ProSoft Technology 5127-MCM-HART Owner's manual

Category
Gateways/controllers
Type
Owner's manual
MCM
ProLinx Gateway
Modbus Master/Slave
10/16/2009
DRIVER MANUAL
Important Installation Instructions
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-
4 (b) of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of the
Canadian Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction.
The following warnings must be heeded:
A WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIV. 2;
B WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES
C WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
D THIS DEVICE SHALL BE POWERED BY CLASS 2 OUTPUTS ONLY.
All ProLinx
®
Products
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
AVERTISSEMENT – RISQUE D'EXPLOSION – AVANT DE DÉCONNECTER L'EQUIPMENT, COUPER LE
COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX.
Markings
UL/cUL ISA 12.12.01 Class I, Div 2 Groups A, B, C, D
cUL C22.2 No. 213-M1987
243333 183151
CL I Div 2 GPs A, B, C, D
Temp Code T5
II 3 G
Ex nA nL IIC T5 X
0° C <= Ta <= 60° C
II – Equipment intended for above ground use (not for use in mines).
3 – Category 3 equipment, investigated for normal operation only.
G – Equipment protected against explosive gasses.
ProLinx Gateways with Ethernet Ports
Series C ProLinxâ„¢ Gateways with Ethernet ports do NOT include the HTML Web Server. The HTML Web
Server must be ordered as an option. This option requires a factory-installed hardware addition. The HTML Web
Server now supports:
 8 MB file storage for HTML files and associated graphics files (previously limited to 384K)
 32K maximum HTML page size (previously limited to 16K)
To upgrade a previously purchased Series C model:
Contact your ProSoft Technology distributor to order the upgrade and obtain a Returned Merchandise
Authorization (RMA) to return the unit to ProSoft Technology.
To Order a ProLinx Plus gateway with the -WEB option:
Add -WEB to the standard ProLinx part number. For example, 5201-MNET-MCM-WEB.
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions,
comments, compliments or complaints about the product, documentation, or support, please write or call us.
ProSoft Technology
5201 Truxtun Ave., 3rd Floor
Bakersfield, CA 93309
+1 (661) 716-5100
+1 (661) 716-5101 (Fax)
www.prosoft-technology.com
support@prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2009. All Rights Reserved.
MCM Driver Manual
10/16/2009
ProSoft Technology
®
, ProLinx
®
, inRAx
®
, ProTalk
®
, and RadioLinx
®
are Registered Trademarks of ProSoft
Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify
products and services of, their respective owners.
ProSoft Technology
®
Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product
shipments. User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided on the
enclosed CD-ROM, and are available at no charge from our web site: www.prosoft-technology.com
Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability.
North America: +1.661.716.5100
Asia Pacific: +603.7724.2080
Europe, Middle East, Africa: +33 (0) 5.3436.87.20
Latin America: +1.281.298.9109
Contents
Important Installation Instructions...................................................................................................2
Your Feedback Please...................................................................................................................3
ProSoft Technology
®
Product Documentation................................................................................3
1 Start Here 7
1.1 System Requirements...........................................................................................7
1.2 Package Contents.................................................................................................8
1.3 Mounting the gateway on the DIN-rail....................................................................9
1.4 Connecting Power to the Unit................................................................................9
1.5 Install ProSoft Configuration Builder Software ..................................................... 10
1.6 Using PCB Help..................................................................................................10
2 Functional Overview 11
2.1 Modbus Master/Slave Port(s)..............................................................................11
2.2 Serial Port Specifications....................................................................................12
2.3 Modbus Master/Slave Port Specifications............................................................13
2.4 Module Internal Database...................................................................................14
3 MCM Protocol Configuration 17
3.1 [Modbus Port x]...................................................................................................18
3.2 [Modbus Port X Commands] ...............................................................................27
4 Serial Port Modbus Error and Status Data 33
4.1 Viewing Error and Status Data ............................................................................33
4.2 Modbus Error and Status Data Area Addresses ..................................................34
4.3 Error Codes ........................................................................................................39
5 Communication Port Cables 41
5.1 Port 0, 1, 2, 3: RS-232 - Null Modem (DTE with Hardware Handshaking) ............42
5.2 Port 0, 1, 2, 3: RS-232 - Null Modem (DTE without Hardware Handshaking) .......42
5.3 Port 0, 1, 2, 3: RS-232 - DTE to DCE Modem Connection...................................43
5.4 Port 0, 1, 2, 3: RS-422 Interface Connections......................................................43
5.5 Port 0, 1, 2, 3: RS-485 Interface Connections......................................................44
6 LED Indicators 45
6.1 Common gateway LEDs......................................................................................45
6.2 LEDs for Serial Ports...........................................................................................46
7 Modbus Port Expander (4102/5102-MBS3-MBM) 47
7.1 [Modbus Master Port]..........................................................................................47
7.2 [Modbus Slave Port x].........................................................................................51
8 Reference 57
8.1 Modbus Protocol Specification............................................................................ 57
8.2 Moving Data using the Data Map........................................................................ 70
9 Support, Service & Warranty 71
9.1 How to Contact Us: Technical Support................................................................ 71
9.2 Return Material Authorization (RMA) Policies and Conditions.............................. 72
9.3 LIMITED WARRANTY........................................................................................ 73
Index 79
Start Here MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 7 of 80
October 16, 2009
1 Start Here
In This Chapter
î‚™ System Requirements..........................................................................7
î‚™ Package Contents...............................................................................8
î‚™ Mounting the gateway on the DIN-rail...................................................9
î‚™ Connecting Power to the Unit...............................................................9
î‚™ Install ProSoft Configuration Builder Software.....................................10
1.1 System Requirements
The configuration software for the MCM gateway requires the following minimum
hardware and software components:
 Pentium
®
II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
 Supported operating systems:
o Microsoft Windows Vista
o Microsoft Windows XP Professional with Service Pack 1 or 2
o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
o Microsoft Windows Server 2003
 128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
 100 Mbytes of free hard disk space (or more based on application
requirements)
 256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 × 768 recommended)
 CD-ROM drive
MCM ♦ ProLinx Gateway Start Here
Modbus Master/Slave Driver Manual
Page 8 of 80 ProSoft Technology, Inc.
October 16, 2009
1.2 Package Contents
The following components are included with your MCM gateway, and are all
required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are
present.
Qty. Part Name Part Number Part Description
1 MCM
gateway
PLX-#### ProLinx communication gateway gateway
1 Cable Cable #15, RS232
Null Modem
For RS232 Connection from a PC to the CFG Port
of the gateway
Varies Cable Cable #9, Mini-DIN8
to DB9 Male
Adapter
For DB9 Connection to gateway’s Port. One DIN to
DB-9M cable included per configurable serial port,
plus one for gateway configuration
Varies Adapter 1454-9F Adapters, DB9 Female to Screw Terminal. For
RS422 or RS485 Connections to each serial
application port of the gateway
1 ProSoft
Solutions CD
Contains sample programs, utilities and
documentation for the MCM gateway.
If any of these components are missing, please contact ProSoft Technology
Support for replacements.
Start Here MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 9 of 80
October 16, 2009
1.3 Mounting the gateway on the DIN-rail
ProLinx 5000/6000 Series gateway
1.4 Connecting Power to the Unit
WARNING: Ensure that you do not reverse polarity when applying power to the gateway. This will
cause damage to the gateway’s power supply.
MCM ♦ ProLinx Gateway Start Here
Modbus Master/Slave Driver Manual
Page 10 of 80 ProSoft Technology, Inc.
October 16, 2009
1.5 Install ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software in order to
configure the gateway. You can always get the newest version of ProSoft
Configuration Builder from the ProSoft Technology web site.
To install ProSoft Configuration Builder from the ProSoft Web Site
1 Open your web browser and navigate to http://www.prosoft-
technology.com/pcb
2 Click the D
OWNLOAD HERE link to download the latest version of ProSoft
Configuration Builder.
3 Choose "S
AVE" or "SAVE FILE" when prompted.
4 Save the file to your Windows Desktop, so that you can find it easily when
you have finished downloading.
5 When the download is complete, locate and open the file, and then follow the
instructions on your screen to install the program.
If you do not have access to the Internet, you can install ProSoft Configuration
Builder from the ProSoft Solutions CD-ROM, included in the package with your
gateway.
To install ProSoft Configuration Builder from the Product CD-ROM
1 Insert the ProSoft Solutions Product CD-ROM into the CD-ROM drive of your
PC. Wait for the startup screen to appear.
2 On the startup screen, click P
RODUCT DOCUMENTATION. This action opens a
Windows Explorer file tree window.
3 Click to open the U
TILITIES folder. This folder contains all of the applications
and files you will need to set up and configure your gateway.
4 Double-click the S
ETUPCONFIGURATIONTOOL folder, double-click the
"PCB_*.
EXE" file and follow the instructions on your screen to install the
software on your PC. The information represented by the "*" character in the
file name is the PCB version number and, therefore, subject to change as
new versions of PCB are released.
Note: Many of the configuration and maintenance procedures use files and other utilities on the
CD-ROM. You may wish to copy the files from the Utilities folder on the CD-ROM to a convenient
location on your hard drive.
1.6 Using PCB Help
Most of the information needed to help you use is provided in a Help System
that is always available whenever you are running . The Help System does not
require an Internet connection.
To view the help pages, start , open the H
ELP menu, and then choose CONTENTS.
Functional Overview MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 11 of 80
October 16, 2009
2 Functional Overview
In This Chapter
î‚™ Modbus Master/Slave Port(s).............................................................11
î‚™ Serial Port Specifications...................................................................12
î‚™ Modbus Master/Slave Port Specifications...........................................13
î‚™ Module Internal Database..................................................................14
The Modbus Master/Slave protocol driver may exist in a single port (MCM) or a
multiple port (MCM4) implementation. In either case, each port can be
independently configured as a Master or Slave port to interface, as required, with
other Modbus devices.
2.1 Modbus Master/Slave Port(s)
The Modbus Master ports can be used to continuously interface with Modbus
slave devices over a serial communication interface (RS-232, RS-422 or RS-
485). Each Master port may have up to 100 user defined commands which
determine the Modbus read/write messages issued to each slave attached to the
port.
In addition, the gateway can be configured to poll slave devices that are not
responding to commands at a lower priority (slow-poll mode). If a slave device
has failed to respond to a command after a user-defined number of retries, the
driver will recognize the slave is experiencing a communication failure. In this
case, if you have set a non-zero value in the Error Delay Count parameter in the
Master port configuration, then, as the driver comes to a command on the Master
Command List that should be sent to the failing slave, instead of sending the
command, the driver will skip the command and decrement the error delay
counter value by one.
When the number of commands have been skipped is equal to the value set in
the Error Delay Count parameter, the error delay counter will have been
decremented go zero and the driver will send next command for that node in the
command list. If the slave responds properly to this command, the driver will
resume normal polling of this slave. If the new command fails, the driver will
continue to recognize the slave is experiencing communication problems and
repeat the process of skipping commands and decrementing the error delay
counter before trying to send another command to that slave. This has the effect
of putting the slave in a low-priority, slow-poll mode until it begins to
communicate normally again.
MCM ♦ ProLinx Gateway Functional Overview
Modbus Master/Slave Driver Manual
Page 12 of 80 ProSoft Technology, Inc.
October 16, 2009
2.2 Serial Port Specifications
Type Specifications
Serial Ports
Serial Port Adapter Cables One MiniDIN to DB-9M adapter cable included for
each configurable serial port
Config Port Connector/ Pinout DB-9F connector / DTE pinout
Serial Port Isolation 2500V RMS port-to-port isolation per UL 1577.
3000V DC min. port to ground and port to logic
power isolation.
Serial Port Protection RS-485/422 port interface lines TVS diode protected
at +/- 27V standoff voltage.
RS-232 port interface lines fault protected to +/- 36V
power on, +/- 40V power off.
Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered and can handle communications up to 115,200 baud.
Functional Overview MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 13 of 80
October 16, 2009
2.3 Modbus Master/Slave Port Specifications
Type Specifications
General Parameters
Internal Database Up to 4000 registers (words) available.
Communication parameters Port 0: Baud Rate: 110 to 115K baud possible
110 to 38.4K baud recommended for all applications.
Higher baud rates are recommended only for use
with very slow Modbus polling rates (e.g. 1command
or less per second)
Port 1, 2, 3: Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 5 to 8 bits
Parity: None, Even, Odd, Mark, Space
RTS Timing delays: 0 to 65535 milliseconds
Modbus Modes RTU mode (binary) with CRC-16
ASCII mode with LRC error checking
Floating Point Data Floating point data movement supported, including
configurable support for Enron implementation
Modbus Function Codes 1: Read Coil Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single Register
15: Force(Write) Multiple Coils
16: Force (Write) Multiple Register
Modbus Master
Command List Up to 100 command per Master port, each fully
configurable for function, slave address, register
to/from addressing and word/bit count
Status Data Error codes available on an individual command
basis. In addition, a slave status list is maintained
per active Modbus Master port.
Polling of command list Configurable polling of command list, including
continuous and on change of data
Modbus Slave
Node address 1 to 247 (software selectable)
Status Data Error codes, counters and port status available per
configured slave port starting at memory register
4400.
MCM ♦ ProLinx Gateway Functional Overview
Modbus Master/Slave Driver Manual
Page 14 of 80 ProSoft Technology, Inc.
October 16, 2009
2.4 Module Internal Database
The internal gateway database is central to the functionality of the gateway. This
database is shared between all the ports on the gateway This permits data from
devices on one communication network port to be viewed and controlled by
devices on another port or network.
Other ProLinx
Protocol
Driver
Modbus
Slave
Driver
Modbus
Master
Driver
ProLinx
Communication
Gatewa
y
s
Internal
Database
(
Up to 4000 re
g
s
)
Other ProLinx
Protocol
Driver
Modbus
Slave
Driver
Modbus
Master
Driver
ProLinx
Communication
Gatewa
y
s
Internal
Database
The Master driver uses the database in two ways:
 A read command issued to a slave device by the Master driver will return the
slave data into the internal database.
 A write command issued to a slave device by the Master driver uses the data
in the internal database as the source data to send to the slave.
The slave driver allows external Master devices to access the database, reading
data from the database or writing data to the database. External Modbus Master
devices can monitor and control data in this database through any port
configured as a slave.
Status and error data from the slave and Master ports generated by the gateway
can be mapped into the internal database, where it can be retrieved by either
protocol driver.
Functional Overview MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 15 of 80
October 16, 2009
2.4.1 Modbus Port Access to Database
The Modbus slave support in the gateway permits remote Master applications
(that is, HMI software, Quantum processors, and so on) to read from and write to
the gateway’s database.
When configured as a slave, the internal database of the MCM gateway is used
as the source for read requests and the destination for write requests from
remote Masters. Access to the database is controlled by the command type
received in the incoming message from the remote Master. The following table
defines the relationship of the gateway’s internal database to the addresses
required in the incoming Modbus TCP/IP requests:
Database Address Modbus Address
0 40001 (five-digit addressing) or 400001 (six-digit addressing)
1000 41001 or 410001
2000 42001 or 420001
3000 43001 or 430001
3999 44000 or 440000
The following virtual addresses are not part of the normal gateway user database
and are not valid addresses for standard data. However, these addresses may
be used for incoming commands that are requesting 32-bit floating-point data. To
use addresses in this upper range requires you to:
1 Set the Float Flag (page 19) to Y
ES
2 Set the Float Start (page 19) to a database address in the range below
3 Set the Float Offset (page 20) to a database address in the gateway user
memory area shown above.
Remember that, once you do this, all data in addresses above the Float Offset
address will be treated as 32-bit floating-point data and require two gateway
memory registers per Modbus address.
Database Address Modbus Address
4000 44001 (five-digit addressing) or 440001 (six-digit addressing)
5000 45001 or 450001
6000 46001or 460001
7000 47001 or 470001
8000 48001 or 480001
9000 49001or 490001
9999 50000 or 500000
MCM ♦ ProLinx Gateway Functional Overview
Modbus Master/Slave Driver Manual
Page 16 of 80 ProSoft Technology, Inc.
October 16, 2009
MCM Protocol Configuration MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 17 of 80
October 16, 2009
3 MCM Protocol Configuration
In This Chapter
î‚™ [Modbus Port x] .................................................................................18
î‚™ [Modbus Port X Commands] ..............................................................27
#This is an example of a Master port using Modbus RTU protocol
[Modbus Port 0]
# Settings required by both Master and Slave
Enabled : Yes #Port enable flag Y=Yes, N=No
RS Interface : 0 #0=RS-232, 1=RS-485, 2=RS-422
Type : Master #Port type M=Master, S=Slave
Float Flag : No #Use floating data type Y=Yes, N=No
Float Start : 7000 #Register offset in message for floats
Float Offset : 2000 #Internal Address for floats
Protocol : RTU #Modbus Protocol R=RTU, A=ASCII
Baud Rate : 384 #Baud rate for port
Parity : None #N=None, O=Odd, E=Even
Data Bits : 8 #5 to 8 data bits for messages
Stop Bits : 1 #1 or 2 stop bits for messages
RTS On : 0 #Delay after RTS set before msg sent (mSec)
RTS Off : 1 #Delay after message before RTS dropped(mSec)
Minimum Response Delay : 2 #Number of mSec to delay before respose
Use CTS Line : No #Monitor CTS modem line (Y/N)
Response Timeout : 1000 #mSec for response timeout of command
Retry Count : 2 #retry count for failed requests
# Settings required for Slave Driver
Internal Slave ID : 1 #Modbus Node address for this port on network
Bit Input Offset : 0 #Internal DB offset to bit input data
Word Input Offset : 0 #Internal DB offset to word input data
Output Offset : 0 #Internal DB offset to bit output data
Holding Register Offset : 0 #Internal DB offset to holding reg data
Use Guard Band Timer : N #Use packet gap timeout for messages
Guard Band Timeout : 0 #0=Use default for baudrate, or set timeout
# Settings required for Master Driver
Minimum Command Delay : 0 #mSec delay between commands
Error Delay Counter : 100 #0-65535 Command cycle count if error
Command Control Reg : -1 #DB start reg for Cmd Control (-1=disable)
[Modbus Port 0 Commands]
# Internal Poll Reg Swap Node Modbus MB Address
# Enable Address Interval Count Code Address Func in Device
START
1 0 0 10 0 1 3 0
1 10 0 10 0 1 4 10
END
MCM ♦ ProLinx Gateway MCM Protocol Configuration
Modbus Master/Slave Driver Manual
Page 18 of 80 ProSoft Technology, Inc.
October 16, 2009
3.1 [Modbus Port x]
The [Modbus Port x] sections of the CFG file, where x stands for 0, 1, 2, or 3, set
the Modbus Master and slave port communication parameters and define the
protocol-specific settings.
3.1.1 Enabled
YES or NO
This flag specifies if the port on the gateway will be utilized. If the parameter is
set to N
O, the port will not be used. If the parameter is set to YES, the port will be
used.
3.1.2 RS Interface
0 = RS-232
1 = RS-485
2 = RS-422
This parameter is used when Ports 1, 2, and 3 are present to configure the
electrical interface for these ports.
RS Interface selections for Port 0 are done with a jumper (electrical shunt) on the
back of the gateway.
3.1.3 Type
MASTER or SLAVE
This parameter defines if the port will emulate a Master or slave device. Choose
a value of M
ASTER to make the port function as a Modbus Master. Choose SLAVE
to make the port function as a Modbus slave.
MCM Protocol Configuration MCM ♦ ProLinx Gateway
Driver Manual Modbus Master/Slave
ProSoft Technology, Inc. Page 19 of 80
October 16, 2009
3.1.4 Float Flag
Yes or No
This flag specifies how the Slave driver will respond to Function Code 3, 6, and
16 commands (read and write Holding Registers) from a remote Master when it
is moving 32-bit floating-point data.
If the remote Master expects to receive or will send one, complete, 32-bit
floating-point value for each count of one (1), then set this parameter to Y
ES,
especially if the Master must read or write from Modbus addresses above
gateway address 3999 (virtual Modbus address 44000 or 440000). When set to
Y
ES, the Slave driver will return values from two, consecutive, 16-bit internal
memory registers (32 total bits) for each count in the read command or receive
32-bits per count from the Master for write commands. Example: Count = 10,
Slave driver will send 20, 16-bit registers for 10 total 32-bit floating-point values.
If, however, the remote Master sends a count of two (2) for each 32-bit floating-
point value it expects to receive or send, or, if you do not plan to use floating-
point data in your application, then set this parameter to N
O, which is the default
setting.
You will also need to set the Float Start and Float Offset parameters to
appropriate values whenever the Float Flag parameter is set to Y
ES.
3.1.5 Float Start
0 TO 65535
Whenever the Float Flag parameter is set to Y
ES, this parameter determines the
lowest Modbus Address received in commands from a remote Master to consider
as requests to read or write floating-point data. All commands with address
values greater than or equal to this value will be considered floating-point data
requests. All commands with address values less than this value will be
considered normal 16-bit register data requests.
This parameter is used only if the Float Flag is set to Y
ES. For example, if a value
of 7000 is entered, all commands received with addresses of 47001 (or 407001)
and above will be considered as requests for floating-point data and 32-bits of
data will be returned for each count of one in the command.
You will also need to set the Float Offset parameter to an appropriate value
whenever the Float Flag parameter is set to Y
ES.
MCM ♦ ProLinx Gateway MCM Protocol Configuration
Modbus Master/Slave Driver Manual
Page 20 of 80 ProSoft Technology, Inc.
October 16, 2009
3.1.6 Float Offset
0 TO 3998
This parameter defines the starting register for floating-point data in the internal
gateway database. This parameter is used only if the Float Flag is set to Y
ES.
For example, if the Float Offset value is set to 3000 and the Float Start parameter
is set to 7000, the data returned as floating-point data for register 47001 (or
407001) will actually come from internal gateway registers 3000 and 3001. If the
requested address was 47002 (407002), the data will be returned from internal
registers 3002 and 3003. If the requested address was 47101 (407101), the data
will be returned from internal registers 3200 and 3201; and so on.
3.1.7 Protocol
RTU
ASCII
This parameter specifies the Modbus protocol version to be used on the port.
Valid Protocols are RTU and ASCII.
3.1.8 Baud Rate
This is the baud rate to be used on the port. Enter the baud rate as a value.
Baud Rate Parameter Value
110 110
150 150
300 300
600 600
1200 12 OR 1200
2400 24 OR 2400
4800 48 OR 4800
9600 96 OR 9600
14,400 14, 114 OR 14400
19,200 19, 192 OR 19200
28,800 28, 288 OR 28800
38,400 38, 384 OR 38400
57,600 57 OR 576
115,200 115 OR 1152
Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered, and can handle communications up to 115,200 baud.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80

ProSoft Technology 5127-MCM-HART Owner's manual

Category
Gateways/controllers
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI