Hager EG 470 User Instruction

Type
User Instruction
4 channels time switch -
weekly cycle
User instruction
GB
on
auto
off
B
A
C
D
Prog
Auto
A
B
C
D
reset
7
6
1234
5
enter
on/offclear
+
ON OFF
ON OFF
ON OFF
ON OFF
EG 470
Working principle :
The EG 470 is a time switch for the auto-
matic control of electrical loads.
It is fully programmable with a maximum
of 84 program steps to be divided bet-
ween the four channels. Each program
step can be applied to one or several
days, maximising the use of each memo-
ry location.
An input lets you simultaneously force
the 4 channels to OFF.
The front cover is sealable preventing
unauthorised access after completion of
programming.
Warning : at the beginning of use, please
reset the device in order to clear the
memory before programming.
This is achieved by using a pen to push
the reset button.
Presentation :
Display :
time
circuit status of channels A, B, C and D
(ON or OFF)
Indication of manual override on
channels A, B, C and D.
day of the week
(1 = Monday, 2 = Tuesday ....)
Indicator of operating mode :
time setting
prog programming mode
for channels A, B, C and D
auto running mode
timed override.
Buttons :
Manual selector to override channels
A B, C and D.
1 to 7 selection of the days
clear : to delete a program step.
on/off: chooses whether the circuit
is on or off
+ and - : changes settings
: to select the operating mode
(time setting, programming, running
mode or override)
enter: to confirm
reset
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
ON OFF
ON OFF
ON OFF
ON OFF
1
5
4
7
2
3
13
8 9
10 11 12
6
B
A
C
D
A
B
C
D
11
13
12
Time and day setting :
1. Press the key repeatedly to place the cursor
below
2. Select with key 1 to 7 , the actual day
(1 = Monday, 2 = Tuesday .)
3. Input time with buttons + and -.
Programming channel A :
1. Press the key repeatedly to place the cursor
below prog for channel A.
2. Select with keys 1 to 7 the day(s) assigned to
this program step. An arrow appears above each
day selected.
3. Input switching time with buttons + and -.
4. Input the type of switching with button on/off
(for the first action ON is automatically proposed).
5. Enter this program step with button enter.
Program additional time settings by repeating steps
2 to 5..
Programming channels B, C and D :
Press key to place the cursor below progfor
channels B, C or D.
Same way of programming as channel A.
Running Auto mode
The switch to automatic mode is made automati-
cally if no key is pressed for 2 minutes.
You can also select the automode by pressing
the key to place the cursor below auto.
This mode is the current displaying mode.
Display of the time, the day and the state of the
four channels.
This mode does not allow any modification, except
the winter / summer time change.
Press key + or - and confirm with enter.
reset
76
12345
enteron/offclear on auto off
B
A
C
D
Prog
Auto
A
B
C
D
+
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
ON
B
A
C
D
A
B
C
D
To check your program on channels A,
B, C or D :
1. Press the key repeatedly to place the
cursor below prog for channel A, B, C or D.
2. Press the key enter repeatedly to display
the different program steps (switching
time, days of the week and state of the
channel ON or OFF).
To override the output :
Permanent override :
The 3 position selector (on - auto - off) for channels
A, B, C or D allows in automatic mode the output to
be overriden ON or OFF.
1. Move the 3 position selector for channels
A, B, C or D to ONor OFF
2. A cursor on the display (in front of
channels A, B, C or D) indicates the
permanent override.
To switch back to automatic mode, move the
selector to auto.
To modify or delete a program
step on channels A, B, C or D :
1. Press the key repeatedly to place the
cursor below prog for channel A, B, C or D.
2. Press the key enterrepeatedly to select
the program step to modify or to delete.
3. Modify :
- switching time with keys +or -
- days assigned with keys 1 to 7.
- state of the channel with key on/off.
To delete a program step, press clear.
4. press enter to confirm.
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
ON
OFF
ON
ON
B
A
C
D
A
B
C
D
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
ON
B
A
C
D
A
B
C
D
6E 6133.b
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manu-
facturing defect. If any product is found to be defective it must
be returned via the installer and supplier (wholesaler). The
warranty is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry
at the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning
goods.
Warranty
GB
The override duration is adjustable from 1 hour to
47 hours by steps of 1 hour then from 2 to 99 days
by steps of 1 day.
The temporary override time period can be different
on each channel.
1. Press the key repeatedly to place the
cursor below for channel A.
2. Input with keys +or. -the override
duration.
3. Select the state of the output with key
on/off.
4. Confirm with enter.
1. Press the key repeatedly to place the
cursor below for channel A, B, C or D.
2. Press clearto cancel the timed override.
3. Press the key repeatedly to place the
cursor below auto and switch back to
automatic mode.
Timed override :
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
ON
B
A
C
D
A
B
C
D
reset
76
12345
enteron/offclear on auto off
Prog
Auto
+
OFF
B
A
C
D
A
B
C
D
To cancel the timed override on channels A, B, C
or D :
Temporary override on channel A.
1. Press the key repeatedly to place the
cursor below for channels B, C or D.
2. Use the same process as for channel A.
3. Press the key repeatedly to place the
cursor below autoand switch back to
automatic mode.
The channel cursor flashes to indicate that a timed
override has been programmed. After the duration,
the program will resume its
normal course.
Temporary override on channels B, C or D.
345621
L
N
EG 470
14 15
789
18 19
A
A,B,C,D
C
11 12 13
B
10
D
16 17
OFF
20
Technical specifications :
Electrical characteristics :
- supply voltage : 230V ±15% 50/60 Hz
- outputs : 4 changeovers contact
µ 16 A - 250 V AC1
µ 3 A - 250 V cos = 0.6
1000 W incandescent lighting
- power consumption : 20 VA
- protection degree : IP20
- insulation class : II
Functional characteristics :
- accuracy : ± 1sec. / day at 20 °C
- operating reserve : lithium battery,
total of five years.
Environment :
Operating temperature : -10 to +50 °C
Storage temperature : -20 to +60 °C
Connection tunnel terminals :
flexible : 0,5 to 2,5 mm
2
rigid : 0,5 to 4 mm
2
Dimensions : 5 modules
Electrical connections :
To reset the time switch :
Press reset to clear the program.
External input for off override :
This external input lets you simultaneously force off
all 4 channels.
To activate this input, just connect the 230V phase
supply to terminal 20.