support/
product_manuals/?cat=4
26-1660-01
Connections
MAGDUO MCPs can be mixed on the same zone as other types of MAGDUO device. The above diagram
shows how to make the zone positive, zone negative and screen connections between the control panel and
MAGDUO MCPs. Refer to the instruction leaflets supplied with other MAGDUO devices for their equivalent
wiring/terminal labelling details.
Please note that the E terminal on the Call Points should only be connected to the zone cable screen and
NOT to the building earth. The cable screen is connected to earth at the panel end only, via the zone
“SCRN” terminal (or EARTH terminal on the MAGDUO panel). It is important to maintain the screen
continuity in order to protect against data corruption from interference.
Remember that the device at the end of the line must have its EOL signal activated using the
relevant EOL switch. Do not use a resistor or capacitor (or another manufacturer’s End of
Line device) as the end of line, as this may prevent correct operation of the zone.
Reset and Test
The MCP contains a re-settable element, which latches in position when operated and
does not need to be replaced. Inserting the key as shown and turning it clockwise until the
element clicks back into place will reset the unit. Testing the MCP may be carried out
either by pressing the element or by using the key in the same manner as for resetting but
without having pressed the element.
B
E Y
R
26-1660-01
MCP DIL Switch Settings
The last device on the circuit must have its EOL signal enabled. Remove the cover as shown, then locate the
switch and set it to ‘ON’.
1)
2)
3)
Technical Data
Dimensions Width x Height ....................................... 87mm x 87mm
Depth ...................................................... 70mm
Operating Temperature . ................................................................ -10
o
C to +50
o
C.
Voltage Ranges DC Output from Mains Powered Panel. .. 25.5 to 35V DC
DC Output from Battery Powered Panel. 20 to 26V DC
Operating Current (Typical) Quiescent ................................................ 50 uA
End of line ON if applicable ..................... 720 uA
(in addition to Quiescent)
Alarm Activated ....................................... 16.5 mA
LED Operation Alarm Indication ....................................... Pulsed twice per second
EOL indication ......................................... 5 second interval
Loading Units
Max Loading Units per zone ................... 160 DLU
MCP......................................................... 16.0 DLU
Flammability ................................................................. UL94-V2
IP Rating ................................................................. IP 65
Part Code ................................................................. MAGDUOCPIP65
SWITCH OFF
SWITCH ON
O N
1
26-1660-01
Essential characteristics
Performance
Nominal activation conditions/Sensitivity,
Response delay (response time) and
performance under fire conditions
Pass
Operational reliability
Pass
Tolerance to supply voltage
Pass
Durability of operational reliability and
response delay, Temperature resistance
Pass
Durability of operational reliability,
Vibration resistance
Pass
Durability of operational reliability,
Humidity resistance
Pass
Durability of operational reliability,
Corrosion resistance
Pass
Durability of operational reliability,
Electrical stability
Pass
Technical Support
Due to the complexity and inherent importance of a life risk type
system, training on this equipment is essential, and
commissioning should only be carried out by competent
persons.
ESP’s policy is one of continual improvement and the right to
change a specification at any time without notice is reserved.
Whilst every care has been taken to ensure that the contents of
this document are correct at time of publication, ESP shall be
under no liability whatsoever in respect of such contents. E&OE.