Bryant 582J Series Installation Instructions Manual

Category
Split-system air conditioners
Type
Installation Instructions Manual

This manual is also suitable for

582J
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
SIZES 04 -- 06 with PURON
R
(R--410A) REFRIGERANT
Installation Instructions
NOTE: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
Rated Indoor Airflow (cfm) 3.....................
INSTALLATION 8...............................
Jobsite Survey 8................................
Step 1 -- Plan for Unit Location 8..................
Roof Mount 8...............................
Step 2 -- Plan for Sequence of Unit Installation 8......
Curb--Mount Instal lati on 8.....................
Pad--Mount Instal lati on 9......................
Frame--Mount Installation 9....................
Step 3 -- Inspect Unit 9...........................
Step 4 -- Provide Unit Support 9...................
Roof Curb Mount 9..........................
Slab Mount (Horizontal Units Only) 9...........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 9..............
Step 5 -- Field Fabricate Ductwork 11...............
Step 6 -- Rig and Place Unit 11....................
Positioning on Curb 13.......................
Step 7 -- Convert to Horizontal & Connect Ductwork 13.
Step 8 -- Install Outside Air Hood 13...............
Economizer and Two Po s ition Damper Hood
Pack age Removal and Setup Factory Optio n 13..
Economizer Hood and Two--Position Hood 14.....
Step 9 -- Units with Hinge d Panels Only 14..........
Step 10 -- Install Flue Hood 15....................
Step 11 -- Install Gas Piping 15....................
Factory--Option Thru--Base Connections
(Gas Connections) 16.........................
Step 12 -- Install External Condensate Trap and Line 18..
Step 13 -- Make Electrical Connections 18...........
Field Power Supply 18........................
Units with Factory--Installed
Non--Fused Disconnect 19.....................
Units without Fac tory --Installe d
Non--Fused Disconnect 20.....................
All Units 20................................
Convenie nce Outlets 20.......................
Factory--Option Thru--Base Connections
(Electrical Connections) 21....................
Units without T hru--Ba se Connections 22.........
Field Control Wiring 22.......................
Thermostat 22...............................
Unit without Thru--Base Connection Kit 22.......
Heat Anticipator Settings 22...................
Perfect Humidityt Control Connections 23........
Perfect Humidity -- Space RH Controller 23.......
EconoMi$e r
R
X (Fact ory--Insta lled Option) 25......
RTU Open Control System 26...................
Supply Air Temperature (SAT) Sensor 29.........
Outdoor Air Temperature (OAT) Sensor 29.......
EconoMi$e r2 30.............................
Field Connections 30..........................
Space Temperature (SPT) Sensors 30............
Indoor Air Quality (CO
2
)Sensor 31.............
Outdoor Air Quality Sensor 31.................
Space Humidity Sensor or Humidistat 32.........
Smoke Detector/Fire Shutdown (FSD) 33.........
Connect ing Discrete Inputs 33..................
Communication Wiring -- Protocols 34............
General 34.................................
Local Access 35..............................
RTU Open Troubleshooting 35.................
Outdoor Air Enthalpy Control 36.................
Differential Enthalpy Control 36................
Return Air Enthalpy Sensor 37.................
Smoke Detectors 37...........................
Step 14 -- Adjust Factory--Installe d Options 41........
Step 15 -- Install Accessories 41...................
UNIT START--UP CHECKLIST 43..................
2
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other c onditions which may cause personal
injury or property damage. Consult a qualified installer,
service agenc y, or your distribut or or branch for
information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazi ng operations and
have a fire extinguisher available. Read these i nstructions
thoroughly and follow all warnings or cautions attac hed to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70,
Nationa l Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safet y information. This is the
safety--alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identi fy
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when leak testing at
pressure greater than 0.5 psig (3450 Pa). Pressures
great er than 0.5 psig (3450 Pa) will cause gas valve
damage resulting in hazardous condition. If gas valve
is subjected to pressure greater than 0.5 psig (3450
Pa), it must be replaced before use. When pressure
testing field--supplied gas piping at pressures of 0.5
psig (3450 Pa) or less, a unit connected to such piping
must be isolated by closing the manual gas valve.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Inlet pressure tab set screw must be tightened and
1
/
8
in.
NPT pipe plug must be installed to prevent gas leaks.
!
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Manifold pressure t ap set screw must be tightened and
1
/
8
in. NPT pipe plug must be install ed to prevent gas
leak.
!
WARNING
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
CARBON--MONOXIDE POISONING HAZARD
Failure to foll ow instructi ons c ould result in severe
personal injury or death due to carbon--monoxide
poisoning, if combustion products infiltrate into t he
building.
Check that all openings in the outside wall around the
vent (and air intake) pipe(s) are sealed to prevent
infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s)
are not obstructed in any way during all seasons.
!
WARNING
582J
518
3
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lock(s) and loc kout tag(s). Unit may have more
than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at
higher pre ssures tha n standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses a nd gloves when handli ng
refrigerants. Keep torches and other ignition sources
away from refrigera nts and oils.
!
WARNING
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning equipment.
CAUTION
!
Rated Indoor Airflow (cfm)
The following table lists the rated indoor airflow used for
the AHRI efficiency rating for the units covered in this
docume nt.
Model Number Full Load Airflow (cfm)
582J*04 1050
582J*05 1400
582J*06 1750
582J
4
Model
J - Puron
®
(R-410A) Refrigerant
Unit Type
582 - Gas Heat RTU, Legacy Series
Packaging and Control
A = Standard Packaging, electro-mechanical
controls that require W7212 EconoMi$er
®
IV
B = LTL Packaging
, electro-mechanical
controls that require W7212 EconoMi$er IV
C = Standard Packaging, electro-mechanical
controls that require W7220 EconoMi$er X
F = LTL Packaging, electro-mechanical
controls that require W7220 EconoMi$er X
Cooling Tons
04 - 3 tons
05 - 4 tons
06 - 5 tons
Heat Level Input
Standard / Stainless Steel
072 = 72,000
115 = 115,000
150 = 150,000
Low NOx
060 = 60,000
090 = 90,000
120 = 120,000
Indoor Fan Options
0 = Direct Drive ECM
2 = Medium Static Option
3 = High Static Option
Refrig. System/Gas Heat Options
A = Standard One Stage cooling models/Nat. Gas Heat
B = Standard One Stage cooling models/Low NO
x
Heat
C = Standard One Stage cooling models/SS HX Heat
G = One-Stage cooling models/Alum Heat Exchanger
with Perfect Humidity™
H = One-Stage cooling models/Low NO
x
Heat
with Perfect Humidity
J = One-Stage cooling models/Stainless Steel Exchanger
with Perfect Humidity
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu
B = Precoat Al/Cu - Al/Cu
C = E-coat Al/Cu - Al/Cu
D = E-coat Al/Cu - E-coat Al/Cu
E = Cu/Cu - Al/Cu
F = Cu/Cu - Cu/Cu
M = Al/Cu -Al/Cu — Louvered Hail Guard
N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard
P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard
Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard
R = Cu/Cu - Al/Cu — Louvered Hail Guard
S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Voltage
E = 460-3-60
J = 208/230-1-60
P = 208/230-3-60
T = 575-3-60
Outdoor Air Options
A = None
B = Temperature Economizer, Barometric Relief,
Standard Leak (W7212 or W7220)
E = Temperature Economizer, Barometric Relief,
Standard Leak w/CO
2
(W7212 or W7220)
H =
Enthalpy
Economizer, Barometric Relief,
Standard Leak (W7212 or W7220)
L =
Enthalpy
Economizer, Barometric Relief,
Standard Leak w/CO
2
(W7212 or W7220)
Q = Motorized 2 Position Damper
U = Temperature
Economizer,
Barometric
Relief,
Ultra Low Leak (W7220)
W =
Enthalpy Economizer,
Barometric
Relief, Ultra Low Leak
(W7220)
Example:
Position:
582JE06A072A0B0AA
123456789
10
11 12 13 14 15 16 17
Factory Installed Options
0A = None
NOTE: See the 582J 3 to 5 ton Price Pages
for a complete list of factory installed
options.
Note: On single phase(-J) voltage code) models, the
following are not available as a factory installed option:
- Perfect Humidity
- Coated Coils or Cu Fin Coils
- Louvered Hail Guards
- Economizer or 2 Position Damper
- Powered 115 Volt Convenience Outlet
C14337
Fig. 1 -- 582J 04--06 Model Number Nomenclature (Example)
582J
5
C14270
Fig. 2 -- Unit Dimensional Drawing
582J
6
C14271
Fig. 2 -- Unit Dimensional Drawing (cont.)
582J
7
C
B
A
D
C08337
LOCATION DIMENSION CONDITION
A
48---in (1219 mm)
18---in (457 mm)
18---in (457) mm
12---in (305 mm)
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
B
42---in (1067 mm)
36---in (914 mm)
Special
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
Check sources of flue products within 10---ft of unit fresh air intake hood
C
36---in (914 mm)
18---in (457 mm)
Side condensate drain is used
Minimum clearance
D
48---in (1219 mm)
42---in (1067 mm)
36---in (914 mm)
Special
No flue discharge accessory installed, surface is combustible material
Surface b ehind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
Check for adjacent units or building fres h air inta kes withi n 10---ft (3 m) of this unit’s flue outl e t
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
planning overhead obstruction or for vertical clearances.
Fig. 3 -- Service Clearance Dimensional Drawing
582J
8
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installa-
tion requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 Plan for Unit Location
Select a locat ion for the unit and its support system (curb
or other) that provide s for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit a s speci fied in unit
drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units.
Be sure that uni t is installed such that snow will not block
the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on
Class A, B, or C roof--covering material when roof c urb is
used.
Do not install unit in an indoor locati on. Do not locate air
inlets near exhaust vents or other sources of contaminated
air. For proper unit ope ration, adequate combustion and
ventilation air must be provided in accordance with
Section 5.3 (Air for Combustion and Ventilation) of the
Nationa l Fuel Gas Code, ANSI Z223.1 (American
Nationa l Standards Institute) and NFPA (National Fire
Protection Association) 54 TIA----54 ----84----1. In Canada,
installation must be in accordance with the CAN1 ---- B149
installati on codes for gas burning applia nces.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Locate mechanical draft system flue assembly at least 4 ft
(1.2 m) from any opening through which c ombustion
products could e nter the building, and at least 4 ft (1.2 m)
from any adjacent building (or per local code). Locate the
flue assembly at least 10 ft (3.05 m) from an adjacent
unit’s fresh a ir intake hood if within 3 ft (0.91 m) of same
elevation (or per local code). When unit is located
adjacent to public walkways, flue assembly must be at
least 7 ft (2.1 m) above gra de.
Selec t a unit mounting system that provides adequate
height to allow insta llat ion of condensat e trap per
requirements. Refer to Step 12 Install External
Condensate Trap and Li ne for required trap dim ensions.
Roof Mount
Check building codes for weight distribution
requirements. Unit operating weight is shown in Table 1.
Step 2 Plan for Sequence of Unit Installation
The support method used for this unit will dictate di fferent
sequence s for the steps of unit install ation. For example,
on curb--mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Revie w the following for rec ommended sequences for
installation steps.
Curb --mounted Installation
Install curb
Install field--fabricated ductwork inside curb
Install accessory thru--base service connection package
(affects curb and unit) (refer to accessory installation
instructions for details)
Prepare bottom condensate drain connection to suit
planned condensate l ine routing (refer to Step 12 for
details)
Rig and place unit
Install outdoor air hood
Install flue hood
Install gas piping
Install condensate line trap and pipi ng
Make electrical connections
Install other accessories
Table 1 Operating Weights
582J*
UNITS LB (KG) UNITS LB (KG) UNITS LB (KG)
04 05 06
Base Unit 490 (222) 544 (246) 597 (270)
Economizer
Vertical 50 (23) 50 (23) 50 (23)
Horizontal 80 (36) 80 (36) 80 (36)
Perfect Humidity™ System 50 (23) 50 (23) 50 (23)
Cu Fins 25 (11) 43 (20) 56 (25)
Powered Outlet 35 (16) 35 (16) 35 (16)
Curb
14---in/356 mm 115 (52) 115 (52) 115 (52)
24---in/610 mm 197 (89) 197 (89) 197 (89)
582J
9
Pad--mounted Installation
Prepare pad and unit supports
Check and tight en the bottom condensat e drain
connection plug
Rig and place unit
Convert unit to side duct connection arrangement
Install field--fabricated ductwork at unit duct openings
Install outdoor air hood
Install flue hood
Install gas piping
Install condensate line trap and pipi ng
Make electrical connections
Install other accessories
Frame--mounted Installation
Frame--mounte d applications gene rally follow the
sequence for a curb instal lation. Adapt as required to
suit specific installation plan.
Step 3 Inspect Unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 4 Provide Unit Support
Roof Curb Mount
Accessory roof curb detail s and dimensions are shown in
Fig. 5. Assemble and install accessory roof curb in
accordance with instructions shipped with the curb.
NOTE: The gasket ing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 5. Improperly appli ed
gasket can also result in air le aks and poor unit
performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are shown in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for a dditiona l information as required.
A-B
0.5” (13)
B-C
1.0” (25)
A-C
1.0” (25)
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
C06110
Fig. 4 -- Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru--the--base power and
gas connection package must be installed before the unit
is set on the roof curb. If field--instal led thru--the--roof
curb gas connections are desired, use factory--supplied
1
/
2
--in. pipe coupling and gas plate assembly to mount the
thru--the--roof curb connection to the roof curb. Gas
connec tions and power connections to the unit must be
field installed aft er the unit is installed on the roof curb.
If ele ctric and control wiring is to be routed through the
basepan, attach the accessory thru--the --base service
connections to the basepan in accordance with the
accessory installation instructions.
Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Alternate Unit Support
(InLieuofCurborSlabMount)—
A non--combustible sleeper rail can be used in the unit
curb support area. If sleeper rail s cannot be used, support
the long sides of the unit with a minimum of 3 equally
spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each
side.
582J
10
E
E
7/16"
[11]
4 9/16"
[115.5]
1/4"
[7.0]
5' 7-3/8"
[1711.3]
1' 4-13/16"
[427] INSIDE
1-3/4"
[44.4]
2-3/8"
[61]
1-3/4"
[44.5]
1.00"
[25.4]
"A"
1-3/4"
[44.4]
21.74"
[552.2]
5.42"
[137.7]
11.96"
[303.8]
4.96"
[126.0]
70.87"
[1800.2]
40.69"
[1033.5]
21.84"
[554.7]
16.03"
[407.2]
1.75"
[44.5]
20.41"
[518.3]
3.00"
[76.2]
13.78"
[350.0]
14.00"
[355.6]
3.00"
[76.2]
15.19"
[385.8]
32.19"
[817.6]
3'-1 3/16"
[944.6]
"A"
1-3/4"
[44.5]
CRBTMPWR001A01 3/4" [19] NPT
3/4" [19] NPT
1/2" [12.7] NPTCRRFCURB002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
POWER WIRING
FITTING
CONTROL WIRING
FITTING
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
THRU THE CURB
1/2" [12.7] NPT 1/2" [12.7] NPT
CRBTMPWR003A01 THRU THE BOTTOM
ROOF CURB
ACCESSORY #
A
CRRFCURB001A01
14"
[356]
24"
[610]
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898--MMC04/22/13
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
A
DRAWING RELEASE LEVEL:
PRODUCTION
THIRD ANGLE
PROJECTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCES ON:
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1 DEC 2 DEC 3 DEC ANG
MATERIAL
----
-
-
-
AUTHORIZATION NUMBER TITLE
1041738
CURB ASY, ROOF
ENGINEERING MANUFACTURING
(004-007)
ENGINEERING REQUIREMENTS
-
-
-
-
SIZE DRAWING NUMBER REV
T-005, Y-002
DRAFTER CHECKER
D
48TC400427
B
WEIGHT:
-
MMC 06/17/11 - -
SHEET 5 OF 5
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
- PURCH - N/A MMC
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
TYPICAL (4) SIDES
SUPPLY AIR RETURN AIR
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
UNIT
GASKET
(SUPPLIED WITH CURB)
RIGID INSULATION
(FIELD SUPPLIED)
DUCT
(FIELD SUPPLIED)
NAIL (FIELD SUPPLIED)
CERTIFIED DRAWING
VIEW "B"
CORNER DETAIL
SEE VIEW "B"
RETURN AIR
SUPPLY AIR
SUPPLY AIR
OPENING
RETURN AIR
OPENING
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SEE NOTE #2
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1/3/4"[44.5]
SCALE 0.250
E-E
SECTION
C13310
Fig. 5 -- Roof Curb Details
582J
11
Step 5 Field Fabricate Ductwork
Cabinet ret urn-air static pressure (a negati ve condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb
and building structur e. Do not connect ductwork to unit.
Fabrica te supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof a ll externa l ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
A minimum clearance i s not required around duct work.
PROPER TY DAMAGE HAZARD
Failure to follow this caution may result in damage
to roofing materials.
Membrane roofs can be cut by sharp sheet metal
edges. Be careful when placing any sheet metal parts
on such roof.
CAUTION
!
Step 6 Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are
required. Rollers may be used to move unit across a roof.
Level by using unit frame as a reference. See Table 1 and
Fig. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6.
Refer to rigging instructions on unit.
Rigging materials under unit (cardboard t o prevent base
pan damage) must be removed PRIOR to placing the unit
on the roof curb.
When using the standard side drain connection, ensure the
red plug in the altern ate bottom connection is tight. Do this
befor e s ettin g th e unit in place. The red drain pan p lug can
be tightened with a
1
/
2
--in. square socket drive extension. For
further details see Step 12 -- Install External Condensate
Trap and Line” on page 18.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
CAUTION
!
Before setting the unit onto the curb, recheck gasketing on
curb.
582J
12
C14272
Fig. 6 -- Rigging Label
582J
13
PositioningonCurb—
Position unit on roof curb so that the following clearances
are maintained: 1/4 in. (6.4 mm) clearance between the
roof curb and the base rail inside the front a nd rear, 0.0 in.
clearance between the roof curb and the base rail inside on
the duct end of the unit. This will result in the distance
betwee n the roof curb and the base rail inside on the
condenser end of the unit being approximately
1
/
4
in. (6.4
mm).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue v ent discharge must have a minimum horizontal
cle arance of 4 ft (1220 mm) from electric and gas meters,
gas regulators, and gas relief equipment. Minimum
distance between unit and other electrically live parts is
48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such
that flu e gas w ill no t aff ect building materials. Locate
mechanical draft system flue assembly at least 48 in. (1220
mm) from an adjacent building or combus tible material.
NOTE: Installation of accessory flue discharge deflector
kit will reduce the minimum clearance to combustible
material to 18 in. (460 mm).
After unit is in position, remove rigging skids a nd
shipping materials.
Step 7 Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory--installed economizer or return air smoke
detector option may be field--converted to horizontal ducted
configuration. T o convert to horizontal configuration,
remove screws from side duct opening covers and remove
covers. Using the same screws, install covers on vertical
duct openings with the insulation--side down. Seals around
duct openings must be tight. See Fig. 7.
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
C06108
Fig. 7 -- Horizontal Conversion Panels
Field--supplied fl anges should be attached to horizontal
duct ope nings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when i nsulating horizontal ductwork.
Step 8 Install Outside Air Hood
Economizer and Two Position Damper Hood
Package Removal and Setup -- Factory Option
NOTE: Economizer and two position damper are not
avai lable as factory installed opt ions for single phase (--J
voltage code) models.
1. The hood is shipped in knock--down form and must be
field assembled. The indoor coil access panel is used as
the hood top while the hood sides , divider and filter are
packaged together , attached to a metal support tray us-
ing plastic stretch wrap, and sh ipp ed in the return air
compartment behind the indoor coil access panel. The
hood assembly’ s metal tray is attached to the basepan
and also attached to the damper using two plas tic tie--
wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 8.)
FILTER ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
COMPRESSOR
ACCESS PANEL
C06023
Fig. 8 -- Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie--wraps securing the assembly to the damper. (See
Fig. 9) Be careful to not damage any wiring or cut
tie--wraps securing any wiring.
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
C08639
Fig. 9 -- Eco n o mizer and Two--Position Da mp er
Hood Parts Location
582J
14
4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and ass emble per the
steps outlined in Economizer Hood and Two–Position
Hood, below.
Economize r Hood and Two--Position Hood
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove t he screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 10.
TOP
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
TOP
PANEL
C06025
Fig. 10 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit. See
Fig. 1 1.
B
TOP
PANEL
INDOOR COIL
ACCESS PANEL
19 1/16”
SCREW
HOOD DIVIDER
LEFT
HOOD
SIDE
33 3/8”
(848mm)
(483mm)
C06026
Fig. 11 -- Economizer Hood Construction
3. Remove the shipping ta pe holding the economizer
barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See
Fig. 11 and 12. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath t he
hood top. Insert the aluminum filter into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 12.
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTER
CLIP
OUTSIDE
AIR
C08634
Fig. 12 -- Economizer Filter Installation
Step 9 Units with Hinged Panels Only
Relocate latch shipped inside the compressor
compa rtment behind the hinged compressor door to
location shown in Fig. 13 after unit installation.
If the unit does not have hinged panels, skip this step and
continue at step 10.
C12101
Fig. 13 -- Compressor Door Latch Loc ation
582J
15
Step 10 Install Flue Hood
Flue hood is shipped screwed to the basepan beside the
burner compartment access panel. Remove from shipping
loca tion and using screws provide d, install flue hood and
screen in location shown in Fig. 14.
BLOWER
ACCESS
PANEL
C07081
Fig. 14 -- Flue Hood Details
Step 11 Install Gas Piping
Installation of the gas piping must be accordance with
loca l building codes and with applicable national c odes.
In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel
Gas Code (NFGC). In Canada, installation must be
accordance with the CAN/CSA B149.1 and CAN/CSA
B149.2 installati on codes for gas burning applia nces.
This unit is factory equipped for use with Natural Gas fuel
at elevations up to 2000 ft (610 m) above sea level. Unit
may be field converted for operation at e levations a bove
2000 ft (610 m) and/or for use with li quefied petroleum
fuel. See accessory kit installation instructions regarding
these accessories.
NOTE: F urnace gas input rate on rating plate is for
installation up to 2000 ft (610 m) above s ea level. In U.S.A.
the input rating for altitudes above 2000 ft (610 m) must be
derated by 4% for each 1000 ft (305 m) above sea level. In
Canada the input rating must be derated by 10% for altitudes
of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas
connection must not be less than 4 in. wg (996 Pa) or greater
than 13 in. wg (3240 Pa) while the unit is operating. On
582J*05--06 (high--heat) units, the gas pressure at unit gas
connection must not be less than 5 in. wg (1245 Pa) or
greater than 13 in. wg (3240 Pa) while the unit is operating.
For liquified petroleum applications, the gas pressure must
not be less than 1 1 in. wg (2740 Pa) or greater than 13.6 in.
wg (3390 Pa) at the unit connection.
Table 2 Natural Gas Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE (XX) MIN MAX
Low & Med Heat Units
582J*XX*065 to 115 04, 05, 06
4.0 in. wg
(996 Pa)
13.0 in. wg
(3240 Pa)
High Heat Units
582J*05*130/150 05
4.0 in. wg
(1245 Pa)
13.0 in. wg
(3240 Pa)
582J*06*130/150 06
Table 3 Liquid Propane Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE (XX) MIN MAX
Low & Med Heat Units
582J*XX*065 to 115 04, 05, 06
11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
High Heat Units
582J*05*130/150 05
11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
582J*06*130/150 06
The gas supply pipe enters the unit at the burner access
panel on the front side of the unit, t hrough the long slot at
the bottom of the access panel. The gas connection to the
unit is made to the
1
/
2
--in. FPT gas inlet port on the unit
gas valve
Manifold pre ssure is fa ctory--adjusted for NG fuel use.
Adjust as required to obtain best flame characteristics.
Table 4 Natural Gas Manifold Pressure Ranges
UNIT MODEL UNIT SIZE (XX) HIGH FIRE LOW FIRE
582J*XX*065 to 115 04, 05, 06
3.5 in. wg
(872 Pa)
See NOTE
below
582J*XX*130/150
(H i g h Heat units only)
05, 06
3.5 in. wg
(872 Pa)
See NOTE
below
NOTE -- LOW FIRE, 1.7 in. Wg (423 Pa), applies to the following
three phase voltage units only: 582J*04*115 and
582J*05/06*150
Manifold pressure for LP fuel use must be adjusted to
specified range. Follow instructions in the accessory kit to
make initial readjustment.
Table 5 Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE (XX) HIGH FIRE LOW FIRE
582J*XX*065 to 115 04, 05, 06
10.0 in. wg
(2490 Pa)
See NOTE
below
582J*XX*130/150
(H i g h Heat units only)
05, 06
10.0 in. wg
(2490 Pa)
See NOTE
below
NOTE -- LOW FIRE, 5.0 in. Wg (1245 Pa), applies to the following
three phase voltage units only: 582J*04*115 and
582J*05/06*150
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage
to equipment.
When connecting the gas l ine to the unit gas valve,
the installer MUST use a backup wrench to prevent
dama ge to the valve.
CAUTION
!
Install a gas supply line that runs to the unit he ating
section. Refe r to the NFPA 54/NFGC or equival ent code
for gas pipe sizing data. Do not use a pipe size smaller
than
1
/
2
--in. Size the gas supply line to allow for a
maximum pressure drop of 0.5--in wg (124 Pa) between
gas regulator source and unit gas valve connection when
unit is operating at high--fire flow rate.
The gas supply line can approach the unit in three ways:
horizontally from out side the unit (across the roof),
thru--curb/under unit basepan (accessory ki t required) or
582J
16
through unit basepan (factory--option or accessory kit
required). Consult accessory kit installation instructions
for details on these installation methods. Observe
cle arance to gas line components per Fig. 15.
LEGEND
*
Field supplied.
NOTE: Follow all local codes.
NFGC – National Fuel Gas Code
STEEL PIPE
NOMINAL DIAMETER
(in.)
SPACINGOFSUPPORTS
X DIMENSION
(ft)
1
/
2
3
/
4
or 1
1
1
/
4
or larger
6
8
10
X
BASE UNIT
BASE RAIL
ROOF
CURB
9” MINIMUM CLEARANCE
FOR PANEL REMOVAL
MANUAL GAS
SHUTOFF VALVE
*
GAS
REGULATOR
*
48” MINIMUM
DRIP LEG
PER NFGC
*
FIELD-FABRICATED
SUPPORT
*
FROM
GAS
METER
C11091
Fig. 15 -- Gas Piping Guide
(with Accessory Thru--the--Curb Service Connections)
Factory--Option Thru--Base Connections
(Gas Connections)—
This service connection kit consists of a
1
/
2
-- i n N P T g a s
adapter fitting (brass), two
1
/
2
--in electrical bulkhead
connector and a
3
/
4
--in electrical bulkhead connector, all
factory--installed in the embossed (raised) section of the
unit basepan in the condenser section.
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
BRASS FITTING FOR 3 TO 6 TON UNITS.
C13410
Fig. 16 -- Fittings
The thru--base gas connector has male and female threads.
The male threads protrude above the basepan of the unit;
the female threads protrude below the basepan.
Check tightness of connector lock nut s before conne cting
gas piping.
Install a
1
/
2
--in NPT street elbow on the thru--base gas
fitting. Attach a
1
/
2
--in pipe nipple with minimum length
of 16--in (406 mm) (field--supplied) to the stree t elbow
and extend it through the access panel at the gas support
bracket. See Fig. 17.
EMBOSSMENT
BRASS FITTING
FOR 3-6 TON UNITS
SUPPORT
BRACKET
C13411
Fig. 17 -- Gas Line Piping for 3 to 5 Ton Units Only
Other hardware required to complete the installation of the
gas supply line will include a manual shutof f valve, a
sediment trap (drip leg) and a ground--joint union. A
pressure regulator valve may also be required (to convert gas
pressure from pounds to inches of pressure). The manual
shutoff valve must be located within 6--ft (1.83 m) of the
unit. The union, located in the final leg entering the unit,
must be located at least 9--in (230 mm) away from the
access panel to per mit the p anel to be removed for service.
If a regulator valve is installed, it must be located a
minimum of 4--ft (1220 mm) away from the unit’ s flue
outlet. Some municipal codes require that the manual shutoff
valve be located u ps tr eam of the s ed iment trap. See Figu res
18 and 19 for typical piping arrangements for gas piping that
has been routed through the sidewall of the curb. See Fig. 20
for typical piping arrangement when thru--base is used.
Ensu r e that all piping does not block access to the unit’s
main contro l box or limit the required wor kin g space in front
of the control box.
9” (229mm) min
Union
Shut Off
Valve
Drip
Leg
Thru-Curb Adapter
Unit Base Rail
C07469
Fig. 18 -- Gas Piping
582J
17
Drip
Leg
Shut Off
Valve
Union
Thru-Curb Adapter
Burner
Access
Panel
9” (229mm) min
Unit Base Rail
C07470
Fig. 19 -- Gas Piping
C08018
Fig. 20 -- Gas Piping Thru--Base Connections
When installing the gas supply line, observe local codes
pertainin g to gas pipe installations . Refer to the NFPA
54/ANS I Z223.1 NFGC latest edition (in Canada, CAN /CSA
B149.1). In the absence of local building codes, adhere to
the follow in g pertinent recommendation s :
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4--in. in every 15 ft (7 mm in every 5 m) to prevent
traps. Grade all horizontal runs downward to risers.
Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical
and thermal dam age. Support all piping with appro-
priate straps, hangers, etc. Use a minimum of one
hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/
2
--in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only
to male threads of joint when making pipe c onnec-
tions. Use only pipe dope that is resistant to action of
liquefied petroleum gases as specified by local and/or
national codes. If using PTFE (Teflon) tape, ensure
the material is Double De nsity type and is labele d for
use on gas lines. Apply tape per manufacturers in-
structions.
4. Pressure--test all gas piping in accordance with local
and national plumbing and gas codes before connect-
ing piping to unit.
NOTE: Pressure test the gas supply system after the gas
supply piping is connected to the gas valve. T he supply
piping must be disconnected from the gas valve during the
testing of the piping system s when test pressure is in
exce ss of 0.5 psig (3450 Pa). Pressure test the gas supply
piping system at pressures equal to or less than 0.5 psig
(3450 Pa). The unit heating sec tion must be isolated from
the gas piping system by closing the external main manual
shutoff va lve and slightly opening the ground--joint union.
Check for gas leaks at the field--installed and
fact ory--installe d gas lines after all piping connections
have been completed. Use soap--and--water solution (or
method specified by local codes and/or regulations).
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, deat h and/or property damage.
S Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
S Never purge a gas line i nto a c ombustion chamber.
S Never t est for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connec tions.
S Use proper length of pipe to avoid stress on gas
control manifold.
!
WARNING
NOTE: If orifice hole appears damaged or it is suspected
to have been redrilled, check orifice hole with a numbered
drill bit of correct size. Never redrill an orifice. A
burr--free and squarely aligned orifice hole is essential for
proper flame characteristics.
BURNER
ORIFICE
A93059
Fig. 21 -- Orifice Hole
582J
18
Step 12 Install External Condensate Trap
and Line
The unit has one
3
/
4
-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 22. Unit a irflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
To use the alternate bottom drain connection, remove the
red drai n plug from the bottom connection (use a
1
/
2
-- i n .
square socket drive extension) and install it in the side
drain connection.
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 23.
DRAIN
(FACTORY-INSTALLED)
PLUG
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
ALTERNATE
BOTTOM DRAIN
C08021
Fig. 22 -- Condensate Drain Pan (Side V iew)
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
OPEN
VENT
TO ROOF
DRAIN
DRAIN PLUG
ROOF
CURB
SEE NOTE
2˝ (51) MIN
C08022
Fig. 23 -- Condensate Drain Piping Details
All units must have an ex ternal trap for condensate
drainage. Install a trap at least 4-in. (102 mm) dee p and
protec t against freeze-up. If drain line is instal led
downstream from the external t rap, pitch the l ine away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
(
3
/
4
-in.).
Step 13 Make Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabi net must have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an ele ctric al fault should occur. This
ground may consist of electrical wire connecte d to
unit ground lug in control compartment, or conduit
approved for e lect rical ground when installed in
accordance with NEC (National Electrical Code);
ANSI/NFPA 70, latest edition (in Canada, Canadian
Electrical Code CSA [Canadian Standards
Association] C22.1), and local electrical codes.
!
WARNING
NOTE: Field--supplied wiring shall conform with the
limitations of minimum 63_F(33_C) rise.
Field Power Supply
If equipped with optional P owered Convenience Outlet: The
power source leads to the convenience outlets transformer
primary are not factory connected. Installer must connect
these leads according to required operatio n of the
convenience outlet. If an always--energized convenience
outlet operation is desired, connect the source leads to the
line side of the unit--mounted disconnect. (Check with local
codes to ensure this method is acceptable in your area.) If a
de--energize via unit disconnect switch operation of the
convenience outlet is desired, connect the source leads to the
load side of the unit disconnect. On a unit without a
unit--mounted disconnect, connect the source leads to
compressor contactor C and indoor fan contactor IFC
pressure lugs with unit field power leads.
Refer to Fig. 30 for power transformer connections and the
discussion on connecting the convenience outlet on page 15.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
contactor IFC (see wiring diagram label for control box
component arrangement) or at factory--installed option
non--fused disconnect switch. Max wire size is #2 AWG
(copper only). See Fig. 24 and unit label diagram for field
power wiring connections.
NOTE: TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connecti on points on
conta ctor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connec tion pressure lugs only.
582J
19
Disconnect
per
NEC
Disconnect
per
NEC
208/230-1-60
11 13 11 13 13
L1
L2 L3
TB
C
C IFC
or
(1-ph
IFM)
208/230-3-60
460-3-60
575-3-60
Units Without Non-Fused Disconnect Option
Units With Non-Fused Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
C14241
Fig. 24 -- Power Wiring Connections
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or perfor mance satisfactio n.
Do not connect aluminum wire between disconnect
switch and 582J unit. Use only copper wire.
(See Fig. 25.)
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 25 -- Disconnect Switch and Unit
Units with Factory--Installed Non--Fused Disconnect
The factory--installed option non--fused disconnect (NFD)
switch is located in a weatherproof enclosure located
under the main control box. The manual switch handle and
shaft are shipped in the disconnect enclosure. Assemble the
shaft and handle to the switch at this point. Discard the
factory test leads (see Fig. 24).
Connect fiel d power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
C12278
Fig. 26 -- Location of Non--Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front pane (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure -- (2) on
the face of the cover and (1) on the left side cover.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from t he factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
6. Measure from the tip of the shaft t o the top surface of
the black pointer; the measurement should be 3.75 --
3.88 in. (95 -- 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cove r with (2) screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re--install
(3) hex screws on the NFD enclosure.
12. Re--install the unit front panel.
C12279
Fig. 27 -- Handle and Shaft Assembly for NFD
582J
20
Units Without Factory--Installed
Non--Fused Disconnect
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provi ded on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the di sc onnect on the unit cabinet.
All Units
All field wirin g must comply with NEC and all lo cal codes.
Size wire based on MCA (Minimum Circuit Amps) on th e
unit informative plate. See Fig. 24 and the unit label
diagram for power wiring connections to the unit power
terminal blocks and equipment ground. Maximum wire size
is #2 ga AWG (copper only) per pole on contactors.
Provide a ground--fault and short--circuit over--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protecti on) device size.
All field wiring must comply with the NEC and local
requirements.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
with the
1
/
4
-in. female spade connector from t he 230--v
connec tion and moving it to the 200-v
1
/
4
-in. male
terminal on t he primary side of the transformer. Refer to
unit label diagram for additional informat ion. Field power
wires will be connected line--side pressure lugs on the
power t erminal block or at factory--installed option
non--fused disconnect.
NOTE: Check all factory and field electrical connections
for tightness.
Convenience Outlets
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience out let circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock--out and tag--out this switch, if necessary.
!
WARNING
Two types of convenience outlets are offered on 582J
models: Non--powered and unit--powered. Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged waterproof
access cover, located on the end panel of the unit. S ee Fig.
28.
NOTE: Unit power ed convenience outlets are not
avai lable as factory installe d options for single phase (--J
voltage code) models.
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Pwd-CO
Transformer
Control Box
Access Panel
C08128
Fig. 28 -- Convenience Outlet Locati on
Installing Weatherproof Cover: A weathe rproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This c over
cannot be factory-mount ed due its depth; it must be
installed at unit installation. For shipment, the
conveni ence outlet is covered with a blank cover plate.
The weatherproof cover kit i s shipped in the unit’s control
box. The kit include s the hi nged cover, a backing pla te
and gasket.
DISCONNECT ALL POWER TO UNIT AND
CONVENIENCE OUTLET. LOCK--O U T A N D TAG--OU T
ALL POWER.
Remove the blank cover plate a t the c onvenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
approximately
1
/
2
-in (13 mm) under screw heads a re
exposed. Press the gasket over the screw heads. Slip the
backi ng plate over the screw heads at t he keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 29. Remove two slot fillers in the bottom of
the cover t o permit service tool cords to exit the cover.
Check for full closing and latching.
RECEPTACLE
NOT INCLUDED
COVER – WHILE-IN-USE
WEATHERPROOF
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 29 -- Weatherproof Cover Installation
582J
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Bryant 582J Series Installation Instructions Manual

Category
Split-system air conditioners
Type
Installation Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI