Emerson S Series Gas Pressure Regulator User manual

Type
User manual

Emerson S Series Gas Pressure Regulator offers precise pressure regulation and stabilization for medium and low-pressure gas systems. Ideal for residential, commercial, and industrial applications, it ensures steady gas flow for direct combustion equipment, gas pipelines, and more. With pressure ranges from 1.5 to 50 KPa and various actuator and spring options, you can customize it to your specific needs.

Emerson S Series Gas Pressure Regulator offers precise pressure regulation and stabilization for medium and low-pressure gas systems. Ideal for residential, commercial, and industrial applications, it ensures steady gas flow for direct combustion equipment, gas pipelines, and more. With pressure ranges from 1.5 to 50 KPa and various actuator and spring options, you can customize it to your specific needs.

S Series
Gas Pressure Regulator
Instruction Manual
D104538X012
April 2022
S Series
22
!
WARNING
Contents
1. Introduction ................................................................................................. 3
2.  Specications ............................................................................................... 3
3. Main Valve Dimensions and Weights ............................................................ 3
4. Structure and Principle of Operation ............................................................. 4
5. Selection of Actuators and Springs ............................................................... 4
6. Flow Table .................................................................................................... 5
7. Installation and Use ...................................................................................... 6
8. Pressure Regulator Maintenance ................................................................... 7
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, re
and/or chemical contamination causing property damage and personal injury or death.
Jeon regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and
regulations and Emerson Process Management Regulator Technologies, Inc. instructions.
If the regulator vents process uid or a leak develops in the system, service to the unit may be required. Failure to correct
trouble could result in a hazardous condition.
Installation, operation and maintenance procedures performed by unqualied personnel may result in improper
adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Call qualied
personnel when installing, operating and maintaining the S series pressure regulator.
S Series
33
P1P2
1. Introduction
The S Series pressure regulator is a spring-loaded direct-acting gas pressure regulator.
Applications: pressure regulation and stabilization of medium and low pressure gas pipeline networks, residential quarters,
industrial and commercial users, and direct combustion equipment.
Applicable medium: natural gas, articial gas, liqueed petroleum gas and other non-corrosive gases.
Example: RTZ1-50/0.4-S
It means that this is an S Pressure Regulator, Direct Operated, Fail Open,
with Body Size DN 50 (Inlet), 0.4 MPa Maximum Inlet Pressure.
Figure
1
2. Specications
Inlet pressure range, P1: 0.02 to 0.4 MPa
Outlet pressure range, P2: 1.5 to 50 KPa (please refer to "5. Selection of Actuators and Springs" for details)
Pressure stabilization accuracy level, AC: up to AC5
Closing pressure level, SG: up to SG10
Working temperature, t:
Nitrile (NBR), Standard: -20 to 60°C / -4 to 140°F
Fluorocarbon (FKM): -10 to 60°C /14 to 140°F
Table 1. Flange Rating
TYPE INLET AND OUTLET
FLANGE, DN FLANGE RATING
S50 50
PN1.6 MPa
In line with the
standard HG20592
S65 65
S80 80
S100 100
S150 150
Figure 2
Features
Modular structure design;
Fast response speed and large circulation capacity;
Fully balanced valve core structure, high pressure regulation accuracy;
Simple structure, convenient operation and maintenance.
3. Main Valve Dimensions and Weights
Table 2. Main Valve Dimensions and Weights (Figure 1)
TYPE DIMENSION, mm WEIGHT, kg
L D H1 H2 H3
S50 254 330 / 436 675 580 207 / 213 37
S65 276 436 / 510 660 / 695 565 / 600 190 / 205 45 / 55
S80 298 436 / 510 / 610 685 / 720 / 725 585 / 620 / 625 216 / 223 / 226 52 / 62 / 72
S100 350 436 / 510 / 610 735 / 770 / 775 615 / 650 /655 248 / 255 / 260 61 / 71 / 81
S150 450 436 / 510 / 710 835 / 870 / 875 630 / 665 / 670 278 / 285 / 290 118 / 128 / 152
Note:  Size D is determined by the actuator specications selected for the outlet pressure adjustment range of the pressure regulator, see tables in Section 5.
