783034400aUK– Translation into English of the original German operating manual – Subject to technical change without notice. © ait-deutschland GmbH
NOTE
The impressed current anode does not function until the
tank is lled with water.
- The top indicator lamp lights up green: Power supply connected
and the impressed current anode is ready for use.
- If none of the indicator lamps lights up there it is probable that no
mains voltage has been applied.
- If the bottom indicator lamp lights up red a malfunction exists.
In this case carry out the checks described in the “Faults during
operation” chapter.
NOTE
If the red indicator lamp then lights up following re-
installation it is probably an installation-related fault. Check
and correct this as per the notes in the “Faults during
operation” chapter.
NOTE
If the malfunction indicator lamp lights up red following re-
installation it is probably an installation-related fault. Check
and correct this as per the notes in the “Faults during
operation” chapter.
Operation and maintenance
The coating of the titanium anode is subjected to virtually no wear.
The indicator lamps must be checked once a month:
- The indicator lamp lights up green: Power supply connected and
the impressed current anode is ready for use.
- If neither of the two indicator lamps lights up phone your installer
or customer service.
- If the indicator lamp lights up red: phone your installer or
customer service for troubleshooting information.
To ensure faultless functioning of the impressed current anode the
following safety instructions must be followed:
1. Do not operate the storage water heater for longer than 2
months without drawing off any water. Otherwise spurious gas
accumulations can occur.
2. Do not disconnect the plug housing from the main supply while
the storage water heater is lled. Otherwise there is no longer
any protection against corrosion.
3. Never disconnect the connection cables if the storage water
heater is full. Otherwise there is no longer any protection against
corrosion.
4. Do not withdraw the impressed current anode from service even
during lengthy stoppages (e.g. holiday). Otherwise there is no
longer any protection against corrosion.
5. Do not disconnect the plug housing or connection cable unless
the storage tank is empty.
Faults during operation of the impressed current
anode
Operating faults in the impressed current anode are normally
indicated by a red LED on the connector housing of the potentiostat.
NOTE
Many causes of faults can be found and corrected directly
at the system with the help of direct voltage, direct current,
polarity, insulation and resistance measurements. The
methods required are described in the “measurement
measures” chapter. Disconnect any installed electrical
tubular heaters from the power supply. The inspections
described may only be carried out by the installer or
competent customer service.
Fault messages, their possible causes and appropriate
troubleshooting measures are described in the following.
FAULT MESSAGES, POSSIBLE CAUSES AND
TROUBLESHOOTING MEASURES
Fault message: Indicator lights do not light up
Possible cause: no mains voltage applied.
Troubleshooting: Ensure continuous mains power supply.
Fault message: Indicator light is lit red
“Reset” the potentiostat by disconnecting the unit from the mains for
approx. 30 seconds to set a dened starting situation. Then supply
the unit with mains voltage once more.
If the LED is still lit red, check the possible causes of faults described
in the following and carry out the troubleshooting measures given.
1. The storage water heater is not lled with water.
Check: Determine whether the storage water heater is
completely lled with water.
Troubleshooting: if necessary ll the storage water heater
completely with water.
2. Electrical continuity between the plug-in potentiostat and anode
/ tank connection is not ensured along the whole connection
cable. Check: All connections and contacts for faultless, metallic
conducting, electrical contact. Troubleshooting: Establish
electrical contact, if not already done, if necessary install new
connection cable.
3. The electrode is not insulated properly from the tank wall or
tank installations. Check: Insulation of the electrode when tank
is drained of water; measurement troubleshooting measures:
Correct the position of the installations and anode if necessary.
NOTE
If the tank is dry the electrical resistance between the
titanium anode and the tank earth must be very high-
resistance, ideally: innite.
4. Check for overloading of the plug-in potentiostat: Check the
protective current actually output
Troubleshooting: Check the use of a more powerful potentiostat
to protect storage tanks made of stainless steel.
Background: The plug-in potentiostat is overloaded if protective
currents within the range of approx. 100 mA and higher are
demanded, whereby the actual overload value depends on
the respective drive voltage. A safe value for drinking water
applications is 50 mA protective current for each square metre
of stainless steel storage water heater surface to be protected.
The impressed current anode can therefore cathodically protect
2 m
2
surface reliably, possibly more depending on the water