7
107958-01 - 8/17
WARNING
All combustion performance numbers MUST be veried with a combustion analyzer. Failure to do so could
result in substantial property damage, severe personal injury or death.
29. Selectthecorrectboilersize,altitude,andfuelusingthetouchscreendisplay.
a. Checkboiler'sratinglabelforactualboilersize.
b. Conrminstallationaltitude.
c. Press"Adjust"buttonontheHomescreen.
d. Press"Adjust"buttonontheAdjustModescreen.
e. Press"Login"buttontoaccessPasswordscreen.
f. Press5-digitdisplaytoopenakeypad.Enter the password "86"andpressthereturnarrowtoclosekeypad.
Press"Save"button.
g. Press"Adjust"buttontoenterAdjustmentMode.
h. Press"ModulationSetup"menubutton.
i. Press"Adjust"buttonafterreadingWarningscreen.
j. Usethearrowbuttonstoselectthecorrectsize,altitude,andfuelofyourboiler.Pressthe(Checkwith
Circle)buttontoenteryourselection.
k. Press"Enter"buttonuntildisplaystopsblinking,pressnextandrepeatuntil"Completed"isdisplayed.
l. PressXtoexit.
m. Press"Conrm"toverifycorrectsize,altitude,andfuelisdisplayed.
30. Attempttostarttheboilerusingtheoperatinginstructionslocatedoninsideofboilerfrontdoor.Iftheboilerdoesnot
lightonthersttryforignition,allowboilertomakeatleastfourmoreattemptstolight.Ifboilerstilldoesnotlight,
turnthethrottlecounter-clockwisein1/8turnincrements,allowingtheboilertomakeatleastfourtriesforignitionat
eachsetting,untiltheboilerlights.
31. Aftertheburnerlights,forcetheburnertohighrebyenteringtheAdjustMenuandthenHighFireHoldasdescribed
inSectionXI"Start-upandCheckout"ofI,O&SInstructions.Allowtheboilertooperateforapproximately5minutes
beforetakingcombustionreadings.Note:after10minutes,theboilerisautomaticallyreleasedfromhighrehold.
32. Performacombustiontest,samplingueproductsfromthetapinfrontoftheventadaptor.
33.Withburnerathighre,adjustthrottleasneededtoobtainCO
2
(orO
2
)settingshowninTable10:
• ToreduceCO
2
(increaseO
2
)turnthrottleclockwise.
• ToincreaseCO
2
(reduceO
2
)turnthrottlecounterclockwise.
Makeadjustmentsinincrementsof
1
/
8
and
1
/
4
turnsandallowtheboileratleastaminutetorespondtoeachadjustment
beforemakinganother.
34. ForceburnertolowrebyenteringtheAdjustMenuandthenLowFireholdasdescribedinSectionXI"Start-upand
Checkout".Allowtheboilertooperateforapproximately5minutesbeforetakingcombustionreadings.
35.Withburneratlowre,adjustoffsetregulatorasneededtoobtainCO
2
(orO
2
)settingshowninTable10.
• ToreduceCO
2
(increaseO
2
)turnoffsetregulatorcounter-clockwise.
• ToincreaseCO
2
(reduceO
2
)turnoffsetregulatorclockwise.
Makeadjustmentsinincrementsnomorethan
1
/
8
turnsandallowtheboileratleastaminutetorespondtoeach
adjustmentbeforemakinganother.
WARNING
Asphyxiation Hazard. Use combustion analyzer for all gas valve adjustments. Low re offset screw is very
sensitive. Adjust offset no more than 1/8 turn before checking combustion with analyzer. Maximum total
offset adjustment ± 1 turn. Adjustments greater than ± 1 turn may damage regulator diaphragm. Failure to
follow these instructions could result in death, serious injury or substantial property damage.