When any alarm is reported to the system, the power to all
ADBI-60’s reverses polarity, but no audible sounds. The
system may then selectively command the ADBI-60, under
programmed control, to become audible. All ADBI-60
bases are capable of sounding simultaneously, individually
or in any combination depending upon the system Pro-
gram and control panel. The ADBI-60 is UL 268 listed and
achieves the audibility sound output of 85 decibels at ten
feet.
CAUTION: The ADBI-60 is not to be used for primary
building evacuation, but only as a
supplemental audible signal device.
Application DataApplication Data
The ADB-3 is fully compatible with Series 3 plug-in detec-
tors. When an ADB-3 is used with a compatible detector,
no remote relay or lamp device can be used with that
same detector. No more than thirty (30) compatible
detectors of any type or combination (other than thermals
or manual stations) may be used on any one Cerberus
Pyrotronics conventional system detector circuit.
The ADBI-60 is compatible only with Cerberus Pyrotronics
MXL or IXL addressable detectors. No more than sixty (60)
“I” Series detectors on MXL or IXL loops may be used on
any one addressable initiating circuit.
The smoke detectors used with the ADB-3 and ADBI-60
are subject to the maximum 30 ft. center spacing (900 sq.
ft.) as referred to in the National Fire Protection Association
Standard 72. This spacing, however, is based on ideal
conditions, namely, smooth ceiling, no air movement, and
no physical obstructions between the fire source and the
detector. This spacing should be used as a guide or
starting in detector installation layout. Do not mount
detectors in areas close to ventilating or air conditioning
outlets. Exposed joists or beamed ceilings may also effect
safe spacing limitations for detectors. It is mandatory that
NFPA 72 and good engineering judgement be applied
regarding detector locations and spacing.
Architect/Engineers SpecificationsArchitect/Engineers Specifications
The audible device that shall be used for localized annun-
ciation shall be contained in a plug-in twist lock detector
base that is compatible with Cerberus Pyrotronics “3”, “X”
or “I” Series plug-in detectors. The detector base shall
contain a prewired piezo electric device that will produce
an audible signal at a minimum of 85 db at 10 feet.
The audible device when used with a standard Cerberus
Pyrotronics conventional zone fire alarm system shall be
the ADB-3. Power shall be provided to the ADB-3 audible
base through the zone wires of the fire alarm control panel.
The input power provided shall be 18 VDC- 24 VDC. The
fire alarm panel shall guarantee that one audible base
model ADB-3, or one remote relay model RR-3/3S or one
remote lamp model RL-30 or RL-40 will activate per zone.
Once activated the ADB-3 shall be silenced via the reset of
the control panel.
Th audible device, when used with the addressable/
analog, Cerberus Pyrotronics fire alarm MXL or IXL Sys-
tems, shall be the ADBI-60. Power shall be provided to the
ADBI-60 by the system if the total power requirement is
less than 3.0 amps or from a separate auxiliary power
supply if the total power requirement exceeds 3.0 amps.
100% of all audible bases shall be capable of sounding
simultaneously, individually or in any combination. Once
initiated, the audible base shall lock into alarm and must
be silenced at the MXL or IXL System control panel or
MXL’s optional printer. The audible base, when used with
the Cerberus Pyrotronics addressable/analog System MXL
or IXL, shall require input power of 28-48 VDC peak
fullwave or 20-27 VDC while on battery.
The audible bases shall be UL listed.
Technical SpecificationsTechnical Specifications
ADB-3 and ADBI-60
Audible Ouput: 85db @ 10 ft./min.
Model ADB-3
Voltage Rating: DC (Zone Power): 18-24 VDC
Current: Supervisory - 0 A
Alarm - 13 mA at 25 VDC
Constraint: Only one device is guaranteed
to activate per zone.
Model ADBI-60
Voltage Rating: On AC Power: 28-48 VDC peak,
Full wave
On Battery: 20-27 VDC
Current: Supervisory - 0 A
Alarm - 37 mA at 25 VDC
Contraints:
1. The maximum number of ADBI-60’s per a AA-30U,
AE-30U, ICP, MMB-1, CES or CSM-4 Bell power loop is
40, with no other devices connected, and with the
maximum loop current available.
NOTE: The number of ADBI-60’s cannot exceed the
maximum current available to the loop. See the IXL
Manual, P/N 315-092371, or the MXL Manual, P/N 315-
092036, for the compatibility details of ICon, ALD and
audible circuit wiring.
2. Maximum line resistance permitted (both wires), not
including the end of the line resistor, is 3 ohms. A
minimum of 14 AWG wire must be used.
3. T-tapping of the audible circuit (Diagrams 2, 3, 4, and 5)
is not allowed.
NOTE: The 24 VDC external power source should not
be powering any other devices that could generate
noise on the line, such as a Voice Alarm system or
devices which are not part of the fire alarm system. If
there is any ground detection with the 24 VDC external
power, disconnect it.
4. Use the AA-30U for either Class A or Class B wiring; the
AE-30U for Class B wiring only (Diagrams 2 and 3).
5. If the ADBI-60 is powered by MXL (Diagrams 4 and 5),
the total system power available for indicating appli-
ances is 3A. If more than 3A is required, use the
configuration in Diagram 2 or Diagram 3 for auxiliary
power.
6. Connect terminal 6 of the PS-35 (Diagrams 2 and 3)
to the minus DC side of the MXL main power supply for
proper ground fault supervision.
7. Each audible base is marked to indicate its type
(ADBI-60 or ADB-3):
oADBI-60
oADB-3
The boxes are usually marked with a check mark.
However, if the audible portion of an ADBI-60 is
polarized for reverse polarity detection, the unit is
marked with an S. If it is not marked with an S, the