  • Hello! I am an AI chatbot trained to assist you with the Aprilaire 8082 TrH Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1
8081 TT / 8082 TrH
Support Module
READ AND SAVE THESE INSTRUCTIONS
Installation Instructions
FEATURES







MODEL 8081 TT OPTIONS
* For remote temperature sensors use the Aprilaire Model 8051 Flush Mount Temperature Sensor, Model 8052 Duct/Outdoor
Temperature Sensor, or the Model 8053 Surface Mount Temperature Sensor.




MODEL 8082 TrH OPTIONS

 
 
3-4
TABLE OF CONTENTS
5-6
7
7

2
3
INSTALLATION RECOMMENDATIONS



CONTROLLING SENSOR SHOULD BE MOUNTED:







DO NOT MOUNT CONTROLLING SENSOR:
















SUPPORT MODULE MOUNTING



WIRING
RC
C
RSA & RSB
T1 & T2
T3 & T4
WIRE SPECIFICATIONS







INSTALLATION NOTES
WIRING TERMINALS
4
5
WIRING (CONTINUED)








8082 8081
8800




1
2
3
4
5
6
OFF ON OFF ON
ADDRESS ADDRESS
ADDRESS ADDRESS
MONITOR (S1)CONTROL (S1)
MONITOR (S2)CONTROL (S2)
SPARESPARE
T1/T2 (S1)ONBOARD SENSOR
DIP SWITCH CONFIGURATION


SUPPORT MODULE ADDRESS SELECTION – DIP SWITCH 1 & 2
ADDRESS 1
ADDRESS 2
ADDRESS 3
ADDRESS 4
OFF ON
OFF ON
OFFON
OFFON


If the support module is set to address 1, sensor 1 is set to monitor, and
the 8800 thermostat does not have an outdoor temperature sensor attached then the 8800 thermostat will
use sensor 1 as the outside temperature value.




SENSOR 1 MODE – DIP SWITCH 3
WIRING DIAGRAM




Note: If the switch is set to off and there is no temperature sensor wired to T1&T2 then no value will
be reported for sensor 1 or sensor 2 and “CHECK SM” message will be displayed at the 8800 thermostat.
SENSOR 1 SELECTION – DIP SWITCH 6
6
7
DIP SWITCH CONFIGURATION (CONTINUED)

DIP SWITCH 5
TROUBLESHOOTING



THE 8800 THERMOSTAT DISPLAY IS BLANK
Temperature


Temperature Accuracy

Humidity

Humidity Accuracy

Electrical



THE 8800 THERMOSTAT DISPLAYS A VERY HIGH TEMPERATURE


8800 THERMOSTAT DOES NOT DISPLAY THE OUTDOOR TEMPERATURE FROM THE SUPPORT MODULE
SPECIFICATIONS
8081








8082








Note: If the 8800 thermostat has both humidity and temperature sensors set to control, the temperature
sensors will be used for control and the 8800 thermostat will display a CONFLICTING CONTROL SENSORS
message in the message center.
SENSOR 2 MODE – DIP SWITCH 4

www.aprilairepartners.com




ACCESSORIES OPTIONAL REMOTE TEMPERATURE SENSORS




MODEL 8051 FLUSH MOUNT TEMPERATURE SENSOR




MODEL 8052 OUTDOOR/DUCT MOUNT TEMPERATURE SENSOR


MODEL 8053 SURFACE MOUNT TEMPERATURE SENSOR
/