  • Hello! I am an AI chatbot trained to assist you with the Samsung AM080FXVAGH Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Air conditioner
Installation manual
AM***FXVAGR / AM***FXVAGH / AM***HXVAGH / AM***MXV*NR
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this installation manual carefully and retain it for future
reference.
DB68-03850A-16
2
Contents
Safety precautions ..........................................................................................................3
Preparing for installation ....................................................................................................6
Selecting installation location .............................................................................................18
Space requirement for installation.........................................................................................21
Accessories ............................................................................................................... 23
Base construction and installation of the outdoor unit .....................................................................24
Installing the wind/snow prevention duct .................................................................................28
Refrigerant pipe installation ...............................................................................................31
Electrical wiring work .....................................................................................................63
Air tightness test and vacuum drying......................................................................................80
Pipe insulation ............................................................................................................82
Charging refrigerant (for the turkish market only)..........................................................................85
Basic segment display.....................................................................................................88
Setting outdoor unit option switch and key function ......................................................................88
Setting the MCU and Pipe Addresses (for HR Only) .........................................................................98
Things to check after completing the installation .........................................................................102
Inspection and test operation ............................................................................................104
Automatic refrigerant amount detection function ........................................................................110
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger,
headset, USB cable) should not be disposed of with other household waste at the end of their working life. To prevent
possible harm to the environment or human health from uncontrolled waste disposal, please separate these items from
other types of waste and recycle them responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government office, for
details of where and how they can take these items for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product
and its electronic accessories should not be mixed with other commercial wastes for disposal.
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
When using R-410A, moisture or foreign substances may affect the performance and reliability of the product.
Safety precautions must be obeyed when installing the refrigerant pipe.
The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material and thickness
according to the regulations.
R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when filling the refrigerant.
(If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product malfunction.)
You must connect the indoor units for R-410A refrigerant. Refer to product catalog to find out the models names
for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it cannot operated
normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the product. Also, hand
over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for any
installation related claims from the user occurred by neglecting warnings and cautions stated in this manual. (Installer
will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for inevitable
reasons, please contact Samsungs qualified dealers for system air conditioners.
WARNING
Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
SEVERE WARNING SIGNS
Consult qualified installer or dealer for installation.
X When installation is done by unqualified person, problems such as water leakage, electric shock or fire may occur.
Installation work must be done properly according to this installation manual.
X When installation is not done properly, it may cause water leakage, electric shock or fire.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding allowable
safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the installation.
X When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and it
may cause injury.
Use the supplied accessories, specified components and tools for the installation.
X Do not use the pipe and the installation product used for the R-22 refrigerant.
X Failure to use the specified components can cause product fall down, water leakage, electrical shock, and fire. (The pipe
and flare components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
X If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
4
Safety precautions
Check the following before installation and service work.
X Before welding, remove dangerous and inflammable things that may cause an explosion and fire around the work.
X Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause the pipe
to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
X When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.
X Potential risk of electric shock, fire, product failure or injury.
Fix the outdoor unit securely on foundation to resist strong wind or earthquake.
X If the outdoor unit is not properly fixed, it turns over and accidents may occur.
Electric work must be done by qualified persons, complying the national wiring regulations and installed according to
the instruction stated in the installation manual with leased circuit.
X Capacity shortage on the leased circuit and improper installation may cause electric shock or fire.
Make sure to perform grounding work.
X Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper grounding
could cause electric shock.
Wiring must be connected with the designated wires and it must be fixed securely so that it does not apply any external
force to the connection part of the terminals.
X If connection for fixation is not properly done, it may cause heat generation or fire.
Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.
X If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or fire.
Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
X When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-off and it may cause
electric shock or fire.
X Do not use damaged parts. It may cause fire or electric shock.
You must cut-off the power before you work on, or adjust any power supply part for product installation, maintenance,
repair or any other services.
X There is risk of electric shock.
X Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure DC
voltage is charged to those parts.
X When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.
X When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
Gas leakage must be checked after installation is completed.
X When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself when the
temperature decrease below 0°C.
X If you cut-off the power, compressor protection mode cannot be operated and may cause damage to the product.
Wear protective equipment (such as safety gloves, goggles, and headgear) during installation and maintenance works.
Installation/repair technicians may be injured if protective equipment is not properly equipped.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by
a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
5
ENGLISH
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water
drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water
leakage.