ADJUSTING SCREW
SPRING COVER
ACTUATOR
VALVE TRIM ASSEMBLY
VALVE BODY
INLET OUTLET
DIAPHRAGM
VALVE STEM
ORIFICE
VALVE DISK SEAL
H1
D
H2
H3
L
Model
Maximum Inlet Pressure, MPa
Nominal Size
Direct Operated Regulator, Fail Open
Gas Pressure Regulator
RT Z1 - / 0.4 - S
S Series
44
4. Structure and Principle of Operation
The S Series pressure regulator is composed of the valve body, valve core assembly, actuator and other parts.
The principle of operation of the pressure regulator (see Figure 2): The outlet pressure of the regulator is set through the
adjusting screw of the main actuator spring. When gas consumption increases at downstream, the outlet pressure, P2 tends
to drop.
This pressure drop is sensed below the main diaphragm, causing the main diaphragm to move down, as a result of the acting
main actuator spring. The main actuator spring overcomes the pressure beneath the diaphragm and pushes the diaphragm
downward, causing the valve disk, which is connected through the stem, to move away from the orice and creates an 
opening. This will allow the gas to ow downstream keeping the outlet pressure constant.
When the amount of gas increases at the downstream of the regulator, the operating process will be in reverse until the
regulator is closed.
5. Selection of Actuators and Springs
ACTUATOR PRESSURE REGULATING
RANGE, KPa
DIAMETER OF SPRING WIRE,
mm SPRING CODE COLOR
SNL436
1.5 - 2.5 4.5 JJJJ43CXT03 Black
2.5 - 4 5.5 JJJJ43CXT04 White
4 - 8 7.0 JJJJ43CXT05 Green
8 - 12 7.5 JJJJ43CXT06 Blue
12 - 15 9.0 JJJJ43CXT07 Red
SNL330 25 - 50 9.0 JJJJ43CXT08 Zinc-coated
6.0 JJJJ43CXT09 Zinc-coated
Table 3. Type S50
ACTUATOR PRESSURE REGULATING
RANGE, KPa
DIAMETER OF SPRING WIRE,
mm SPRING CODE COLOR
SNL510
1.5 - 2.5 6.0 JJJJ44CXT03 Black
2.5 - 4 7.0 JJJJ44CXT04 White
4 - 8 8.0 JJJJ44CXT05 Green
8 - 12 9.0 JJJJ44CXT06 Blue
12 - 15 9.0 JJJJ43CXT07 Red
SNL436 25 - 50 9.0 JJJJ43CXT08 Zinc-coated
6.0 JJJJ43CXT09 Zinc-coated
Table 4. Type S65
ACTUATOR PRESSURE REGULATING
RANGE, KPa
DIAMETER OF SPRING WIRE,
mm SPRING CODE COLOR
SNL610 1.5 - 2.5 6.0 JJJJ45CXT01 Purple
2.5 - 4 8.0 JJJJ45CXT02 Gray
SNL510 4 - 8 8.0 JJJJ44CXT05 Green
8 - 12 9.0 JJJJ44CXT06 Blue
SNL436
12 - 15 9.0 JJJJ43CXT07 Red
25 - 50 9.0 JJJJ43CXT08 Zinc-coated
6.0 JJJJ43CXT09 Zinc-coated
Table 5. Types S80 and S100
ACTUATOR PRESSURE REGULATING
RANGE, KPa
DIAMETER OF SPRING WIRE,
mm SPRING CODE COLOR
SNL710 1.5 - 2.5 7.0 JJJJ46CXT02 Red
2.5 - 4 8.0 JJJJ46CXT03 Zinc-coated
SNL510 4 - 8 8.0 JJJJ44CXT05 Green
8 - 12 9.0 JJJJ44CXT06 Blue
SNL436
12 - 15 9.0 JJJJ43CXT07 Red
25 - 50 9.0 JJJJ43CXT08 Zinc-coated
6.0 JJJJ43CXT09 Zinc-coated
Table 6. Type S150
Note: When selecting the spring, choose the set point in the middle of the spring pressure range for better operation.
