AURORA PVI-6000-TL

Power One AURORA PVI-6000-TL Quick Installation Manual

  • Hello! I am an AI chatbot trained to assist you with the Power One AURORA PVI-6000-TL Quick Installation Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1.
3.2.
4.
6.
5.
7.
IMPORTANT SAFETY INSTRUCTION
QUICK INSTALLATION GUIDE
SELECT INSTALLATION LOCATION
SWITCHBOX WIRING DETAILWALL MOUNTING
DC ARRAY CONNECTIONS - INDEPENDENT MODE
AC GRID CONNECTIONS
DC ARRAY CONNECTIONS - PARALLEL MODE
SIGNAL WIRING CONNECTIONS
QUICK INSTALLATION GUIDE
AURORA PVI-5000/6000-TL
AURORA PVI-5000/6000-TLAURORA PVI-5000/6000-TL
QUICK INSTALLATION GUIDEQUICK INSTALLATION GUIDE
BCM.00163.0_AA
Quick Installation Guide
AURORA PVI-5000/6000-TL
This Quick Installation Guide is oered in addition to the full Technical
Manual which can be found on the CD accompanying this guide and the
Power-One Renewable Energy website at: http://www.power-one.com.
The installation is to be done according to the applicable local code
regulations (National Electric Code (NEC), Canadian Electric Code (CEC),
and/or other local codes and regulations).
This Quick Installation Guide applies to the following AURORA® UNO
Inverter transformerless models:
PVI-5000-OUTD-US, PVI-5000-OUTD-US-A
PVI-6000-OUTD-US, PVI-6000-OUTD-US-A
All model dimensions are 41.4”H x 12.8”W x 8.6”D and weigh 59.5 lbs (27
kg).The -A model includes an Integrated PV AFCI Type 1 device for arc fault
detection (AFD section 12) mounted on the rail in the wiring box (Figure 2).
Wiring connections are the same for both models unless specied.
SAVE THESE INSTRUCTIONS - KEEP IN A SAFE PLACE!
This is a list of special safety symbols used in this guide. The symbol usage is as follows:
CAUTION: Indicates directions which must be understood and followed in order to avoid
potential safety hazards, including equipment damage or personal injury.
DANGEROUS VOLTAGE: The product works with high voltages. During inverter operation,
parts will be energized at voltage levels.
HOT TEMPERATURE: Some surfaces may become hot. Do not touch the product while it is
in operation.
UL 1741 Standard for Safety for Inverters, Converters, Controllers and nterconnection System
Equipment for use with Distributed Energy Resources. CSA-C22.2 No. 107.1-01 - General Use
Power Supplies.
ELECTRICAL CONNECTION WARNINGS - The PV source conductors must be Listed PV wire per NEC
690.35. PV output conductors shall consist of sheathed (jacketed) multi-conductor cables or installed
in an approved raceway and must be isolated from the enclosure and system grounding, as required by
NEC 690.35 and is the responsibility of the installer.
An external DC switch must be used if not integrated in the inverter. All models listed above have an
integrated DC switch.
The inverter shall be connected only to a dedicated branch circuit provided with the maximum branch
OCPD listed in the Technical data sheet, section 14. To reduce the risk of re, connect only to a circuit
provided with 25A, 30A, 35A for PVI-5000-OUTD-US(-A) or 30A, 35A, 40A for PVI-6000-OUTD-US(-A)
maximum branch circuit overcurrent protection in accordance with the NEC (ANSI/NFPA 70).
The installer and/or operator must protect the installation from access by the public and/or highlight
with signs or notices the hazards of the equipment.
Select a well-ventilated location sheltered from direct sun radiation or any other heat source (other
inverters). Choose a location that allows unobstructed airow around the inverter. Maintain minimum
clearance distances shown.
For multiple inverter installations, position the inverters side-by-side or in a staggered arrangement so
heat dissipation does not aect other inverters; maintain minimum clearances shown.