X When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m away from the electric
appliances and install it at least 2m away from the lightning conductor.
X Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
X Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
X You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
X Make sure that the pipes does not get any weaker by welding it too much.
X Make sure to install the product away from children’s reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle:
25˚~55˚
Height of the building Protection control
20m or less 55˚
40m or less 35˚
60m or less 25˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
X If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
X Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
X Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
X The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The efficiency of the heat exchanger may reduce or product may break.
X The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
X The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
X The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of fire or explosion.)
X The place with carbon fiber or flammable dust.
X The place near seashore or hot spring where there is risk of outdoor unit corrosion.
6
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
X For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (To not use
T-joint)
X You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must use
KEY MODE to run trial operation.
X DVM S air conditioner uses R-410A refrigerant.
X Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
X Make sure to note that outdoor unit combination is different from DVM PLUS III and IV.
X The length of maximum piping, level difference, the quantity of connectable indoor units, the installation at the outdoor
joints and the outdoor unit combinations are different from the conventional models.
X If the pipe length is over 2 m between outdoor units, make traps to prevent oil stagnation. Oil stagnation may occur
when outdoor unit at the end of module stops while other outdoor units are still in operation.
Preparing for installation
Outdoor unit classification
Classification Small type DVM S Large A type DVM S Large B type
Appearance
Packaging material disposition
Safely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for
personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children. Children
may put them over their face, which is very dangerous since it may lead them to suffocation.
CAUTION
7
ENGLISH
Outdoor unit combination
f Make sure to use an indoor unit that is compatible with DVM S.
f Indoor units can be connected within the range indicated in following table.
f If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity
of the indoor unit may decrease.
f Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity. 0.5 ×
(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × (Outdoor unit capacity)
Please contact your local Samsung representative or refer to the Technical Data Book for further details if the project
requires you to design the project with a connection ratio greater than 130 %.
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM✴✴✴FNQDEH, AM✴✴✴JNVDKH) can be connected.
Use the following table to determine the size and number of outdoor units needed to achieve the capacity
requirements.
CAUTION
Standard type (Heat pump)
Model name for combination
AM080FXVAGH AM100FXVAGH AM120FXVAGH AM140FXVAGH AM160FXVAGH
Number of individual outdoor units
11111
Combined outdoor
unit
AM080FXVAGH
1
AM100FXVAGH
1
AM120FXVAGH
1
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
AM200FXVAGH
AM220FXVAGH
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
22.4 28 33.6 40 45
Heating (kW)
25.2 31.5 37.8 45 50.4
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
11.2 14 16.8 20 22.5
Maximum (kW)
29.1 36.4 43.7 52 58.5
Maximum number of connectable
indoor units
14 18 21 26 29
8
Preparing for installation
Model name for combination
AM180FXVAGH AM200FXVAGH AM220FXVAGH AM240HXVAGH AM260HXVAGH
Number of individual outdoor units
11111
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
AM140FXVAGH
AM160FXVAGH
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
1
AM240HXVAGH
1
AM260HXVAGH
1
Rated capacity
Cooling (kW)
50.4 56 61.6 67.2 72.8
Heating (kW)
56.7 63 69.3 75.6 81.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
25.2 28 30.8 33.6 36.4
Maximum (kW)
65.5 72.8 80.1 87.4 94.6
Maximum number of connectable
indoor units
32 36 40 43 47
Model name for combination
AM280HXVAGH1 AM300HXVAGH1 AM320HXVAGH1 AM340HXVAGH1 AM360HXVAGH1
Number of individual outdoor units
22222
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
1111
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
11
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
78.6 84.0 89.6 95.2 101.6
Heating (kW)
88.2 94.5 100.8 107.1 114.3
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
39.3 42.0 44.8 47.6 50.8
Maximum (kW)
102.2 109.2 116.5 123.8 132.1
Maximum number of connectable
indoor units
51 54 58 61 64
9
ENGLISH
Model name for combination
AM380HXVAGH1 AM400HXVAGH1 AM420HXVAGH1 AM440HXVAGH1 AM460HXVAGH1
Number of individual outdoor units
22223
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
2
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
AM200FXVAGH
1
AM220FXVAGH
1 121
AM240HXVAGH
AM260HXVAGH
1
Rated capacity
Cooling (kW)
106.6 112.8 117.6 123.2 128.8
Heating (kW)
119.7 126.9 132.3 138.6 144.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
53.3 56.4 58.8 61.6 64.4
Maximum (kW)
138.6 146.6 152.9 160.2 167.4
Maximum number of connectable
indoor units
64 64 64 64 64
Model name for combination
AM480HXVAGH1 AM500HXVAGH1 AM520HXVAGH1 AM540HXVAGH1 AM560HXVAGH1
Number of individual outdoor units
33333
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
11111
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
11112
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
135.2 140.2 145.6 151.2 156.8
Heating (kW)
152.1 157.5 163.8 170.1 176.4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
67.6 70.1 72.8 75.6 78.4
Maximum (kW)
175.8 182.3 189.3 196.6 203.8
Maximum number of connectable
indoor units
64 64 64 64 64
10
Preparing for installation
Model name for combination
AM580HXVAGH1 AM600HXVAGH1 AM620HXVAGH1 AM640HXVAGH1 AM660HXVAGH1 AM680HXVAGH1
Number of individual outdoor units
333334
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
2
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
222232
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
163.2 168.2 173.6 179.2 184.8 190.4
Heating (kW)
183.6 189.0 195.3 201.6 207.9 214.2
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
81.6 84.1 86.8 89.6 92.4 95.2
Maximum (kW)
212.3 218.7 212.3 233.0 240.2 247.5
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model name for combination
AM700HXVAGH1 AM720HXVAGH1 AM740HXVAGH1 AM760HXVAGH1 AM780HXVAGH1 AM800HXVAGH1
Number of individual outdoor units
444444
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
11111
AM140FXVAGH
11
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
222233
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
196.8 201.8 207.2 212.8 218.4 224.8
Heating (kW)
221.4 226.8 233.1 239.4 245.7 252.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
98.4 100.9 103.6 106.4 109.2 112.4
Maximum (kW)
255.8 262.3 269.4 276.6 283.9 292.2
Maximum number of connectable
indoor units
64 64 64 64 64 64
11
ENGLISH
Compact type (Heat pump)
Model name for combination AM360HXVAGH2 AM380HXVAGH2 AM460HXVAGH2 AM480HXVAGH2
Number of individual outdoor units
2222
Combined outdoor unit
AM120FXVAGH
11
AM200FXVAGH
1
AM220FXVAGH
1
AM240HXVAGH
1
AM260HXVAGH
111
Rated capacity
Cooling (kW)
100.8 106.4 128.8 134.4
Heating (kW)
113.4 119.7 144.9 151.2
Total capacity of the connected
indoor units (Cooling)
Minimum (kW)
50.4 53.2 64.4 67.2
Maximum (kW)
131.0 138.3 167.4 174.7
Maximum number of connectable indoor units
64 64 64 64
Model name for combination AM500HXVAGH2 AM520HXVAGH2 AM580HXVAGH2 AM600HXVAGH2
Number of individual outdoor units
2233
Combined outdoor unit
AM120FXVAGH
11
AM200FXVAGH
1
AM220FXVAGH
1
AM240HXVAGH
1
AM260HXVAGH
1211
Rated capacity
Cooling (kW)
140.0 145.6 162.4 168.0
Heating (kW)
157.5 163.8 182.7 189.0
Total capacity of the connected
indoor units (Cooling)
Minimum (kW)
70.0 72.8 81.2 84.0
Maximum (kW)
182.0 189.3 211.1 218.4
Maximum number of connectable indoor units
64 64 64 64
12
Preparing for installation
Model name for combination AM620HXVAGH2 AM640HXVAGH2 AM680HXVAGH2 AM700HXVAGH2
Number of individual outdoor units
3333
Combined outdoor unit
AM120FXVAGH
11
AM200FXVAGH
AM220FXVAGH
22
AM240HXVAGH
11
AM260HXVAGH
12 1
Rated capacity
Cooling (kW)
173.6 179.2 190.4 196.0
Heating (kW)
195.3 201.6 214.2 220.5
Total capacity of the connected
indoor units (Cooling)
Minimum (kW)
86.8 89.6 95.2 98.0
Maximum (kW)
225.7 233.0 247.5 254.8
Maximum number of connectable indoor units
64 64 64 64
Model name for combination AM720HXVAGH2 AM740HXVAGH2 AM760HXVAGH2 AM780HXVAGH2
Number of individual outdoor units
3333
Combined outdoor unit
AM120FXVAGH
AM200FXVAGH
AM220FXVAGH
11
AM240HXVAGH
11
AM260HXVAGH
1223
Rated capacity
Cooling (kW)
201.6 207.2 212.8 218.4
Heating (kW)
226.8 233.1 239.4 245.7
Total capacity of the connected
indoor units (Cooling)
Minimum (kW)
100.8 103.6 106.4 109.2
Maximum (kW)
262.1 269.4 276.6 283.9
Maximum number of connectable indoor units
64 64 64 64
13
ENGLISH
Standard type (Heat recovery)
Model name for combination
AM080FXVAGR AM100FXVAGR AM120FXVAGR AM140FXVAGR AM160FXVAGR
Number of individual outdoor units
11111
Combined outdoor
unit
AM080FXVAGR
1
AM100FXVAGR
1
AM120FXVAGR
1
AM140FXVAGR
1
AM160FXVAGR
1
AM180FXVAGR
AM200FXVAGR
AM220FXVAGR
AM240MXVGNR
AM260MXVGNR
AM280MXVGNR
AM300MXVANR
Rated capacity
Cooling (kW)
22.4 28 33.6 40 45
Heating (kW)
25.2 31.5 37.8 45 50.4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
11.2 14 16.8 20 22.5
Maximum (kW)
29.12 36.4 43.68 52 58.5
Maximum number of connectable
indoor units
14 18 21 26 29
Model name for combination
AM180FXVAGR AM200FXVAGR AM220FXVAGR AM240MXVGNR AM260MXVGNR
Number of individual outdoor units
11111
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
AM140FXVAGR
AM160FXVAGR
AM180FXVAGR
1
AM200FXVAGR
1
AM220FXVAGR
1
AM240MXVGNR
1
AM260MXVGNR
1
AM280MXVGNR
AM300MXVANR
Rated capacity
Cooling (kW)
50.4 56 61.6 67.2 72.8
Heating (kW)
56.7 63 69.3 75.6 81.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
25.2 28 30.8 33.6 36.4
Maximum (kW)
65.52 72.8 80.08 87.36 94.64
Maximum number of connectable
indoor units
32 36 40 43 47
14
Preparing for installation
Model name for combination
AM280MXVGNR AM300MXVANR AM320FXVGNR AM340FXVGNR AM360FXVGNR
Number of individual outdoor units
12222
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
11
AM140FXVAGR
1
AM160FXVAGR
AM180FXVAGR
AM200FXVAGR
1
AM220FXVAGR
11
AM240MXVGNR
AM260MXVGNR
AM280MXVGNR
1
AM300MXVANR
1
Rated capacity
Cooling (kW)
78.6 84 89.6 95.2 101.6
Heating (kW)
88.2 94.5 100.8 107.1 114.3
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
39.3 42 44.8 47.6 50.8
Maximum (kW)
102.18 109.2 116.48 123.76 132.08
Maximum number of connectable
indoor units
51 54 58 61 64
Model name for combination
AM380FXVGNR AM400FXVGNR AM420FXVGNR AM440FXVGNR AM460FXVGNR
Number of individual outdoor units
22222
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
AM140FXVAGR
1
AM160FXVAGR
11
AM180FXVAGR
1
AM200FXVAGR
1
AM220FXVAGR
111
AM240MXVGNR
AM260MXVGNR
AM280MXVGNR
AM300MXVANR
11
Rated capacity
Cooling (kW)
106.6 112 117.6 124 129
Heating (kW)
119.7 126 132.3 139.5 144.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
53.3 56 58.8 62 64.5
Maximum (kW)
138.58 145.6 152.88 161.2 167.7
Maximum number of connectable
indoor units
64 64 64 64 64
15
ENGLISH
Model name for combination
AM480FXVGNR AM500FXVGNR AM520FXVGNR AM540FXVGNR AM560FXVGNR
Number of individual outdoor units
22222
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
AM140FXVAGR
AM160FXVAGR
AM180FXVAGR
1
AM200FXVAGR
1
AM220FXVAGR
1
AM240MXVGNR
1
AM260MXVGNR
1
AM280MXVGNR
AM300MXVANR
11111
Rated capacity
Cooling (kW)
134.4 140 145.6 151.2 156.8
Heating (kW)
151.2 157.5 163.8 170.1 176.4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
67.2 70 72.8 75.6 78.4
Maximum (kW)
174.72 182 189.28 196.56 203.84
Maximum number of connectable
indoor units
64 64 64 64 64