S Series
55
OUTLET
PRESSURE INLET PRESSURE, MPa
KPa 0.02 0.05 0.1 0.2 0.25 0.3 0.4
1.5 270 500 700 1000 1100 1150 1250
2.5 270 487 700 1000 1100 1150 1250
3.0 270 487 700 1000 1100 1150 1250
4.0 270 487 700 1000 1100 1150 1250
6.0 270 474 700 1000 1100 1150 1250
8.0 240 474 700 1000 1100 1150 1250
10 230 460 700 1000 1100 1150 1250
12 192 460 700 1000 1100 1150 1250
15 167 448 700 1000 1100 1150 1250
25 - - - - 385 700 1000 1100 1150 1250
30 - - - - 330 700 1000 1100 1150 1250
50 - - - - - - - - 700 1000 1100 1150 1250
Table 7. Type S50
6. Flow Table
Table
8. Type S65
OUTLET
PRESSURE INLET PRESSURE, MPa
KPa 0.02 0.05 0.1 0.2 0.25 0.3 0.4
1.5 320 570 1100 1300 1500 1700 2000
2.5 450 700 1200 1600 1800 2000 2400
3.0 400 700 1200 1600 1800 2000 2400
4.0 380 700 1200 1600 1800 2000 2400
6.0 360 700 1200 1600 1800 2000 2400
8.0 330 700 1200 1600 1800 2000 2400
10 300 700 1200 1600 1800 2000 2400
12 240 700 1200 1600 1800 2000 2400
15 200 700 1192 1600 1800 2000 2400
25 - - - - 600 1153 1600 1800 2000 2400
30 - - - - 450 1100 1600 1800 2000 2400
50 - - - - - - - - 1025 1600 1800 2000 2400
Table 9. Type S80
OUTLET
PRESSURE INLET PRESSURE, MPa
KPa 0.02 0.05 0.1 0.2 0.25 0.3 0.4
1.5 600 1200 1500 2000 2200 2500 3000
2.5 700 1200 1800 2200 2500 2800 3200
3.0 700 1200 1800 2200 2500 2800 3200
4.0 700 1200 1800 2200 2500 2800 3200
6.0 650 1200 1800 2200 2500 2800 3200
8.0 550 1100 1800 2200 2500 2800 3200
10 550 1100 1780 2200 2500 2800 3200
12 500 1000 1770 2200 2500 2800 3200
15 240 1000 1780 2200 2500 2800 3200
25 - - - - 850 1740 2200 2500 2800 3200
30 - - - - 850 1700 2200 2500 2800 3200
50 - - - - - - - - 1540 2200 2500 2800 3200
OUTLET
PRESSURE INLET PRESSURE, MPa
KPa 0.02 0.05 0.1 0.2 0.25 0.3 0.4
1.5 600 1200 1500 2000 2200 2500 3000
2.5 700 1200 1800 2200 2500 2800 3200
3.0 700 1200 1800 2200 2500 2800 3200
4.0 700 1200 1800 2200 2500 2800 3200
6.0 650 1200 1800 2200 2500 2800 3200
8.0 550 1100 1800 2200 2500 2800 3200
10 550 1100 1780 2200 2500 2800 3200
12 500 1000 1770 2200 2500 2800 3200
15 240 1000 1780 2200 2500 2800 3200
25 - - - - 850 1740 2200 2500 2800 3200
30 - - - - 850 1700 2200 2500 2800 3200
50 - - - - - - - - 1540 2200 2500 2800 3200
Table
10. Type S100
OUTLET PRESSURE INLET PRESSURE, MPa
KPa 0.02 0.05 0.1 0.2 0.25 0.3 0.4
1.5 1500 2400 3500 4000 4200 4500 5500
2.5 1714 2798 4000 4400 4800 5000 6000
3.0 1674 2783 4000 4400 4800 5000 6000
4.0 1587 2750 4000 4400 4800 5000 6000
6.0 1440 2694 3987 4400 4800 5000 6000
8.0 1326 2653 3980 4400 4800 5000 6000
10 959 2537 3955 4400 4800 5000 6000
12 800 2500 3900 4400 4800 5000 6000
15 - - - - 2400 3919 4400 4800 5000 6000
25 - - - - 2236 3873 4400 4800 5000 6000
30 - - - - 2040 3815 4400 4800 5000 6000
50 - - - - - - - - 3500 4400 4800 5000 6000
Table 11. Type S150
Note:
The data in the table is the ow rate  with relative density of 0.61 for natural gas under standard conditions.
