Johnson Controls Premier Series Installation & Operation Manual

Category
Split-system air conditioners
Type
Installation & Operation Manual
5795595-JIM-A-1019
Advanced Graphic
Touchscreen Display on
25–50 Ton Johnson Controls
®
Premier
Rooftop Units
Chapter 1: Using This Guide ............................................... 3
Introduction .................................................................... 3
Key Concepts ................................................................. 3
Chapter Organization .............................................. 3
Chapter 2: Introduction to the Touchscreen Display ............ 3
Introduction .................................................................... 3
Key Concepts ................................................................. 3
LED Display ............................................................ 3
Features .................................................................. 4
Theory of Operation ................................................ 4
Display Congurations ............................................ 4
Chapter 3: Installing the Display .......................................... 4
Introduction .................................................................... 4
Key Concepts ................................................................. 5
Mounting Options ................................................... 5
Display Unit Dimensions ........................................ 5
Internal Components of the Display ........................ 5
Internal Wiring for Adapters in the Display .............. 6
Procedure Overview....................................................... 7
Install the Display .................................................... 7
Detailed Procedures....................................................... 8
Mount Display on a Wall or in a Remote Panel ...... 8
Cabling a Display with a Single Controller ............ 10
Cabling a Display with Multiple Controllers ............ 11
Chapter 4: Operating the Display ...................................... 12
Introduction .................................................................. 12
Key Concepts ............................................................... 12
Display .................................................................. 12
Operate the Touchscreen ...................................... 13
Using the Display .................................................. 13
Procedure Overview..................................................... 14
Menu Navigation ................................................... 15
Detailed Procedures..................................................... 22
System Settings .................................................... 22
Login Page ............................................................ 23
Establish Communication with Controller ............. 24
Home Page ........................................................... 25
Viewing MAP Application ...................................... 26
View Setpoint Data and Adjust/Override Setpoints 30
View Alarm Summary ............................................ 31
View Graph Data ................................................... 32
USB Functions and Data Import/Export ................ 32
Display Faults and Diagnosis................................ 34
Updating the Display Firmware ............................. 34
Appendix A: Specications and Technical Data ................. 35
Introduction .................................................................. 35
Key Concepts ............................................................... 35
Specications ........................................................ 37
Wiring Instructions........................................................ 39
Table of Contents
LD28392
INSTALLATION & OPERATION
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
2
List of Tables
Table 1: Display Unit Dimensions ................................................................................................................................................. 5
Table 2: Display Screen Components ......................................................................................................................................... 13
Table 3: Display Touch Commands ............................................................................................................................................ 14
Table 4: Operating the Display .................................................................................................................................................... 14
Table 5: Menu Navigation ........................................................................................................................................................... 15
Table 6: User Level Restrictions ................................................................................................................................................. 23
Table 7: MAP Gateway LED Designations and Descriptions ...................................................................................................... 29
Table 8: Alarm Category Definition ............................................................................................................................................. 31
Table 9: Display Faults and Diagnosis ........................................................................................................................................ 34
Table 10: Reference Documents ................................................................................................................................................ 35
Table 11: Ordering Codes ........................................................................................................................................................... 35
Table 12: Display Specifications and Technical Data .................................................................................................................. 37
Table 13: MAP Gateway Specifications and Technical Data....................................................................................................... 38
List of Figures
Figure 1: Touchscreen Display Mounted on Control Panel .......................................................................................................... 3
Figure 2: BOX710-01 Display Enclosure for Wall Mount .............................................................................................................. 5
Figure 3: Display Unit Dimensions ............................................................................................................................................... 5
Figure 4: Communication, Storage, and Power Ports on Display ................................................................................................ 5
Figure 5: Power Adapter Connection to Display ........................................................................................................................... 6
Figure 6: SA/FC Bus Communication with SERIAL Port Adapter on the Display ......................................................................... 6
Figure 7: MAP and Display Connection: RJ-12 and RJ-45 .......................................................................................................... 6
Figure 8: Wall-mounting the Display ............................................................................................................................................. 8
Figure 9: Remote Panel/Gypsum Plaster Wall-mounting the Display .......................................................................................... 9
Figure 10: Cutout and Display Clearances ................................................................................................................................. 10
Figure 11: Single Controller Cable Connection .......................................................................................................................... 10
Figure 12: Multiple Controllers Cable Connection ...................................................................................................................... 11
Figure 13: Display Home Page................................................................................................................................................... 12
Figure 14: Display Navigation Structure ..................................................................................................................................... 15
Figure 15: TAP-TAP Menu ..........................................................................................................................................................22
Figure 16: System Settings > Exit .............................................................................................................................................. 23
Figure 17: Start HMI Option........................................................................................................................................................ 23
Figure 18: Login Page ................................................................................................................................................................ 23
Figure 19: Signing Out................................................................................................................................................................ 23
Figure 20: Device Discovery Search .......................................................................................................................................... 24
Figure 21: Available Controllers .................................................................................................................................................24
Figure 22: Home Page for Connected Controller: Enclosed Cabinet ......................................................................................... 25
Figure 23: Home Page for Connected Controller: Cutaway Cabinet .......................................................................................... 25
Figure 24: Wi-Fi for MAP ............................................................................................................................................................ 26
Figure 25: Ethernet Tab .............................................................................................................................................................. 26
Figure 26: Ethernet Parameters ................................................................................................................................................. 27
Figure 27: Network Page ............................................................................................................................................................ 27
Figure 28: DHCP Button .............................................................................................................................................................28
Figure 29: Log In ........................................................................................................................................................................ 28
Figure 30: Enter IP Address .......................................................................................................................................................29
Figure 31: Closing the MAP Browser .........................................................................................................................................29
Figure 32: Adjusting/Overriding Setpoint Data ........................................................................................................................... 30
Figure 33: Alarm Summary ......................................................................................................................................................... 31
Figure 34: Graph Example ......................................................................................................................................................... 32
Figure 35: Opening a PDF.......................................................................................................................................................... 32
Figure 36: USB Functions .......................................................................................................................................................... 33
Figure 37: Settings Menu ........................................................................................................................................................... 34
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
33
Chapter 1Chapter 2
Chapter 1: Using This Guide
Introduction
The Advanced Graphic Touchscreen Display Installa-
tion and Operation Manual provides information about
how to use the advanced graphic display interface.
This chapter outlines the manual's organization and
content.
Key Concepts
Chapter Organization
Each chapter of this manual is divided into four sec-
tions:
1. Introduction: Briey outlines the main sections
2. Key Concepts: Describes background informa-
tion necessary to perform or understand specic
tasks
3. Procedure Overview: Describes general steps
for performing the tasks described in the De-
tailed Procedures section
4. Detailed Procedures: Describes in detail the
steps needed to complete specic tasks de-
scribed in that chapter. This section is benecial
to users who are new to the touchscreen display
Chapter 2: Introduction to the
Touchscreen Display
Introduction
The touchscreen display is a user interface (UI) man-
aged with the Applied Smart Equipment series of con-
trollers. The display can act as a simple adjust and in-
dication unit or can be used for more complex tasks,
such as integrating with multiple controllers and com-
missioning units that are often associated with a work-
station.
The touchscreen display is designed for facility engi-
neers or service technicians who need a straightfor-
ward way to monitor and adjust setpoints in a controller
without being limited in capability.
NOTE: Throughout the remainder of this manual, the
touchscreen display is referred to as “display.”
Key Concepts
LED Display
The display presents a new, graphical interface with
fully mobile access. It enables enhanced data visual-
ization that allows building operators to work smarter
and make the most of their HVAC investments. The
advanced interface can be configured for applications
with more than one controller, in which it can be perma-
nently mounted on the building wall, in a wall-mounted
enclosure, or in a remote control panel as part of the
existing workstation setup.
LD28394
Figure 1: Touchscreen Display Mounted on Control Panel
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
NOTE: Throughout the remainder of this guide, the Ap-
plied Smart Equipment main control board is
referred to as "controller" and the MAP Gate-
way tool is referred to as "MAP." The Applied
Smart Equipment controller is only provided on
the Premier line of rooftop units.
44
Features
The display is intuitive, simple to learn, and syncs eas-
ily with all Smart Equipment controllers. Building own-
ers and contractors can effortlessly monitor their equip-
ment or edit parameters from anywhere.
The UI is a 10-inch WXGA type color, wide screen,
backlit display with a thin lm transistor (TFT) and
multi-touch, capacitive touchscreen at 1280 x 800
resolution
Graphical representation of the Premier line of
rooftop units and its major components with real-
time data
Displays separate pages to navigate for each ma-
jor component
Allows user to congure the display unit to com-
municate with multiple controllers connected to a
common BACnet
®
MS/TP bus using the appropri-
ate conguration to match the selected controller.
Displays active alarm events
Built-in browser for web connectivity to MAP
Gateway
Provides the ability to read documents (PDFs
only)
Displays parameter data from the controller in a
graphical format
Data upload/retrieval options
Displays unit nomenclature for quick identication
of features and options on the unit
Theory of Operation
The display is available with the Applied Smart Equip-
ment type controller. It connects directly to the built-in
RS-485 port (SA or FC bus) on the main control board
(Figure 11 on page 10), allowing straightforward ac-
cess to monitor and change all of the equipment pa-
rameters.
Offering many-to-one, multi-client connectivity, the
MAP Gateway tool (Version 5.0 and above) is synced
with the display that gives user access to any Smart
Equipment device that is on a common BACnet (MS/
TP) field bus.
The display is operated through the built-in menu sys-
tem and MAP Gateway tool to provide access to the
real-time data and parameters stored in the Applied
Smart Equipment controller.
Display Configurations
Each display unit is pre-loaded with firmware. Different
display unit configurations customize the display as re-
quired for different unit applications.
When the user integrates the display with a controller,
the display unit matches one of its stored configuration
codes with the code defined in the controller configura-
tion. If it finds a match, then the display uses the cor-
responding display configuration. If it does not find a
match, it uses the default configuration.
The display unit matches the available configurations
only for the Applied Smart Equipment controllers.
Related Information
Refer to Chapter 4: Operating the Display, for informa-
tion on upgrading the display firmware in the field with
the latest released display configuration files.
Chapter 3: Installing the Display
Introduction
The display can be permanently mounted on a panel
or on the wall. For panel or wall mounting applications,
the display unit is permanently connected to at least
one controller.
This chapter describes how to:
Mount the display on a wall or panel located in a
remote location from the unit
Cable the display for a single controller application
Cable the display for a multiple controller application
When the display is selected while ordering the unit
through the Selection Navigator tool, the factory
mounts the display on the unit control panel in the con-
trols section.
NOTE: The standard UI is installed in the unit control
panel as a default if the touchscreen display
was not selected when ordering the unit. If the
standard interface must be replaced with the
touchscreen display in the field, contact the
factory for further information.
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
Mount the display remote in an existing control panel
or on a wall, using a BOX710-01 display enclosure
from Johnson Controls, shown in Figure 2.
55
Chapter 3
Key Concepts
Mounting Options
Wall Box
Bracket
Display
LD28395
Figure 2: BOX710-01 Display Enclosure for Wall
Mount
H
L
0.31 inches
(8 mm)
C
B
A
LD28396
Figure 3: Display Unit Dimensions
Table 1: Display Unit Dimensions
Item A B C H L
Display (inches/mm) 10.66 / 271 10.66 / 271 2.20 / 56 7.75 / 197 11.10 / 282
NOTE: A and B represent dimensions for cutout.
1
2
3
4
5
6
7
8
9
Available ports:
1. 2 USB Ports V2.0
2. Ethernet port 2 (10/100 Mb) - (ETH2/
RJ-45)
3. Ethernet port 1 (10/100 Mb) - (ETH1/
RJ-45)
4. Serial port - (SERIAL)
5. Ethernet port 0 (10/100/1000 Mb) -
(ETH0/ RJ-45)
6. Power supply
7. 2 Expansion slots for plug-in modules
8. SD Card Slot
9. Aeration hole, located on either side
of the display
NOTE: For technical specications of available ports, refer Table 12 on page 37.
LD28397
Figure 4: Communication, Storage, and Power Ports on Display
Display Unit Dimensions
Figure 3 shows the overall dimensions of the display.
For panel cutout dimensions or wall enclosure drill hole
spacing, see Detailed Procedures on page 8 in this
chapter.
Internal Components of the Display
Figure 4 shows the rear view of the display with all
ports for communication, storage, and power.
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
66
Internal Wiring for Adapters in the Display
Figure 5Figure 7 show the internal wiring of the adapt-
ers required for display serial communications cable
and power connection. The power adapter and display
communication (SERIAL) adapter is provided with the
display unit.
3 Prong Plug
24 VDC Power Supply
Display Power Adapter
LD28398
Figure 5: Power Adapter Connection to Display
SA Bus
+
-
COM
SA PWR
RS-485 limit of 1,000 feet
for controller to SERIAL
port on the display
FC Bus
+
-
COM
SHLD
RS-485 limit of 5,000 feet
for controller to SERIAL
port on the display
1357
2468
1357
2468
SERIAL Port Display
SERIAL Port Display
LD28399
Figure 6: SA/FC Bus Communication with SERIAL Port Adapter on the Display
RJ-12 SA/FC Bus Port on the Controller
RJ-45 Port on the MAP
RJ-12 Port on the MAP
RJ-45 (ETH0/ETH1/ETH2)
Port on the display
RJ-12 (Telephone style port)
limit of 100 feet for SA/FC bus
port on the controller to the MAP
RJ-45 (Ethernet style port) limit
of 328 feet for the MAP to the
display (can be extended using
an Ethernet switch)
LD28400
NOTE:
1. Field to provide cable length as required.
2. When using an Ethernet switch, the MAP must be powered using an external power source. Refer to Figure 12 on page 11 for an ex-
ample of the Ethernet switch.
Figure 7: MAP and Display Connection: RJ-12 and RJ-45
The SA or FC bus adapter is required at the controller
for communications with the display. The SA adapter is
required when only one controller is integrated with the
display. The FC bus adapter is used for multiple con-
trollers connected on a common BACnet MS/TP bus.
SA/FC bus adapters are field provided and installed as
applicable.
For cable type requirements, refer to Table 12 on page
37.
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
77
Chapter 3
Procedure Overview
Install the Display
Mount Display on a Wall or in a Remote Panel
1. When mounting the display on a wall, attach the
wall-mounting box to the wall, and place the dis-
play onto the box.
When mounting the display in a remote panel,
insert the display into the existing cutout in the
control panel.
2. Connect the serial communications cable, MAP
cable, and power supply to the display.
3. Connect the serial communications and MAP ca-
bles from the display to the controller, and apply
power to the display.
Cable the Display to the Unit
To establish a direct connection to the controller:
1. Connect the serial communications cable into
the communication port labeled SERIAL on the
display unit.
Plug the other end of the serial communications
cable into the SA bus adapter on the controller.
2. Connect the Ethernet cable from the MAP to the
port labeled ETH2 on the display using a RJ-45
style cable.
Use a RJ-12 style cable to connect the MAP with
the SA bus modular jack provided on the controller.
Use a 12–15 VDC power supply for the MAP.
NOTE: Refer to Viewing MAP Application on
page 26 for instructions to set up the MAP.
3. Connect a 24 VDC supply voltage to power up
the display.
To extend the serial communications cable in order to
view field bus devices:
1. The display can integrate multiple eld bus de-
vices on Metasys
®
systems, Facility Explorer
®
systems, Smart Equipment rooftop units (RTUs)
with unit control boards (UCBs), Johnson Con-
trols
®
branded eld controllers, including FEC,
FAC, VMA, PCA, PCG, PCV Series devices,
TEC3000 Series thermostats, and other Applied
Smart Equipment controllers using the MAP.
2. Connect the serial communications cable into
the communication port labeled SERIAL on the
display unit.
Plug the other end of the serial communications
cable into the FC bus adapter of the controller.
Multiple field devices can be connected on the
FC bus of the controller that are on a common
MS/TP bus.
NOTE: In the Detailed Procedures section of this
chapter, review Cabling a Display with
Multiple Controllers on page 11.
3. Connect the Ethernet cable from the MAP to any
of the Ethernet ports (ETH0/ETH1/ETH2). This
guide shows the RJ-45 style cable connected to
the ETH2 port on the display.
Use a RJ-12 style cable to connect the MAP with
the FC bus modular jack provided on the controller.
Use a 12–15 VDC power supply for the MAP. Or-
der Option 1 for touchscreen display installation
when the unit is without a factory installed MAP
and 110V transformer. Order Option 2 when in-
stalling the touchscreen with a factory installed
MAP and a 110V transformer is not provided
on the unit. Order Option 3 when installing the
touchscreen display with a factory installed MAP
and 110V transformer provided on the unit. A
110V transformer is provided on the unit when
at least one of the following options is installed:
internal lights, UV lights, gas heat, or a conve-
nience outlet.
NOTE: Refer to Viewing MAP Application on
page 26 for instructions to set up the MAP.
4. Connect a 24 VDC supply voltage to power up
the display.
NOTE: Multiple field bus device integration with the
display is only available on a common FC bus.
For cable type requirements and distance limi-
tations, refer to Table 12 on page 37.
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
88
X
Y
Z
Connect to ground
2
1
4
3
5
6
Wall Box
Cutout X Y Z
BOX710-01 11.57 (294) 8.26 (210) 3.38 (86)
NOTE: Dimension in inches (mm).
LD29401
Figure 8: Wall-mounting the Display
Detailed Procedures
Mount Display on a Wall or in a Remote
Panel
NOTE: A display enclosure is required to mount the
display on a wall or in a remote panel. Refer to
Table 11 on page 35.
To mount the display on a wall:
1. Find an easily accessible location where wire
connections can be made and display param-
eters can be viewed from a oor level. Mount the
display box on a dry surface. Avoid prolonged
exposure to direct sunlight to prevent the risk of
overheating the device.
2. Drill appropriate holes for the wall-mounting box
using the dimensions shown in Figure 8.
3. Attach the wall-mounting box to the wall using
the screws provided in the wall mounting kit.
4. Place the display in the box.
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
99
Chapter 3
21
4
3
5
Bracket
supplied with
BOX710-01
X
Y
Display
Bracket
Wall Box
Cutout X Y
BOX710-01 10.90 (277) 7.55 (192)
NOTE: Dimension in inches (mm).
LD28402
Figure 9: Remote Panel/Gypsum Plaster Wall-mounting the Display
To mount the display in a remote control panel or gyp-
sum plaster wall:
1. Avoid locations such as the heat exchanger,
variable frequency drive (VFD), or any housing
that may contain electric motors or other strong
sources of electrical interference. Mount the dis-
play enclosure on a vibration free surface.
2. Make an appropriate cutout in the panel using
the dimensions shown in Figure 3 on page 5
(note the maximum display thickness shown in
the Table 1 on page 5).
After the display is securely mounted in its location:
1. Connect the serial communications cable, Ether-
net cable for MAP, and power supply to the dis-
play. Use one of the removable slots provided on
the box to run cable back to the controller.
NOTE: Refer to the sections Cabling a Display
with a Single Controller on page 10 and
Cabling a Display with Multiple Controllers
on page 11 in this chapter for wire ter-
minations.
2. Ground the display unit.
3. Ensure the aeration holes located on the side of
the display are not covered.
4. Place the display in the bracket, apply slight pres-
sure on the front of the display. Make sure to push
the display in all the way so that it is rmly secured
in place
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
1010
Cabling a Display with a Single Controller
Figure 11 shows the connections made to the display
for power and communications in a single controller
application.
1. The serial communications RS-485 cable con-
nects to the SA bus on the controller and ter-
minates on the SERIAL port of the display. The
SERIAL port adapter is factory provided. The SA
bus adapter on the controller is eld provided.
2. Options 1, 2, and 3 include a 24 VDC power sup-
ply to power on the display. Refer to Table 11 on
page 35 for detailed information on kit compo-
nents.
3. Use the RJ-12 modular jack for the SA bus pro-
vided on the controller to connect to the MAP.
Terminate the RJ-45 cable on the display from
the MAP in any of the available (ETH0/ETH1/
ETH2) ports. This guide shows the RJ-45 cable
connected to the ETH2 port on the display.
NOTE: Refer to Viewing MAP Application on
page 26 for more details.
RJ-45 from MAP to Display
S
A
B
u
s
R
S
-
4
8
5
P
o
w
e
r
C
o
n
n
e
c
t
i
o
n
+
+
-
-
COM
SHLD
RJ-12 to MAP
+
-
COM
PWR
N
L
+ 15 VDC
2
4
V
D
C
P
o
w
e
r
S
u
p
p
l
y
Applied Smart Equipment
Main Control Board
(Controller)
SA Bus - MAP
LD28404
Figure 11: Single Controller Cable Connection
IP66 protection is guaranteed only when:
Maximum deviation from the plane surface to the
cut-out is 0.019 inches
Thickness of the case where it is mounted to the
equipment is 0.059 to 0.23 inches
Maximum surface roughness where the gasket is
applied is 0.004 inches
B
A
NOTE: A = Display; B = Installation Cutout
LD28403
Figure 10: Cutout and Display Clearances
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
For SA/FC bus cable recommendations and
controller terminal block information, refer to
the BACnet Integration Setup section in the
Johnson Controls Premier Rooftop Units Start-
Up and Operation Guide (5586996-JSG-A).
1111
Chapter 3
4. A 12–15 VDC voltage for the MAP is required. Or-
der Option 1 for touchscreen display installation
when the unit is without a factory installed MAP
and 110V transformer. Order Option 2 when install-
ing the touchscreen with a factory installed MAP
but a 110V transformer is not provided on the unit.
Order Option 3 when installing the touchscreen dis-
play with a factory installed MAP and a 110V trans-
former provided on the unit. A 110V transformer is
provided on the unit when at least one of the fol-
lowing options is installed: internal lights, UV lights,
gas heat, or a convenience outlet.
NOTE: When using the Ethernet port to connect on the
MAP, power must be supplied by an external
supply that is not the USB connection or the
SA/FC bus connection.
2. For integration to the display, Steps 3 and 5 are
only applicable to the Applied Smart Equipment
controller.
3. The serial communications RS-485 cable con-
nects to the FC bus on the controller and ter-
minates on the SERIAL port of the display. The
SERIAL port adapter is factory provided. The FC
bus adapter on the controller is eld provided.
NOTE: The multiple controller integration on the dis-
play using the FC bus cannot support appli-
cations where BACnet IP connection on the
Applied Smart Equipment controller is utilized.
For this application, FC bus does not support
BACnet IP, Modbus
or N2.
4. Options 1, 2, and 3 include a 24 VDC power supply
to power on the display. Refer to Table 11 on page
35 for detailed information on kit components.
5. Use the RJ-12 modular jack for FC bus provided
on the controller to connect to the MAP.
Terminate the RJ-45 cable on the display from
the MAP in any of the available (ETH0/ETH1/
ETH2) ports. This guide shows the RJ-45 cable
connected to the ETH2 port on the display.
NOTE: Refer to Viewing MAP Application on
page 26 for more details.
RJ-45
S
A
B
u
s
R
S
-
4
8
5
P
o
w
e
r
C
o
n
n
e
c
t
i
o
n
+
+
-
-
COM
SHLD
RJ-12 to MAP
+
-
COM
SHLD
N
L
+ 15 VDC
24 VDC
Power
Supply
SE
C
ont
r
o
ll
er
A
S
E
Cont
r
ol
le
r
B
Ethernet Switch (Optional)
Applied Smart Equipment
Main Control Board
(Controller)
+
COM
SHLD
FC Bus - MAP
LD28405
Figure 12: Multiple Controllers Cable Connection
Cabling a Display with Multiple Controllers
Figure 12 shows the connections made to the display
for power and communications in a multiple controller
application.
1. Connect multiple controllers in a daisy chain on
the FC bus.
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
For SA/FC bus cable recommendations and
controller terminal block information, refer to
the BACnet Integration Setup section in the
Johnson Controls Premier Rooftop Units Start-
Up and Operation Guide (5586996-JSG-A).
1212
6. A 12–15 VDC voltage for the MAP is required.
Refer to Step 4 to determine which kit to order
and Table 11 on page 35 for detailed informa-
tion on components provided with each kit.
NOTE: When using the Ethernet port to connect on the
MAP, power must be supplied by an external
supply that is not the USB connection or the
SA/FC bus connection.
Connect to a MAP
Display the main menu and menu navigation
View setpoint data and adjust/override setpoints
View alarm events
View graph data
View documents
Export data, restore backup, and clone using a
USB drive
Display faults and diagnosis
Update the display rmware
Key Concepts
Display
The display combines state-of-the-art connectivity fea-
tures and top performance in an advanced design. The
display is a glass projected capacitive touchscreen
with 10.1 inch wide screen and 1280x800 pixels. The
interface on the touchscreen display supports multi-
touch gesture programming
Figure 13 shows the home page layout of the display
with display screen components highlighted. See Table
2 on page 13.
Login/Logout
Date and Time
Navigation Wheel
Minimize/Maximize Navigation Wheel
Unit Status Bar
More
LD28406
Figure 13: Display Home Page
Chapter 4: Operating the Display
Introduction
The display is operated through a simple menu system
interface that provides easy, intuitive access to real-
time data and parameters stored in the controller.
This chapter describes how to:
Operate the touchscreen
Go to system settings
Enter a password
Establish communication with a controller
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
1313
Chapter 4
Operate the Touchscreen
A capacitive touchscreen is activated by human touch,
which serves as an electrical conductor used to stimu-
late the electrostatic field of the touchscreen. However,
gloves or specialized stylus pens may also be used.
Using the Display
Certain areas of the touchscreen always show the
same type of information during normal operation
(once the user has selected a display configuration).
These areas of the touchscreen are indicated in Figure
13 and described in Table 2 on page 13.
CAUTION
Do NOT use sharp objects that might damage the
surface of the screen.
CAUTION
Take care not to allow layers of dust to form on
the graphic panel in a way that might cause ac-
cumulation of static charges. Keep the faceplate of
the display clean. The equipment must be cleaned
only with a soft cloth and neutral soap product. Do
not use solvents.
Table 2: Display Screen Components
Area Description
Display Conguration Shows the unit conguration of the selected controller
Date and Time Shows the current time setup in the selected controller in 12 hour format
Login Shows the user login/logout information
More
Indicates when there are more pages of data associated with the current function.
Use the page up or page down key to display the next or previous page
Unit Status Bar
Lists the current unit status, zone temperature, discharge air temperature (DAT)
and indoor air quality (IAQ) information
Minimize/Maximize Navigation Wheel Tap on this to minimize/maximize the navigation wheel
Heat Shows the parameters associated with the heating function
Cool Shows the parameters associated with the cooling function
Economizer Shows the parameters associated with the economizer
Demand
Ventilation
Shows the parameters associated with demand ventilation
Alarm Shows the alarm summary
Settings Shows the conguration page
Graph Show graphs for sensors connected to the unit
USB
Functions
Provides the ability to do backup, restore, export data, and clone
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
1414
Table 3: Display Touch Commands
Motion Finger Action Description
Tap
Tap on the touchscreen with a nger. A single tap is used to make selections when
navigating through the menu or for user parameter selections
Double Tap (Tap-Tap)
Tap on the touchscreen twice in quick succession with a nger. Use the double tap
to access system settings for MAP setup
Swipe
Swipe on the touchscreen. This motion can be used to reveal internal components
of the cabinet
Zoom In
Pinch on the touchscreen with two ngers to zoom in. Zoom in is used to view trend
data, documents, and MAP application data
Zoom Out
Move two ngers in an outward direction on the touchscreen to zoom out. Zoom out
is used to view trend data, documents, and MAP application data
Procedure Overview
Table 4: Operating the Display
To Do This Follow These Steps
System Settings
To set up the MAP or to adjust screen settings such as brightness and calibration, double
tap on the touchscreen during the initial power up sequence
Enter a Password Enter user name and password on the login screen
Device Discovery Page
This page shows a drop-down of only single/multiple Applied Smart Equipment controllers
when integrated with the display on the common MS/TP bus. Select the controller to view
data. When multiple controllers are available, select the controller based on the Dev ID
address assigned to the unit’s controller
Conguration Page
This page shows the controller information that the display is communicating with currently.
MAP browser, the open PDF icon, and the navigation wheel can also be viewed
Home Page
Home page has a navigation wheel with symbols that represent categories for the main
menu. Also see an internal view of the unit by using the swipe motion on the cabinet
Home Page with Internal View
The home page with internal view always has the graphical representation of the internal
view of the cabinet. Navigation wheel is also shown in a maximized manner
View Setpoint Data
View the setpoint data after selecting a function in the main menu, and use the more arrows
to page through data
Adjust Setpoint
Tap on the setpoint data, and use adjust setpoint icon to change the value
NOTE: See the Detailed Procedures on page 22 in this chapter for further instructions for all of the tasks above.
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
1515
Chapter 4
Menu Navigation
Figure 14 shows a high level display navigation struc-
ture. For a complete menu structure with parameters,
units, and ranges, see Table 5.
Login Page
Device Discovery
Page
Home Page
Configuration
Page
Home Page with
Internal View
Heat
Cool Economizer Settings Graphs
USB
Fuctions
Alarms
Demand
Ventilation
LD28393
Figure 14: Display Navigation Structure
Table 5: Menu Navigation
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Heat
Heating Status
Heating Status
OFF-Idle, SAT Tempering, Morning Warmup,
Thermostat Heating, Unoccupied Heating,
Occupied Heating, OFF-Disabled, OFF-OAT
Lockout, OFF-SAT Limit, OFF-Waiting for
Changeover Delay, Comfort Ventilation
Air Proving Switch OFF, ON
Supply Fan %S Command %
Supply Fan Status
OFF-Idle, ON-Purge, ON-Gas Valve or
Limit Fault, ON-Defrost
Modulating Heat Output % / 0–100
Heat Stage 1 Status OFF, ON
Heat Stage 2 Status OFF, ON
Heat Stage 3 Status OFF, ON
Heat Stage 4 Status OFF, ON
Heat Stage 5 Status OFF, ON
Heat Stage 6 Status OFF, ON
Heat Stage 7 Status OFF, ON
Heat Stage 8 Status OFF, ON
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
1616
Table 5: Menu Navigation (Continued)
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Heat
Heating Setup
(Click >> to
continue to the
next page of
parameters)
Heating Mode Enabled For Operation No, Yes
Number of Heating Stages Installed 0–10
Heating Control Type None, Gas, Electric, Hot Water, Steam
Occupied Heating Setpoint deg F / 40–85
Unoccupied Heating Setpoint deg F / 45–98
Discharge Air Temp Setpoint Conguration
Fixed, OAT Reset, Supply Fan Reset,
Zone Temp Reset, External
Heating Discharge Air Temp Upper Setpoint deg F / 86–135
Heating Discharge Air Temp Lower Setpoint deg F / 85–134
Outdoor Air Temperature Reset Setpoint
Upper
deg F / 61–131
Outdoor Air Temperature Reset Setpoint
Lower
deg F / 60–130
Zone Temperature Reset Setpoint Upper deg F / 61–131
Zone Temperature Reset Setpoint Lower deg F / 60–130
Supply Fan Discharge Air Temp Setpoint
High Threshold
% / 0–100
Supply Fan Discharge Air Temp Setpoint Low
Threshold
% / 0–100
Heating Adaptive Tuning Enable No, Yes
Outdoor Air Temp Heating Cutout Setpoint deg F / 0–100
Morning Warmup Enabled No, Yes
Morning Warmup/Return Air Temp Setpoint deg F / 50–85
Morning Warmup Discharge Air Temp Setpoint deg F / 85–135
Unoccupied Heating Enabled No, Yes
Discharge Air Temp Tempering Enable No, Yes
Discharge Air Temp Tempering Setpoint deg F / 40–60
Staged Heating Command %
Heating Status
OFF-Idle, ON-Defrost, SAT Tempering,
Morning Warmup, Thermostat Heating,
Unoccupied Heating, Occupied Heating,
OFF-Disabled, OFF-OAT Lockout, OFF-
SAT Limit, OFF-Waiting for Changeover
Delay, Comfort Ventilation
Operating Heating Setpoint deg F
Operating Heating Discharge Air Temp Setpoint deg F
Operational Outdoor Air Temperature deg F
Operational Zone Temperature deg F
Return Air Temperature deg F
Discharge Air Temperature deg F
Heating Entering Temperature deg F
Heat Entering Temp Sensor Alarm Normal, Alarm
Discharge Air Temperature Tempering State Disable, Enable
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
1717
Chapter 4
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Cool
Cooling Setup
(Click >> to
continue to the
next page of
parameters)
Cooling Mode Enabled For Operation No, Yes
Number of Cooling Stages Installed
Occupied Cooling Setpoint deg F / 45–98
Unoccupied Cooling Setpoint deg F / 46–99
Discharge Air Temp Setpoint Conguration
Fixed, OAT Reset, Supply Fan Reset,
Zone Temp Reset, External
Cooling Discharge Air Temp Upper Setpoint deg F / 40–79
Cooling Discharge Air Temp Lower Setpoint deg F / 41–80
Outdoor Air Temperature Reset Setpoint
Upper
deg F / 51–111
Outdoor Air Temperature Reset Setpoint
Lower
deg F / 50–99
Zone Temperature Reset Setpoint Upper deg F / 51–81
Zone Temperature Reset Setpoint Lower deg F / 50–80
Supply Fan DAT Setpoint High Threshold % / 0–100
Supply Fan DAT Setpoint Low Threshold % / 0–100
Compressor 1A Enabled Yes, No
Compressor 1B Enabled Yes, No
Compressor 2A Enabled Yes, No
Compressor 2B Enabled Yes, No
Modulating Compressor Enable Disable/Enable
Circuit 1 Outdoor Air Temperature Cooling
Cutout
deg F / …75
Circuit 2 Outdoor Air Temperature Cooling
Cutout
deg F / …75
Morning Cooldown Enabled No, Yes
Morning Cooldown/Return Air Temp Setpoint deg F / 50–85
Morning Cooldown Discharge Air Temp
Setpoint
deg F / 40–69
Circuit 1 Number of Condenser Fans 1–2
Circuit 2 Number of Condenser Fans 1–2
Circuit 1 Modulating Condenser Fan Installed True, False
Circuit 2 Modulating Condenser Fan Installed True, False
Cooling Service
(Click >> to
continue to the
next page of
parameters)
Staged Cooling Demand % / 0–100
Cooling Status
OFF-Idle, Thermostat Cooling, Unoccupied
Cooling, Occupied Cooling, OFF-OAT
Lockout, OFF-Disabled, OFF-Lockout, OFF-
Low Supply Voltage, OFF-LowAmbient,
OFF-Low Ambient Pre-Run Delay, OFF-
Waiting For Changeover Delay, OFF-Free
Cooling, Comfort Ventilation
Operating Cooling Setpoint deg F / 0–100
Operating Cooling Discharge Air Temp
Setpoint
deg F
Table 5: Menu Navigation (Continued)
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
1818
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Cool
Cooling Service
(Click >> to
continue to the
next page of
parameters)
Operational Outdoor Air Temperature deg F
Operational Zone Temperature deg F
Return Air Temperature deg F
Econ Free Cooling Available No, Yes
Discharge Air Temperature deg F
Condenser Fan 1A OFF, ON
Condenser Fan 1B OFF, ON
Condenser Fan 2A OFF, ON
Condenser Fan 2B OFF, ON
Modulating Condenser Fan 1 Command % / 0–100
Modulating Condenser Fan 2 Command % / 0–100
Minimum Runtime for a Cooling Stage minutes / 3–10
Rapid Start Time Limit minutes / 0–15
Cooling Adaptive Tuning Enable No, Yes
Freeze Condition Setpoint deg F / 20–32
Evaporator Temperature deg F
Suction Line Pressure 1 psi
Liquid Line Pressure 1 psi
Suction Line Temperature 1 deg F
Liquid Line Temperature 1 deg F
Suction Line Pressure 2 psi
Liquid Line Pressure 2 psi
Suction Line Temperature 2 deg F
Liquid Line Temperature 2 deg F
Economizer
Economizer
Service
Cooling Status
OFF-Idle, Thermostat Cooling, Unoccupied
Cooling, Occupied Cooling, OFF-OAT
Lockout, OFF-Disabled, OFF-Lockout, OFF-
Low Supply Voltage, OFF-LowAmbient,
OFF-Low Ambient Pre-Run Delay, OFF-
Waiting For Changeover Delay, OFF-Free
Cooling, Comfort Ventilation
Economizer Status
Disabled, Damper Not Functional, Purge,
Unavailable-Sensor Fault, Econ Loading,
SAT High Limit, Mixed Air Low Limit
Cycle, Demand Ventilation Air Quality,
Outdoor Airow Control, Free Cooling is
Active, Miinimum Position, Test, Comfort
Ventilation, Low OA Ambient
Econ Free Cooling Available No, Yes
Economizer Damper % Command %
Supply Air Temperature deg F
Operational Outdoor Air Temperature deg F
Outdoor Air Enthalpy Btu/lb
Table 5: Menu Navigation (Continued)
Johnson Controls
Touchscreen Installation & Operation Manual | 5795595-JIM-A-1019
Johnson Controls
1919
Chapter 4
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Economizer
Economizer
Service
Return Air Enthalpy Btu/lb
Operational Indoor Air Quality ppm
Operational Outdoor Air Quality ppm
Fresh Air Intake Value CFM
Economizer Damper Position % Open
FDD Economizer Alarm Delay seconds / 1–3600
FDD Economizer Damper Allowed Error % / 0–100
FDD Damper Min Position Tolerance % / 0–100
Return Air Damper Position %
Return Air Damper Command %
Return Air Humidity Sensor Alarm Normal, Alarm
Demand
Ventilation
Demand
Ventilation
Setup
Continuous Ventilation Yes, No
Fan O Delay for Heat seconds / 0–30
Fan O Delay for Cool seconds / 0–30
Pre-Filter Dierential Pressure iwg
Final Filter Dierential Pressure iwg
Maximum Airow cfm / 0–100,000
UV Light Installed No, Yes
UV Light Lifetime hours / 0–20,000
Pickup Gain 0–100
Demand
Ventilation
Service
(Click >> to
continue to the
next page of
parameters)
Supply Fan Accumulated Runtime hours
Supply Fan Number Times On counts
Operating Fan Request OFF, ON
Fan Request Source
Unreliable, Local Input, Network Sensor,
High Priority, BAS Override, Input Not
Available
Fan VFD1 Accumulated Runtime hours
Fan VFD1 Number of Times On counts
Air Proving Switch OFF, ON
Supply Fan VFD 1 Fault Normal, Alarm
Supply Fan VFD 2 Fault Normal, Alarm
Discharge Air Static Pressure iwg
Discharge Air High Duct Pressure Normal, Alarm
Discharge Air Dierential Pressure iwg
Discharge Air VP Sensor Alarm Normal, Alarm
Return Air VP Sensor Alarm Normal, Alarm
Return Fan Pressure Sensor Alarm Normal, Alarm
UV Light Runtime hours
UV Light Needs Service Normal, Alarm
UV Light Runtime Reset OFF, Reset
UV Light Runtime Override hours / 0–100,000
Table 5: Menu Navigation (Continued)
Johnson Controls
5795595-JIM-A-1019 | Touchscreen Installation & Operation Manual
Johnson Controls
2020
Menu Submenu Parameters Displayed
Conditions for Parameter Displayed
Units / Range
Demand
Ventilation
Energy
Recovery
Wheel (ERW)
Heat Recovery Wheel Status
OFF, Max Cooling, Max Heating, Blocking
Protection, Heating Control, Heating Low
Limit
Supply Fan Command OFF, ON
Econ Free Cooling Available No, Yes
Exhaust Air Heat Recovery Temp deg F
Heat Recovery Wheel Command OFF, ON
Heat Recovery Wheel Output %
Heat Recovery FBD Command OFF, ON
Demand
Ventilation
Exhaust Setup
Exhaust Type
None, Barometric, Modulating Damper,
Variable Frequency Fan
Exhaust Damper Position for Exhaust Fan to
Turn ON
% / 20–99
Exhaust Damper Position for Exhaust Fan to
Turn OFF
% / 10–89
Building Pressure Setpoint iwg / -0.25 to 0.25
Pickup Gain 0–100
Demand
Ventilation
Exhaust Service
Exhaust Fan Status
OFF-Idle, ON-Normal Command, OFF-
Disabled, OFF-VFD Fault, OFF-Low
Building Static Pressure, OFF-Economizer
Damper Position
Exhaust Fan Command OFF, ON
Building Static Pressure iwg
Exhaust Damper % Command %
Exhaust Flow Value CFM
Power Ex VFD OFF, ON
Exhaust Fan VFD % Command %
Exhaust Fan Accumulated Runtime hours
Exhaust Fan VFD Fault Normal, Alarm
Exhaust Air Dierential Pressure iwg
Demand
Ventilation
Return Fan
Setup
Return Fan Installed False, True
Return Fan Pressure High Setpoint iwg / 0–5
Return Fan Pressure Low Setpoint iwg / 0–5
Building Pressure Setpoint iwg / -0.25 to 0.25
Demand
Ventilation
Return Fan
Service
Exhaust Flow Value CFM
Building Static Pressure iwg
Return Fan VFD Percent Command %
Exhaust Damper % Command %
Return Fan Command OFF, ON
Return Air Dierential Pressure iwg
Table 5: Menu Navigation (Continued)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42

Johnson Controls Premier Series Installation & Operation Manual

Category
Split-system air conditioners
Type
Installation & Operation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI