  • Hello! I am an AI chatbot trained to assist you with the PVI Industries PV500-43 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 1 7/10
Setup Manual
BACnet Protocol Gateway for TempTrac
®
and
XR10CX Water Heater Control
WhenaBASinterfacewithTemptracortheXR10CXrequiresaprotocolotherthanthestandard
ModbusRTUforTemptracandXR10CX,PVIIndustriesoffersapremappedgatewayfromFieldServer
Technologies.TheProtoCessorProtoNodeRERcurrentlysupportsBACnetIPorMSTP.Consultfactory
forotherprotocols.
Thismanualismeant
tobeageneraloverviewoftheapplicationofthisgateway,foradditional
informationpleasevisit:www.protocessor.comorcontactFieldServerTechnologiesat8003178319
Email:[email protected]fortechnicalassistance.TheProtoCessorProtoNodecanbeuser
configuredwiththefollowingspecifics:IPaddress,serialaddress,baudrateandoneof
threeregister
profiles.
RS485portforHost
orFieldserial
protocolsupport
Ethernetportfor
DiagnosticsandHostor
FieldProtocolsupport
6PinRS485+/‐andFG
Power+/‐andFG5Vdc,930
VacorVdc
Dipswitches
HARDWARE DISCRIPTIO
N
Voltage
selection
jumper
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 2 7/10
Note:WiringfortheRS485serialnetworkshouldbemadeina“daisychained”2wireshielded/twistedpair.
Protonode
+‐GNDRCGND
XR10CX
TempTrac
COMMON/SHIELD
LT
+
RS485+
/
‐
Power5Vdc,930
VacorVdc
+
XJ485SERIALINTERFACE
Optionalserialcablemustbe
orderedwiththeheater.
PREINSTALLEDTERMINATION
OPTIONALFIELDINSTALLED
TERMINATIONRESISTOR
ModbusRTU
BACnetIP/MSTP
SYSTEM OVERVIEW TEMPTRAC & XR10C
X
XR10CX
OPERATINGCONTROL
TEMPTRAC
OPERATINGCONTROL
BUILDING
AUTOMATIONSYSTEM
BACnetGATEWAY
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 3 7/10
DipswitchesA0toA7configuretheserialaddress.Thetablebelowliststhesettingsupto10.Thefull
257addresssettingscanbefoundinthePr otoCessor GettingStarted(T17007)manualat
www.protocessor.com
DipswitchesB0toB3configurebaudrate.
Thetablebelowlists thesettings.
Dip
switchesS0toS3selecttheregisterprofiletobeused.When
switchS0isOntheregisterprofilewillonlymoni toronecontrol
withannodeaddressof1.Allregistersareanalog/16bit.
WhenswitchS0isOffandS1isOntheregisterprofilewillmonitor
upto
8controls.Theregisteraddressesaredetailedbelow.The
respectivenodeaddressesare1to8.
A7 A6 A5 A4 A3 A2 A1 A0 Address
Off Off Off Off Off Off Off Off 0
Off Off Off Off Off Off Off On 1
Off Off Off Off Off Off On Off 2
Off Off Off Off Off Off On On 3
Off Off Off Off Off On Off Off 4
Off Off Off Off Off On Off On 5
Off Off Off Off Off On On Off 6
Off Off Off Off Off On On On 7
Off Off Off Off On Off Off Off 8
Off Off Off Off On Off Off On 9
Off Off Off Off On Off On Off 10
Baud B3 B2 B1 B0
Auto3 Off Off Off Off
110 Off Off Off On
300 Off Off On Off
600 Off Off On On
1200 Off On Off Off
2400 Off On Off On
4800 Off On On Off
9600 Off On On On
19200 On Off Off Off
20833 On Off Off On
28800 On Off On Off
38400 On Off On On
57600 On On Off Off
76800 On On Off On
115200 On On On Off
Control Discription Modbus
Address
BACnet
Address
Temptrac SetPoint Read/Write 40769 1
Temptrac Temp. Probe1 ReadOnly 40257 90
Temptrac Temp. Probe2 ReadOnly 40259 91
Temptrac Temp. Probe3 ReadOnly 40261 92
Temptrac On/OffEnable Read/Write 401281 95
XR10CX Temp. Probe1 ReadOnly 40257 90
XR10CX SetPointRead/Write 40854 101
CONFIGURATION SETTINGS TEMPTRAC & X
R
10C
X
Off‐‐‐On
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 4 7/10
PowerLEDcomesonandremains solid
LAstartsflashingaboutoncepersecond.ThistellsusthatPIC(PeripheralInterfaceController)
number1intheProtoCessorhaspoweredupsuccessfully.
LBstartsflashingaboutoncepersecond.ThistellsusthatPICnumber2intheProtoCessor
has
poweredupsuccessfully.
GP105willgoonsolidwithin4560secondsafterpowerup,signifyingnormaloperation.
ProtoCessorwillbeabletocomeupinRUINETshortlyafterthisLEDcomeson.Duringthefirst
4560secondstheLEDshouldbedark.
Uponsuccessful
operationofGP105theProtoCessorwillgothroughdiagnosticsofthefieldport
communications.
TheFFPETHmoduleisoperationalafterthispoint.
RXFieldPortLED:Onnormaloperation,theRXLEDwillflashwhenamessageisreceivedonthe
fieldportoftheProtoCessor.
TXFieldPortLED:Onnormaloperation,theTXLEDwillflashwhenamessageissentonthefield
portoftheProtoCessor.
POWERING UP THE PROTOCESSOR/PROTONOD
E
PWR
GP105
LB
TX
RX
LA
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 5 7/10
MakesurethattheFSTUtilitiesisdownloadedonthecomputer.
(http://fieldserver.com/techsupport/utility/utility.p hp
)
ConnectanEthernetcrossovercablebetweenthePCandProtoCessororconnectthe
ProtoCessorandthePCtotheHub/switchusingastraightcat5cable.
TheDefaultIPAddressoftheProtoCessoris192.168.1.24,SubnetMaskis255.255.255.0.
IfthePCandtheProtoCessorare
ondifferentIPNetworks,assignaStaticIPAddresstothePC
onthe192.168.1.0network.
Doubleclickonthe“RUIPING”Utility.IftheIPAddressoftheProtoCessormoduleappearson
thescreen,theProtoCessorisrunning.
CONNECTION TO PROTOCESSOR USING UTILITIE
S
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 6 7/10
Doubleclickonthedebuggingutility,“RUINET4”(RemoteUserInterface).Thefollowingscreen
willappear:
Seethe“ProtoCessorMapping”documenttoensurethatthedeviceissetupcorrectlywith
respecttoBaudrate,NodeAddress,andPointswhichareconfiguredinthedevice.
Select“O”forConnectOverviewtoseethenumberofmessagesoneachprotocol.Ifthe
ProtoCessoriscommunicating
correctlywiththedevicethenthedisplaywillshowTxandRx
messageswithoutanyerrors.
IfthereareerrorsontheProtoCessorsocketcommunications,thenthepointslistintheCSVfile
willrequireeditinguntiltherearenoerrors.Eachtimethepointsareedited,theCSVwill
need
toberedownloadedusingRuinet.
WhencommunicationbetweenthedeviceandtheProtoCessorisestablishedtheFieldSideof
theProtoCessormaybeconnectedtotheappropriatedevice/software.EnsurethattheField
Sideparametersonthedevice/softwarearesetupasperthe“ProtoCessorMapping”
document.
ReadandWritedatafromeachsideandmakesuretheProtoCessorworksasexpected.
PV500-43
PVIIndustries,LLCP.O.Box7124Ft.Worth,TX7611118004335654Page | 7 7/10
IfPWRLEDdoesnotcomeonandLAandLBdon’tflash,calloremailProtoCessorsupport
IfPWRLEDdoesnotcomeonbuttheLAandLBflash,thenthePWRLEDisbr oken.
IfLAandLBdon’tstarttoflashtherecould
beaproblemwiththeProtoCessorandyouneedto
contact[email protected].
IfGP105nevercomesonthenyouneedtocontactProtoCessorsupport.
IfTXandorRXdon’tflash,itmayrepresentaproblemwiththefieldwiringorConfiguration
problemsintheProtoCessoronfield
sideorincorrectpollingparameters(suchasCOMM
propertieslikebaud,parity,andetc).
TheGatewayisunabletofindoneormorecontrolsintheRS485network.Theindividual
controlsmaynotbeprogrammedwiththecorrectanduniquenodeaddress.Seetherespective
controlmanualfordetails.
TheGatewayhasnocomm unicationwiththecontrolsintheRS485network.ChecktheRS485
wiringforcorrectwiringmethod.Seepage2ofthismanual fordetails.
MoreinformationfortheProtoCessor/ProtoNodecanbefoundat:Web:www.protocessor.com
FieldServerTechnologies,1991TarobCourt,Milpitas,California95035
USA
Tel:4089644433,FAX:4082629042,TollFree:8003178319Email:[email protected] o m
TROUBLESHOOTING TIP
/