For other media, the data in the table should be multiplied by the corresponding factor.
Conversion factor: Articial Gas: 1.17, Butane: 0.55, Propane: 0.63, Air: 0.78, Nitrogen: 0.79
“- - - -” means unavailable
In order to make the pressure regulator work normally, the inlet and outlet pressure in a corresponding table should be
indicated when ordering if the ow rate used recently is less than 15%.
S Series
66
!
WARNING
7. Installation and Use
1. Installation
Installation, operation and maintenance procedures performed by unqualied personnel may result in improper
adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Only a qualied
person shall install, operate and maintain the unit.
The user must train relevant personnel or contact the after-sales service of the company.
1)  Install the regulator where it is far from re source, vibration; and the environment temperature meet requirement, heat 
tracing is necessary if the installation place temperature is lower than requirement.
2) Ensure that pressure rate of the pipeline is corresponding with the pressure range indicated on the regulator nameplate.
3) Ensure that ow arrow direction on the regulator is corresponding with pipeline ow direction.
4) Clean the pipeline before installing the regulator.
5) Install the regulator horizontally. The regulator cannot be installed forcefully when it is connected to the front and
rear pipelines.
6) When there is a fast opening or closing combustion chamber or valve behind the regulator, there should be a certain
volume to avoid drastic rise or fall of pressure caused by the rapid changes in ow rate.
7) Filter must be installed on the upstream of the regulator, and there should be an adequate straight pipeline downstream
of the regulator. The pressure sensing line measuring point must be located 4 to 6 times the pipe diameter downstream of
the regulator. It is recommended that the ow rate in the downstream pipe is ≤30m/s, and the diameter of the straight pipe 
should be larger than the outlet pipe of the regulator if necessary. (Installation sketch see Figure 3).
Forceful installation is strictly prohibited; during pipeline pressure test and purging, please use a blind plate to completely
block the pressure regulator or remove the pressure regulator, otherwise the pressure regulator is susceptible to damage.
Figure 3
Figure 4
BASE
ADJUSTING SCREW
SIGNAL PIPE
DN 4 to 6
SPRING
COVER
INLET
OUTLET
VENT
PRESSURE METER
!
WARNING
S Series
77
2. Use
2.1 Start-up
1) A lter should be installed on the upstream of the regulator;
2) Open the shut-off valve;
3) Slowly open the inlet valve upstream of the regulator;
4) Slightly open the outlet valve downstream of the regulator and observe whether the outlet pressure is the desired set
pressure, otherwise set according to Section 2.2;
5) Observe for a while until the ow becomes stable;
6) Fully open the outlet valves of the regulator.
2.2 Pressure Regulator Outlet Pressure Setting
To change the outlet pressure of the regulator, slowly turn the spring cover to open, then, slowly turn the adjusting screw 
(clockwise to increase and counter-clockwise to decrease the outlet pressure) to meet the pressure requirement. When
adjusting the pressure, make sure that the length of thread engagement between the spring cover and the base cannot be less 
than 10 mm.
8. Pressure Regulator Maintenance
General Rules of Maintenance
Close the inlet and outlet valve of the regulator before maintenance, then release all the pressure inside the regulator; avoid
damaging orice, diaphragm etc. parts during assembly or disassembly; check if each moveable parts can be moved freely; 
Setup the regulator according to Clause 2. The Use of Regulator after maintenance, and check leakage on each sealing part by
soap solution.
Our company provides training services to maintenance personnel. For other information, please contact our after-sales
service department.
1. Routine Maintenance
The management department of the pressure regulator shall determine the daily maintenance cycle according to the gas
quality and use situation to ensure the safe use of gas:
1) Check the pressure regulator for external leakage using a gas alarm instrument (or soap solution).
2) Observe the pressure gauge reading and check the outlet pressure of the pressure regulator.
3) Clean the outside of the pressure regulator.
2. Regular Inspection
It is recommended to carry out regular cleaning and maintenance of the inside of the pressure regulator every 3-6 months on the
basis of gas quality and use situation (when the medium is articial gas, it is recommended to shorten the maintenance cycle to 
1-3 months); check or replace the rubber members prone to swelling or aging to ensure safe gas supply and normal use.
The management department of the pressure regulator should determine the regular maintenance cycle according to the gas
quality and use situation to ensure the normal operation of the pressure regulator:
1) It is recommended to check the lockup pressure of the pressure regulator at least every three months: connect a pressure
gauge to the outlet end of the pressure regulator, turn on the switch, slowly close the ball valve at the outlet end of the
pressure regulator, record the lockup pressure three minutes later and check whether it is within the normal range. When
the lockup pressure of the pressure regulator is normal, there is no need to disassemble the pressure regulator.
2) It is recommended to check the inlet pressure setting of the disconnector at least every three months.
3) It is recommended to clean and maintain the internal parts of the pressure regulator and shut-off valve every three to six
months, check the vulnerable parts such as the disk seal , the diaphragm and the O-ring, and replace the swollen, aging
seals with uneven indentation.
4) Check the wear and deformation of key components in the pressure regulator, and replace if necessary.
S Series
88
SIZE, DN ACTUATOR OUTLET PRESSURE, KPa DISK MATERIAL SPARE KIT
50
SNL436 1.5 - 25 Nitrile (NBR) JJJJB2BX001
SNL330 25 - 50 Nitrile (NBR) JJJJB2BX002
SNL436 1.5 - 25 Fluorocarbon (FKM) ERAA49669A0
SNL330 25 - 50 Fluorocarbon (FKM) ERAA49670A0
65
SNL510 1.5 - 12 Nitrile (NBR) JJJJB3BX001
SNL436 12 - 25 Nitrile (NBR) JJJJB3BX002
SNL436HP 25 - 50 Nitrile (NBR) JJJJB3BX002
SNL510 1.5 - 12 Fluorocarbon (FKM) ERAA49673A0
SNL436 12 - 25 Fluorocarbon (FKM) ERAA49674A0
SNL436HP 25 - 50 Fluorocarbon (FKM) ERAA49674A0
80
SNL610 1.5 - 4 Nitrile (NBR) JJJJB4BX001
SNL510 4 - 12 Nitrile (NBR) JJJJB4BX002
SNL436 12 - 25 Nitrile (NBR) JJJJB4BX004
SNL436HP 25 - 50 Nitrile (NBR) JJJJB4BX004
SNL610 1.5 - 4 Fluorocarbon (FKM) ERAA49678A0
SNL510 4 - 12 Fluorocarbon (FKM) ERAA49679A0
SNL436 12 - 25 Fluorocarbon (FKM) ERAA49680A0
SNL436HP 25 - 50 Fluorocarbon (FKM) ERAA49680A0
4. Spare Parts Package of the S Series Pressure Regulator
3. Troubleshooting
ISSUE CAUSE TROUBLESHOOTING
Reduced outlet pressure
Inlet pressure is too low
The actual ow exceeds the design ow of the 
pressure regulator
There are too many foreign materials inside the
pressure regulator and jamming occurs
Choose a suitable pressure regulator, and clean the
inside of the pressure regulator
Lockup pressure rises
Diaphragm is swollen, aging or damaged Replace the diaphragm
Valve port sealing gasket is swollen and aging Replace the swollen gasket
The O-ring in the disk assembly is damaged Replace the O-ring
Foreign materials are adsorbed at the valve port or
damage happens Clean or replace the valve port
The pressure regulator is straight through Adjusting spring is compressed by outrange Replace the relatively hard spring
Outlet Pressure Unstable
Inlet pressure unstable
The actual ow rate is much lower than the rated 
ow rate
Contact operation management department
Change to a suitable regulator
S Series
99
4. Spare Parts Package of the S Series Pressure Regulator (continued)
SIZE, DN ACTUATOR OUTLET PRESSURE, KPa DISK MATERIAL SPARE KIT
100
SNL610 1.5 - 4 Nitrile (NBR) JJJJB5BX001
SNL510 4 - 12 Nitrile (NBR) JJJJB5BX002
SNL436 12 - 25 Nitrile (NBR) JJJJB5BX003
SNL436HP 25 - 50 Nitrile (NBR) JJJJB5BX003
SNL610 1.5 - 4 Fluorocarbon (FKM) ERAA49684A0
SNL510 4 - 12 Fluorocarbon (FKM) ERAA49685A0
SNL436 12 - 25 Fluorocarbon (FKM) ERAA49686A0
SNL436HP 25 - 50 Fluorocarbon (FKM) ERAA49686A0
150
SNL710 1.5 - 4 Nitrile (NBR) JJJJB6BX001
SNL510 4 - 12 Nitrile (NBR) JJJJB6BX002
SNL436 12 - 25 Nitrile (NBR) JJJJB6BX003
SNL436HP 25 - 50 Nitrile (NBR) JJJJB6BX003
SNL710 1.5 - 4 Fluorocarbon (FKM) ERAA49690A0
SNL510 4 - 12 Fluorocarbon (FKM) ERAA49691A0
SNL436 12 - 25 Fluorocarbon (FKM) ERAA49692A0
SNL436HP 25 - 50 Fluorocarbon (FKM) ERAA49692A0
Neither Emerson, Emerson Automation Solutions, nor any of their afliated entities assumes responsibility for the selection, use
or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the
purchaser and end user.
Jeon is a mark owned by one of the businesses of Emerson Automation Solutions. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales
are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specications of
such products at any time without notice.
www.emerson.com
Emerson, Emerson Automation Solutions以及它的任何附属实体都不承担产品选型
使用或维护的责任。承担任何正确选型
使用和
维护的责任唯有产品的购买者和终端用户。
JeonEmerson Automation Solutions业务单元的子公司之一拥有的商标。所有 其他商标是他们相应拥有者的产权。
本样本的内容介绍,仅供参考,我们已经尽了一切努力,确保其准确性。本样本不能被理解为关于产品或在此描述的服务或其使用,或适
用性的担保或保证,明示或暗示。所有销售都是依据我们的条款和条件,这些都可以根据需要获得。我们保留在任何时间修改或改进设计
或规格,而不另行通知的权利。
FISHER JEON Gas Equipment (Chengdu) Co., Ltd
No. 9, Wukedong 2nd Road, Wuhou Science Technic Park,
Chengdu, 610045, P.R. China
T: (028) 85360000 F: (028) 85371201
Service T: (028) 85366930 or (028) 85360000 Ext. 1613
Emerson Process Management
Chennai Private Limited
Plot No. 5, 6, 7 and 8 Self Help Industrial Estate
Keelkattalai, Chennai, India - 600117
T +91 44 4903 4405
F +91 44 4903 4400
费希尔久安输配设备(成都)有限公司
FISHER JEON Gas Equipment (Chengdu) Co., Ltd
地址:中国四川成都市武侯科技园武科东二路9号
总机:(028) 85360000 传真:(028) 85371201
服务热线:(028) 85366930 (028) 85360000分机1613
邮编:610045
Emerson Asia Pacic Private Limited
1 Pandan Crescent
Singapore 128461
T: +65 6777 8211
F: +65 6770 8028
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Emerson S Series Gas Pressure Regulator User manual

Type
User manual

Emerson S Series Gas Pressure Regulator offers precise pressure regulation and stabilization for medium and low-pressure gas systems. Ideal for residential, commercial, and industrial applications, it ensures steady gas flow for direct combustion equipment, gas pipelines, and more. With pressure ranges from 1.5 to 50 KPa and various actuator and spring options, you can customize it to your specific needs.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI