100mm VIDEO-GRAPHICS RECORDER: ISOLATED TRANSMITTER POWER SUPPLY
Page 1HA027489
Issue 1 Jly 01
Black
Black
Black
Red
Red
Red
+
Transmitter
+
-
Other transmitters
V+
V-
Channel input
+ +
Only one channel
shown, for clarity.
Long terminal cover
Recorder rear
terminal panel
User terminal block
I
R
Transmitter Power Supply
PCB
0 mA
4 mA
20 mA
0 V
0.4 V
2.0 V
0 V
1.0 V
5.0V
100
250
Voltages generated by
various currents for
R = 100
and R =250
R (minimum spec) = 1.4W, 1%. 100 or 250 as required (see table)
USER WIRING (Cont.)
Figure 5 Application wiring
EUROTHERM LIMITED
Faraday Close, Durrington, Worthing, West Sussex, BN13 3PL
Telephone: 01903 695888. Facsimile: 01903 695666
Website: http://www.eurotherm.co.uk
HA027489/1 (CN13088)Page 4
INTRODUCTION
This option consists of a circuit board, teminal block and suitable wiring inside a long terminal cover at the rear of the
recorder. The board supplies three mutually isolated dc supplies (nominal 25 Volts) each of which is intended to
power a single 0 to 20mA or 4 to 20 mA current loop.
The circuit board is protected by a 20mm anti-surge (type T) fuse, the value of which depends on the supply voltage
as shown in the table below.
Access to the output wiring and to the fuse is achieved by isolating the recorder from mains power and opening the
terminal cover (after removing its securing screw). The process is fully described below.
Isolated transmitter power supply
Models 5100e / 5100V
284 mm (11.18 in)
213mm (8.39in)
137mm
(5.4in)
25mm
(0.99 in)
Mounting slot
(Left hand side)
Panel thickness
(25.4mm (1 in) max)
View on right hand
side
Safety Isolation
Isolation (dc to 65Hz; BS EN61010) Installation category II; Pollution degree 2.
Channel to channel: 100V RMS or dc (double insulation).
Channel to ground: 100V RMS or dc (basic insulation).
Installation category II
The rated impulse voltage for equipment on
nominal 230V ac mains is 2500V.
Pollution degree 2
Normally, only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity
caused by condensation shall be expected.
SPECIFICATION
Physical
The long terminal cover adds 71 mm (closed) or 186 mm (open) to the back-of-panel length of the recorder, as shown below. Otherwise the recorder dimen-
sions are as given in the recorder user guide.
Supply voltage Fuse rating Part Number
110V ac 100 mA CH050012
120V ac 100 mA CH050012
220V ac 63 mA CH050630
240V ac 63mA CH050630