Model name for combination
AM580FXVGNR AM600FXVGNR AM620FXVGNR AM640FXVGNR AM660FXVGNR AM680FXVGNR
Number of individual outdoor units
223333
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
11
AM140FXVAGR
1
AM160FXVAGR
1
AM180FXVAGR
AM200FXVAGR
1
AM220FXVAGR
111
AM240MXVGNR
AM260MXVGNR
AM280MXVGNR
1
AM300MXVANR
121111
Rated capacity
Cooling (kW)
162.6 168 173.6 179.2 185.6 190.6
Heating (kW)
182.7 189 195.3 201.6 208.8 214.2
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
81.3 84 86.8 89.6 92.8 95.3
Maximum (kW)
211.38 218.4 225.68 232.96 241.28 247.78
Maximum number of connectable
indoor units
64 64 64 64 64 64
16
Preparing for installation
Model name for combination
AM700FXVGNR AM720FXVGNR AM740FXVGNR AM760FXVGNR AM780FXVGNR AM800FXVGNR
Number of individual outdoor units
333333
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
AM140FXVAGR
AM160FXVAGR
AM180FXVAGR
1
AM200FXVAGR
1
AM220FXVAGR
112111
AM240MXVGNR
1
AM260MXVGNR
1
AM280MXVGNR
1
AM300MXVANR
111111
Rated capacity
Cooling (kW)
196 201.6 207.2 212.8 218.4 224.2
Heating (kW)
220.5 226.8 233.1 239.4 245.7 252
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
98 100.8 103.6 106.4 109.2 112.1
Maximum (kW)
254.8 262.08 269.36 276.64 283.92 291.46
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model name for combination
AM820FXVGNR AM840FXVGNR AM860FXVGNR AM880FXVGNR AM900FXVGNR
Number of individual outdoor units
33333
Combined outdoor
unit
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
AM140FXVAGR
AM160FXVAGR
AM180FXVAGR
AM200FXVAGR
AM220FXVAGR
1
AM240MXVGNR
1
AM260MXVGNR
1
AM280MXVGNR
1
AM300MXVANR
22223
Rated capacity
Cooling (kW)
229.6 235.2 240.8 246.6 252
Heating (kW)
258.3 264.6 270.9 277.2 283.5
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
114.8 117.6 120.4 123.3 126
Maximum (kW)
298.48 305.76 313.04 320.58 327.6
Maximum number of connectable
indoor units
64 64 64 64 64
17
ENGLISH
Moving the outdoor unit
f Select the moving path in advance.
f Be sure that moving path can support weight of the outdoor unit.
f Do not slant the product more than 30˚ when carrying it. (Do not lay the product down in sideways.)
f Surface of the heat exchanger is sharp. Be careful not to get injured while moving the product.
You must use certain part of the product when moving the product.
CAUTION
When moving with a crane
f Fasten the wire rope as shown in the figure.
f To protect damage or scratches, insert a piece of cloth between the
outdoor unit and the wire rope.
Wire rope
Holes for wire rope
to go through
When moving with a forklift
f Carefully insert the forklift forks into the forklift holes at the bottom of
the outdoor unit.
f Be careful with the forklift from damaging the product.
Forklift
Forklift holes
Holes for forklift
forks to go through
When moving the product without wooden pallet and the crane is not available for use
f Connect a wire rope to the outdoor unit as you would move it with a
crane.
f Hang the wire rope to the forklift fork to move the outdoor unit.
Wire rope
Forklift
18
Selecting installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval.
f Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential areas,
keep the operation hours in mind.)
f Place where structure can bear the weight and vibration of the outdoor unit.
f Place with flat surface where rainwater does not settle or leak.
f Place where it is not exposed to strong wind.
f Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct can be purchased separately)
f Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
f Place where it allows easy waterproofing and draining work for the condensation water generated from the outdoor unit
during heating operation.
f Place where there is no risk of inflammable gas leakage.
f Place where there is no direct influence of snow or rain.
f Place where a large amount of water generated by external environment does not directly affect the top of the outdoor
unit.
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
1. Do not install the product in a place where it is directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure (such as building) that can block see breeze.
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea
breeze by installing a protection wall.
2. Consider that the salinity particles clinging to the external panels should be sufficiently washed out.
3. Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that the slope
does not disturb drainage.
- Keep the floor level so that rain does not accumulate.
- Be careful not to block the drain hole due to foreign substance.
4. When product is installed in seashore, periodically clean it with water to remove attached salinity.
5. Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the base part has
good drainage.
6. If the product is damaged during the installation or maintenance, make sure to repair it.
7. Check the condition of the product periodically.
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG
(Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like
covering the product.
19
ENGLISH
8. If the product installed within 500m of seashore, special anti-corrosion treatment is required.
Please contact your local SAMSUNG representative for further details.
Sea
Sea
Sea breeze
Sea breeze
Outdoor
unit
Outdoor
unit
Outdoor unit
Protection wall should be constructed with a solid material that
can block the sea breeze and the height and width of the wall
should be 1.5 times larger than the size of the outdoor unit. (You
must secure more than 700mm of space between the protection
wall and the outdoor unit for air circulation.)
Sea
Sea breeze
Outdoor
unit
Outdoor unit
Protection wall
Environment Installation conditions Anti-Corrosion Eect from Installation Anti corrosion Eect by Maintenance
Seashore
Seashore within 500m
Direct exposure
With Anti-corrosion coating: 2
years from installation
*
Check 1 year later from installation
After Corrosion Protection period
(2 years)
Cleaning & Spray R-Pro :
2 years extended
Seashore within 500m
Building / Protection Wall
With Anti-corrosion coating:
4 years from installation
Without Anti-corrosion
coating: 2 years from
installation
* Check 1 year later from installation
After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating):
4 years extended
Cleaning & Spray R-Pro
(without initial coating):
2 years extended
Seashore within 500m~2km
With Anti-corrosion coating: 4
years from installation
Without Anti-corrosion
coating: 2 years from
installation
* Check 1 year later from installation
After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating):
4 years extended
Cleaning & Spray R-Pro
(Without initial coating):
2 years extended
Seashore
+
Corrosive gas area
Seashore within 500m
Corrosive gas area
With Anti-corrosion coating: 2
years from installation
* Check 1 year later from installation
After Corrosion Protection period
(2 years)
Cleaning & Spray R-Pro :
2 years extended
Seashore within 500m~2km
Corrosive gas area
Corrosive gas area
The place where corrosive
gas generates
20
Selecting installation location
System air conditioner may cause static noise when listening to AM stations. Therefore, select an installation
location for indoor unit where electrical wiring can be done while keeping certain distance from a radio,
computer and stereo equipment.
- Especially, keep the unit at least 3m away from the electrical equipment in an area with weak electromagnetic
waves and put the main power cable and communication cables in a separately installed protection tube.
- Make sure that there is no equipment that generates electromagnetic waves. If not electromagnetic waves
may cause problem to the control systems which may lead to air conditioner malfunction. (Example: Remote
control sensor of the indoor unit may not receive the signal very well, due to ballast stabilizer of the lighting
equipment.)
In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns of direct
snowfall on the outdoor unit. Also, build higher base support so that accumulated snow does not block the air
inlet or the heat exchanger.
R-410A refrigerant is a safe, nontoxic and nonflammable refrigerant. However, if the place holds any concerns for
exceeding dangerous level of refrigerant concentration in case of refrigerant leakage, extra ventilation system is
required.
When you install the outdoor unit in a high places such as roof, install fence or guardrail around it. When there is
no fence or guardrail, service person could fall.
Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and sulfurous gas are
produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex, cattle shed, sulfuric hot spring,
nuclear power plant, ship etc.) When installing the product in those places, contact an installation specialty
store as the copper pipe and brazing part will need additional corrosion proof or anti-rust additive to prevent
corrosion.
Make sure to keep any inflammable materials (such as wooden materials, oil etc.) around the outdoor unit. When
there's fire, those inflammable material will easily catch the fire and may pass it on to the product.
Depending on the condition of power supply, unstable power or voltage any cause malfunction of the parts or
control system. (At the ship or places using power supply from electric generator...etc)
Make sure to install MCU when using HR products.
When you select the location to install MCU, the location is far away from indoor rooms because the refrigerant
running of MCU may create noise.
CAUTION
/