Vertiv MPH2 Rack Quick start guide

Type
Quick start guide
Emerson Network Power MPH2TM Rack PDU
Rack Mount and Setup Quick Installation Guide
1
To Contact Technical Support: Visit www.EmersonNetworkPower.com
SL-20861_REV3 590-1379-501A
Emerson, Emerson Network Power, the Emerson Network Power logo, MPH2 and RPC2 are trademarks or service marks of Emerson Electric Co. Avocent and the Avocent logo are trademarks or service marks
of Avocent Corporation. Liebert is a trademark or service mark of Liebert Corporation. All other marks are the property of their respective owners. This document may contain confidential and/or proprietary
information of Avocent Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or
use without specific authorization from Avocent Corporation is strictly prohibited. ©2016 Avocent Corporation. All rights reserved.
HELPFUL RESOURCES
Product documentation downloads are
available on the product page at:
www.EmersonNetworkPower.com
For hardware inquiries:
1-800-222-5877, ext. 1
+800-1155-4499, ext. 1 (outside North America)
liebert.upstech@emerson.com
For firmware inquiries:
1-800-222-5877, ext. 2
+800-1155-4499, ext. 2 (outside North America)
liebert.monitoring@emerson.com
VERTICAL MPH2 RACK PDU MOUNTING
A vertical MPH2 rack PDU may be mounted
by using either the supplied in-line brackets
or the supplied mounting buttons.
Determine which mounting method best
suits your rack and install the necessary
hardware in the rack. The rack PDU may be
mounted so that its input power cord exits
at either the top or bottom of the rack.
In-line bracket installation
Install the brackets by inserting the legs of
each bracket into the slots on each end of
the rack PDU.
Insert two of the supplied spring nuts into
the appropriate T-slot on the rack frame.
Use a small, pointed object to position the
spring nuts into place.
Hold the bottom of the rack PDU assembly
over the desired mounting holes in the rack
frame or rack manufacturer’s bracket and
insert the fasteners into the PDU bracket.
Leave the fasteners slightly loose.
Position the top PDU bracket over the
desired mounting holes and insert its
fasteners. Tighten all rack PDU bracket
fasteners.
Button mount installation
Use a torx screw to attach the supplied
button mounts to the rear of the rack PDU.
NOTE: Only use the mounting buttons
provided with the MPH2 rack PDU. Using other
mounting buttons may damage the rack PDU.
Find the keyhole slots in the rack frame or
install the rack manufacturer’s keyhole slot
brackets in the desired location in the rack.
Insert each of the attached mounting
buttons into the large opening of a
keyhole slot.
Slide the assembly down into
the narrow portion of the keyhole slots to
lock in place.
HORIZONTAL MPH2 RACK PDU
MOUNTING
Attach the supplied brackets to each side
of the rack PDU. Attach each bracket to the
rack using the appropriate screws for your
rack.
Button mount installation
Button
Mount
Keyhole Slot
Back View Front View
Springnuts in
Rack Frame
In-line bracket installation
Horizontal installation
In-line
Bracket A
B
C
Emerson Network Power MPH2TM Rack PDU
Rack Mount and Setup Quick Installation Guide
2
To Contact Technical Support: Visit www.EmersonNetworkPower.com
SL-20861_REV3 590-1379-501A
Emerson, Emerson Network Power, the Emerson Network Power logo, MPH2 and RPC2 are trademarks or service marks of Emerson Electric Co. Avocent and the Avocent logo are trademarks or service marks
of Avocent Corporation. Liebert is a trademark or service mark of Liebert Corporation. All other marks are the property of their respective owners. This document may contain confidential and/or proprietary
information of Avocent Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or
use without specific authorization from Avocent Corporation is strictly prohibited. ©2016 Avocent Corporation. All rights reserved.
MPH2 RACK PDU SETUP
NOTE: Ensure all devices to be powered
through the MPH2 rack PDU are turned off and
unplugged from input power sources.
1Connecting to a network
Connect an ethernet cable from your
network to the RPC2 Communications
Module’s Network port.
2Connect Devices’ Power Cords
NOTE: Record where each piece of equipment
is connected using the branch and receptacle
numbers on the MPH2 rack PDU for reference.
Connect the devices’ input power cables to
the MPH2 rack PDU’s outlets.
3Creating a Rack PDU Array
Use an RJ-45 cable to connect the link port
of the first MPH2 rack PDU to the Network
In port of the second MPH2 rack PDU;
repeat for up to two more MPH2 rack PDUs.
4Connecting an SN sensor
Use an RJ-45 cable to connect an approved
SN sensor to the sensor port of the RPC2
Communications Module.
5
Connecting a console server or switch
Use an Ethernet cable to connect a console
server or switch to the serial port of the
RPC2 Communications Module.
6Connnecting a Basic Display Module
Use an RJ-45 cable to connect an optional
Basic Display Module (BDM) to the display
port of the RPC2 Communications Module.
7Turning on the MPH2 rack PDU
Ensure all circuit breakers on the unit are
in the Off position. Connect input power
to the MPH2 rack PDU. Press the circuit
breaker down into the On position. Verify
input power is present, the LEDs are
illuminated and the onboard display is
turned on. Turn on the connnected devices
one at a time.
8Viewing IP address, MAC address and
Firmware version
Use the arrow keys under the LCD of
the MPH2 rack PDU to highlight the
Information icon, then press the select key,
which is located between the arrow keys.
Use an arrow key to highlight the Network
icon and press the select key again. The
LCD displays the IP address, MAC address
and RPC2 module firmware version.
Serial
Port
RPC2 Communications Module ports
Sensor
Port
Display
Port
Link
Port
Network
Port
MPH2 Rack PDU configuration
(Vertical model shown)
1
3
2
4
6
5
Powered Devices
Network
Basic Display Module
Console Server
or Switch Sensor
Additional PDUs
  • Page 1 1