Package contents include:
1 AURORA Inverter
1 Mounting bracket
1 Hardware bag containing:
2 - Terminal connectors
4 - 6.3 x 70mm screws
4 - S x 10 wall plugs
1 - Red cable AWG #10
1 - Black cable AWG # 10
1 - 6 x 10mm machine screw
1 - 6mm at washer
1 - Torx 20 wrench
1 Quick Installation Guide
1 CD with Software, Warranty, and full
Technical Manual
The inverter can be congured with two independent maximum power point tracking (MPPT) channels
(Figure 3) or as a single channel with one MPPT by paralleling the two channels (Figure 4 and Figure 5).
Switch S1 (Figure 6), is used to select parallel (PAR) or independent (IND) input mode.
To access the switchbox wiring and Switch S1, loosen the four captive screws on the front covers using
the Torx wrench provided.
Before removing front covers, DC switch must be in the OFF position.
Using DC knockouts (Figure 1), connect raceway from the PV array conduits to the DC array. Pull array
wiring through and connect to String 1 and String 2 as shown in Figure 3.
TO STRING 1 TO STRING 2
TO STRING 4
(OPTIONAL)
TO STRING 3
(OPTIONAL)
Input Mode Switch S1 in IND
(down) default position
Switch S1, located on the
inverter connection board,
Figure 6, is set in IND
position (DOWN) by default.
Figure 1: Switch and wiring box external/ internal view
Connect array to String 1 and String 2 input positions shown, running separate wires for POS and NEG
for each array. Up to four strings can be connected in the INDEPENDENT mode.
To connect four strings, String 3 and String 4 are connected in addition to 1 and 2, running separate
wires for POS and NEG for each array.
The maximum allowable input short circuit current limit of the PV array for each MPPT
input channel is 22Adc.
Array equipment grounding must be installed per the requirements of the NEC and is
the responsibility of the installer. The transformerless design requires that the PV array
to be oating with respect to ground per NEC 690.35.
Power-One DOES NOT provide AC output overcurrent protection; it is the
responsibility of the end user to provide protection for the AC output circuit.
The AC grid wiring is connected through the inverter switchbox. Run an
approved raceway between inverter and external AC disconnect switch.
Make conduit entry through openings B or E shown in Figure 1. Connect
AC wiring to switch box terminal block J and the main AC ground cable to
switchbox terminal block K.
Table 1, (which is also found on a label in the switchbox), shows AC wiring
connections according to the AC grid type; connect wiring to the numbered
terminals based on selected grid type.
Size conductors per NEC Article 310; Use 90°C copper wire only.
Terminal block accommodates wire size range of 14-4 AWG.
Table 1: Grid standard
The default 240V-SPLIT-PHASE connection requires the grid Neutral to be connected
for proper operation.
Before connecting the inverter to the grid, the grid type must be selected if it diers
from the default 240V-SPLIT-PHASE setting. See Section 9 for instructions to change
the default.
* IMPORTANT: If several AURORA inverters are installed to a three-phase AC GRID,
always distribute the inverters between the phases in order to reduce power
imbalance between the phases. Always refer to the local standards.
PARALLEL TWO INPUTS WHEN:
The current from PV array exceeds 22 Adc or the array power exceeds limit for
single channel (section 14). Refer to section 4 to access the switchbox wiring
and and connect raceway from the PV array conduits to the DC array. Place
switch S1 in the PAR position (UP) to congure inverter in parallel mode.
For -S versions only, in the switchbox, parallel the two MPPT inputs of
terminal [–IN1 and –IN2] and [+IN1 and +IN2],using the two #10 AWG jumper
wires (provided with inverter), 1 black and 1 red, connecting the input as shown
in Figure 4.
For -A versions only, in the inverter box, parallel the two MPPT inputs of
terminal [–IN1 and –IN2] and [+IN1 and +IN2] , using the two #10 AWG jumper
wires (provided), 1 black and 1 red, connecting the input as shown in Figure 5.
Input Mode Switch
S1 in PAR (UP)
position
TO STRING 1 TO STRING 2
Paralleling jumpers
required for
PARALLEL input
mode operation
-S version only
Paralleling jumpers required for
PARALLEL input mode operation
-A version only
Figure 4: Parallel connection of DC array
in the switchbox -S version
Figure 5: Parallel connection of DC array
in the inverter box -A version
S
RQ
T
P
Label Inverter Connection Board Details
PInput Mode Selector Switch S1
QExternal alarm Out Terminals
RRS-485 Terminal Block*
SRS-485 RJ45 Connector**
TRS-485 Line Termination Resistor Switch S2
* REM-Remote control not available for -A model;
terminal +R not accessible with AFD
** DO NOT CONNECT pin #4 when cabling units
with AFD installed.
Figure 6: Inverter connection board
Wiring for the RS-485 communication system and hardwired control options are routed through the
switchbox (openings D of Figure 1) and into the main inverter chassis for termination. Alarm and
monitoring connections are shown as items Q and R in Figure 6. If the terminal blocks are used, the
signal RTN, +T/R and –T/R have to be cabled.
RS-485 cable must be NRTL certied and provided
with additional protection by means of a non-
metallic tubing. Use Belden #3106A (or eq.) cable for
the RS-485 signals (RTN, ±T/R); ensure the ±T/R pair is
connected through the cable twisted pair. Strip 1/4”
insulation from all wires and connect to terminal block
as indicated in Figure 7.
Figure 7: Signal wiring terminal block
Systems with multiple inverters require the RS-485 cable to be daisy chained inverter-to-inverter and
there will be up to two RS-485 cables entering the inverter.
If a daisy chain connection is required for AFD installed inverters (-A models) use standard
multiconductor RS-485 cable and connect the three RS-485 leads (-RTN, +T/R, -T/R) USING ONLY
THE TERMINAL BLOCK. Do not use RJ45 connectors with AFD installations.
Locate Switch S2 on the inverter
board (Figure 6, label T). Conrm
the switch is up in the OFF position
for every inverter in the chain
except for the last inverter, which
must be turned ON.
Last inverter in Daisy Chain needs to have the switch S2 pushed
down into the ON position (Termination resistor active).
The default position of the S2 switch in the OFF position.
Inverter default address is 2.
If multiple inverters are connected in a daisy chain, each unit must be assigned a dierent RS-485
address. Refer to section 9 for instructions to assign addresses using the display menu.
The sum total length for all the RS-485 lines in the system must be less than 1000m (~1100 yards).
Communications cabling must not be combined into the AC or DC power conduits; run these in a
separate conduit.
Using the mounting bracket as a template, locate and
mark the desired mounting location.
Mount bracket to wall using four screws (provided)
through holes B. Two additional screws can be used in
position A if necessary.
Orient the bracket so the hooks C face out and up.
Hang the inverter on the bracket by lifting up
and over the mounting plate, engaging the
brackets C-D and E-F on the back.
Secure chassis bottom using machine screw
and washer (provided) through center bottom
hole H, engaging threaded insert in the bracket
G. Add additional screws as necessary through
bottom ange securing to mounting surface.
All -S and -A models have an integrated DC disconnect switch rated 600V/25A per contact. Maximum
array DC voltage input to each MPPT circuit is 600 Vdc under any condition.
The switch disconnects the DC current from the PV panels in the “OFF” position. The
inverter will stop producing power, but DOES NOT disconnect the AC from the grid.
Label Description
A DC conduit entry plastic
threaded plugs trade size 3/4”, 1”
BAC conduit entry plastic
threaded plugs trade size 3/4”, 1”
CDC Disconnect Switch
D
Signal cable opening with
plastic threaded plug, 1/2” trade
size
E
AC power cable opening with
plastic threaded plug; trade size 1”
F
DC power cable opening with
plastic threaded plug; trade size
3/4”, 1”
HCover screws (4)
J
AC grid output terminals, NOTE 1
KAC main ground, NOTE 2
LArray PE ground, NOTE 1
MAFD board (-A only)
Figure 1: Switch and wiring box external/ internal view
MPPT1 and MPPT2 DC array input, Note 1
M
NOTE 1: DC array wiring and ground
terminals are spring pressure type and
accommodate a wire size range of 16-6
AWG. AC output terminals are spring
pressure type and accommodate a wire
size range of 14-4 AWG.
NOTE 2: AC ground terminals are spring
pressure type and accept 16-4 AWG wire. Figure 2: Switch and wiring box with AFD mounted
on din rail -A model only (label M) AFD/ internal view
9.8.
11.10.
12.
14.
13.
QUICK INSTALLATION GUIDE
AURORA PVI-5000/6000-TL
QUICK INSTALLATION GUIDE
AURORA PVI-5000/6000-TL
AURORA PVI-5000/6000-TLAURORA PVI-5000/6000-TL
QUICK INSTALLATION GUIDE
SETTING RS-485 ADDRESS AND GRID TYPELED INDICATORS AND LCD
START-UP AND GRID CONNECTION ADJUSTMENT OF DISCONNECT PARAMETERS
ARC FAULT DETECTION -A MODELS ONLY
TECHNICAL DATA TABLE
POWER DERATING
BCM.00163.0_AA
A two-line Liquid Crystal Display (LCD) located in the center of the front panel (Figure 8) provides inverter
operating status and statistics, service messages, and alarm and fault indicators.
Three LED indicator lights on the left side of the display show system status:
• POWER LED (green) indicates the inverter is operating normally.
• ALARM LED (yellow) indicates a fault condition has been detected; a description will appear in the
two-line display.
• GFI LED (red) indicates the inverter has detected a ground fault in the DC side of the PV system.
LED INDICATORS PROGRAMMING
CONTROLS
TWO LINE
LCD DISPLAY
Figure 8: LED Indicators, controls, and two-line display
During operation the display cycles through available data points, updating every ve seconds. Screens
may be scrolled manually by pressing the UP and DOWN programming control keys (Figure 8).
Pressing the ESC key gives access to three main menus: Statistics - Settings - Info.
Use the UP and DOWN keys to scroll between the menus and press ENTER to make a selection. To return
to the preceding menu, press the ESC key.
The Statistics, Settings and Info menus can be accessed with just the array connected. Some parameters
(e.g. current, voltage, power, partial energy, lifetime energy etc.) are available only after grid connection.
Based on individual installations, the following parameters may need to be congured
prior to initial grid connection:
Based on individual installations, the following parameters may need to be congured prior to initial
grid connection:
• The RS-485 bus address for daisy chain (Section 9),
• AC grid type if dierent from default (Section 9),
• Adjustments to default frequency and disconnection time (Section 10).
Complete descriptions of the data available on the display menus can be found in the full manual on the
CD accompanying this guide or on the Power-One website.
For –A models only, an autotest circuit is included in the module design of Power-One’s DC ARC FAULT
DETECTOR and INTERRUPTOR (AFDI) solution. The AFDI performs a self-test when the system is started,
(ie every morning when sunlight is sucient for grid connection). The inverter display shows the results
of the self-test as described in section 11.
During normal operation, (while the inverter in connected to the grid), the input current is continually
measured and analyzed. If a DC arc fault is detected, the inverter is disconnected from the AC grid and
the error message ARC FAULT E050” will be shown on the inverter display.
Press and hold the ESC key for three seconds to clear the error which will start the self-test. If self-test
results are OK (section 11), the inverter will re-connect to the AC grid. If the DC arc fault is still present,
the self test will result in error message AF Self Test E053”. Refer to the Troubleshooting section in the
full technical manual for possible solutions to clear the error.
When the AFD protection trips continously an electrical arcing has taken place. In this
case Power-One recommends a complete and accurate check of DC connections.
The AF self test can be manually started anytime using the disconnect procedure below:
1. Turn o the inverter (switching o both DC and AC switches) and,
2. Turn on both the DC and AC switches waiting for display communication of self-test result.
Once the inverter has been wired and connected to the grid, use the following procedures to disconnect:
1. Disconnect from the AC Grid by turning OFF the external AC switch or turning OFF the Over
Current Protection Device (circuit breaker).
2. Disconnect the inverter from the PV array by turning OFF the external DC disconnect switch.
NOTE: When possible, turn o the AC switch rst, however, there is no specic order for turning o
the two switches.
WARNING: After shutdown, wait at least 10 minutes before removing guards or covers
in order to allow devices inside the unit to cool and any electrostatic charges and
parasitic voltages to be discharged.
When removing the inverter covers, always check voltage levels at the DC input
terminals and the AC output cables to ensure no hazardous voltages are present.
When multiple units have been connected in a daisy chain, the individual address will need to be
assigned prior to grid connection using the display menu. The grid default type, 240V Split Phase, can
also be changed prior to grid connection using the display menu.
With only the array connected, set the inverters DC disconnect switch to ON. GREEN
POWER LED will ash and YELLOW ALARM LED will be steady. The LCD will read “Missing
Grid”. Press ESC to open the menus. Use the DOWN key to scroll to Settings, and press
ENTER.
The Settings menu requires an access password.
Upon selecting SETTINGS the password screen will display; the default
password is 0000.
Pressing ENTER four times loads four zeroes on the display and opens
the submenu (Figure 9).
The LCD has two visible text lines and the UP and DOWN control
keys are used to scroll through the menu items. An arrow on the left
side of the display highlights the current selection. Move the arrow
UP or DOWN to the desired selection and press ENTER to access the
associated submenu (Figure 9). To return to the preceding menu, press
the ESC key.
Address and Set Vgrid are described below for use in installation.
Complete descriptions of the submenus can be found in the full
manual.
Figure 9: Settings submenus
Address: Scroll to Address and press Enter to open the
submenu. Address values are assigned manually using any
value in the range [2 to 64]. Press the UP and DOWN keys to
scroll through numbers and ENTER to select. Auto address = 1
and can be used only once; default address is set at 2.
Set VGrid: Scroll DOWN to Set VGrid and press ENTER to
open the submenu. To choose a grid connection dierent
from the 240V Split-phase default, use the UP or DOWN
key to move the arrow to the desired selection and
press ENTER. A second display screen will open; press
ENTER to conrm selection or ESC to cancel.
An inverter not in direct sunlight will output its maximum rated power up to at least 40C (almost 120F).
Power reduction and temperature at which it occurs depend on many operating parameters other than
ambient temperature, such as input voltage, grid voltage, and power available from the photovoltaic
modules. The inverter can decrease power output during certain periods of the day according to these
parameters.
PVI-5000-OUTD-US
Operating ambient temperature at full power (without derating): -25 °C...+ 60 °C
PVI-6000-OUTD-US
Operating ambient temperature at full power (without derating): -25 °C...+ 60 °C
To adjust frequency and disconnect times to meet local utility requirements, modications are made
using the Aurora Manager-TL software. The software, with instructions to download and install on a
PC, can be found on the CD included with this inverter. If an internet connection is available, check the
product page at www.power-one.com/renewable-energy to download the most recent version of the
software.
Prior to connecting to the grid, with the inverter’s DC disconnect switch set to ON, a computer, with
Aurora Manager-TL software installed, should be connected to the inverter via an RS-485-USB adapter
(not included). The USB driver les and instructions for installation can be found on the CD included
with the inverter or Power-One website. PC-inverter connection cable required is standard USB 2.0 cable,
terminals type A and B.
Launch the application from the computer desktop icon. At Select Mode screen, enter the address
assigned a single inverter and press Start. For multiple inverters press Scan to search All Inverters.
Grid parameters will be displayed. Default settings cause automatic disconnection from the grid in
160ms when line frequency is outside the range of 59.3 Hz < f < 60.5 Hz. Press the Write button to
change values of desired parameters to those required by the local utility.
After frequency and disconnect time values have been adjusted, turn DC power OFF and
ON to save new data. Changes to parameters must be made to meet the requirements of
the local utility. Entry of improper values could cause inverter to shut down.
Cond.
Simulated utility source Max.time (sec) at 60Hz
a
before cessation of current
to the simulated utility
Voltage (V) Frequency (Hz)
A<0.50 V
nor
b
Rated (60Hz) 0.16 (Fixed)
B0.50 V
nor
b
≤ V < 0.88 V
nor
(Adjustable) Rated (60Hz) 2 (Fixed)
C1.10 V
nor
b
< V<1.20 V
nor
(*)
(Adjustable) Rated (60Hz) 1 (Fixed)
D1.20V
nor
≤ V (*) Rated (60Hz) 0.16 (Fixed)
ERated f > 60.5 Hz (Default)
(Adj. 60.2 to 63.0 Hz)
0.16 (Default)
(Adj. 0.16 to 300 sec)
FRated f < 59.3 Hz (Default)
(Adj. 59.8 to 57.0 Hz)
0.16 (Default)
(Adj. 0.16 to 300 sec)
GRated f< 57.0 Hz 0.16 (Fixed)
HRated f > 63.0 Hz 0.16 (Fixed)
Table 2: Voltage/Frequency tolerances for Utility Interaction required by UL1741
The procedure for START-UP is as follows:
• Set the inverter’s DC disconnect switch to ON.
• Set the AC disconnect switch to the inverter to ON.
Once both disconnects are closed, the inverter starts the grid connection sequence. These screens are
initially displayed at start-up:
While the system checks for grid connection (Missing Grid) to be
established, the ALARM LED turns steady YELLOW and the POWER
LED ashes GREEN.
When waiting for sunlight (Waiting Sun) the POWER LED turns
steady GREEN. As soon as conditions are met, the inverter is
connected to the grid.
For –A versions ONLY, the display shows the AFD board self-test
running and results upon connection. If the self-test results are
OK, the inverter will continue to Next connections.
If a potential problem on the AFD board is detected, the self-test
will result in error. Refer to the Troubleshooting section in the full
technical manual for possible solutions to clear the error.
All versions will display the following screens during connection: the time (seconds) remaining to
complete the output voltage and frequency values check, and whether the values are within range.
A nal display screen for insulation resistance (RISO) is displayed.
If all items described above test OK, the inverter is connected to
the grid and displays the message, “Inverter OK”, along with the
date and time.
Clock malfunctioning, or other non-function related faults that do
not interfere with operation, may be shown instead of the date
and time.
* All data is subject to change without notice **Inverter can apply that much current – Breaker will open
3AURORA UNO
Standard - With DC Switch - Floating Array and Arc Fault Detection (AFD) PVI-5000-OUTD-US-A PVI-6000-OUTD-US-A
TECHNICAL DATA VALUES PVI-5000-OUTD-US PVI-6000-OUTD-US
Nominal Output Power W 5000 6000
Maximum Output Power W 5000 6000
Rated Grid AC Voltage V 208 240 277 208 240 277
Input Side (DC)
Number of Independent MPPT Channels 2 2
Maximum Usable Power for Each Channel W 4000 4000
Absolute Maximum Voltage (Vmax) V 600 600
Start- Up Voltage (Vstart) V 200 (adj. 120-350 ) 200 (adj. 120-350 )
Full Power MPPT Voltage Range V 200-530 200-530
Operating MPPT Voltage Range V 0.7xVstart-580 0.7xVstart-580
Maximum Current (Idcmax) for both MPPT in Parallel A 36 36
Maximum Usable Current per Channel A 18 18
Maximum Short Circuit Current Limit per Channel A 22 22
Number of Wire Landing Terminals Per Channel 2 Pairs 2 Pairs
Array Wiring Termination Terminal block, Pressure Clamp, AWG8-AWG4
Output Side (AC)
Grid Connection Type 1Ø/2W Split-Ø/3W 1Ø/2W 1Ø/2W Split-Ø/3W 1Ø/2W
AdjustableVoltage Range (Vmin-Vmax) V 183-228 211-264 244-304 183-228 211-264 244-304
Grid Frequency Hz 60 60
Adjustable Grid Frequency Range Hz 57-60.5 57-60.5
Maximum Current (Iacmax) A
RMS
27 23 20 30 28 24
Power Factor > 0.995 > 0.995
Total Harmonic Distortion At Rated Power % < 2 < 2
Contributory Fault Current** A
pk
/A
RMS
36.25/25.63 36.5/25.81 31.75/22.45 36.25/25.63 36.5/25.81 31.75/22.45
Grid Wiring Termination Type Terminal block, Pressure Clamp, AWG8 - AWG4
Protection Devices
Input
Reverse Polarity Protection Yes Yes
Over-Voltage Protection Type Varistor, 2 for each channel Varistor, 2 for each channel
PV Array Ground Fault Detection Pre start-up Riso and dynamic GFDI
(Requires Floating Arrays)
Pre start-up Riso and dynamic GFDI
(Requires Floating Arrays)
Output
Anti-Islanding Protection Meets UL 1741/IEEE1547 requirements Meets UL 1741/IEEE1547 requirements
Over-Voltage Protection Type Varistor, 2 (L
1
- L
2
/ L
1
- G) Varistor, 2 (L
1
- L
2
/ L
1
- G)
Maximum AC OCPD Rating A 35 30 25 40 35 30
E
Maximum E % 97.1 97.1
CEC E % 96 96.5 96.5 96 96.5 96.5
Operating Performance
Stand-by Consumption W
RMS
< 8 < 8
Night time consumption W
RMS
< 0.6 < 0.6
Communication
User-Interface 16 characters x 2 lines LCD display
Remote Monitoring (1xRS485 incl.) AURORA-UNIVERSAL (opt.)
Wired Local Monitoring (1xRS485 incl.) PVI-USB-RS485_232 (opt.), PVI-DESKTOP (opt.)
Wireless Local Monitoring PVI-DESKTOP (opt.) with PVI-RADIOMODULE (opt.)
Environmental
Ambient Air Operating Temperature Range °F (°C) -13 to +140 (-25 to +60) -13 to +140 (-25 to +60)
with derating above 122 (50)
Ambient Air Storage Temperature Range °F (°C) -40 to 176 (-40 to +80) -40 to 176 (-40 to +80)
Relative Humidity % RH 0-100 condensing 0-100 condensing
Acoustic Noise Emission Level db (A) @1m < 50 < 50
Maximum Operating Altitude without Derating ft(m) 6560 (2000) 6560 (2000)
Mechanical S
Enclosure rating NEMA 4X NEMA 4X
Cooling Natural Convection Natural Convection
Dimensions (H x W x D) in (mm) 41.4 x 12.8 x 8.6 (1052 x 325 x 218)
Weight lb (kg) < 59.5 (27.0) < 59.5 (27.0)
Shipping Weight lb (kg) < 78 (35.4) < 78 (35.4)
Mounting System Wall bracket Wall bracket
Conduit Connections Trade Size Kos: (2ea x 1/2”)
and (2ea x 1-1/4”, 3 places side, front, rear)
Trade Size Kos: (2ea x 1/2”)
and (2ea x 1-1/4”, 3 places side, front, rear)
DC Switch Rating (Per Contact) A/V 25 / 600 25 / 600
Safety
Isolation Level Transformerless (Floating Array) Transformerless (Floating Array)
Safety and EMC Standard UL 1741, CSA - C22.2 N. 107.1-01 UL 1741, CSA - C22.2 N. 107.1-01
Safety Approval
c
CSA
us c
CSA
us
Warranty
Standard Warranty years 10 10
Extended Warranty years 15 & 20 15 & 20
Available Models
Standard - With DC Switch - Floating Array PVI-5000-OUTD-US PVI-6000-OUTD-US
/