STEP 4 – WIRE THE SENSOR TO THE APRILAIRE CONTROL
• Use18–22awgwire(2-wirethermostatcable).
• Usethetwosmallwirenutsprovided.
• Uselessthan300'ofwire.
• Donotroutewirealong120VAClines.
CAUTION
Excessive bare wire can lead to shorts.
Strip only as much insulation as is necessary.
• Thesensorisnotpolarityspecific.Eithersensorleadmaybe
connected to either terminal on the Aprilaire control to which it
is wired.
– Forsupportmodules,useT1andT2orT3andT4terminals.
– Forthermostats,useS1andS2(Outdoor)orT1andT2(Remote)
terminals.
– Forzonecontrols,useDAT,PlenumSensororODTterminals.
– ForHomeComfortControl,useRAT,LATorODTterminals.
• Usecarewhenroutingandstrippingthewire.Sharpbends(kinks)
orcutsinthewire(particularlysusceptiblewheretheinsulationhas
beenstripped)canleadtoeventualconductorfailure.
STEP 5 – RECONNECT POWER TO THE APRILAIRE CONTROL
Sensor Specifications:
Resistance@77°F(25°C):10k
Tolerance@77°F(25°C):±3%
STEP 2 – DISCONNECT POWER TO THE APRILAIRE CONTROL TO
WHICH THE SENSOR WILL BE WIRED
CAUTION
Damage to components can occur if power is not disconnected.
STEP 3 – VERIFY THE SENSOR RESISTANCE
Useanohm-meterormultimetertomeasuretheresistanceofthe
sensor.MeasureatthewiresneartheAprilairecontroltocheckany
wiresplices.Confirmtheresistancecorresponds(within5%)tothe
temperature where the sensor is installed.
Temperature (°F) Resistance (k )
30 34.6
40 26.1
50 19.9
60 15.3
70 11.9
80 9.4
90 7.4
100 5.9
Note: This measurement should be done without the sensor
connected to the Aprilaire control.
2