Omega LVCN210 LVCN318 LVCN414 Series Owner's manual

Type
Owner's manual
1
2
3
INTRODUCTION/TABLEOFCONTENTS StepOne
The small tank sensor is an innovative level sensor family that replaces float, conductance and pressure
sensors that fail due to contact with dirty, sticking and scaling media in small (< 4’/1.25m) to medium
(<18’/5.5m)talltanks.Appliedinskid,machine,toolandprocessapplications,thegeneral purposesensors
areavailablewithsingleandmultifunctioncapabilitiesincludingmeasurement,switchingandcontrol.
NewFeatures
Easilychangeoutputfromdistancetovolume
Selectfrom6standardtankshapesora16pointstrappingtableforcustomer/oddsizetanks
TableofContents
Specifications:.........................................................................................................................................................4
Dimensions: .........................................................................................................................................................5
SafetyPrecautions:................................................................................................................................................6
Components: .........................................................................................................................................................7
GettingStarted:......................................................................................................................................................8
USB®FobInterface:...............................................................................................................................
....8
LVCN414SWSoftware:..........................................................................................................................................9
1.OutputConfiguration:..........................................................................................................................10
LVCN414,LVCN210,LVCN318,LVCN414Rseries:......................................................................10
LVCN414Iseries:........................................................................................................................17
LVCN414Vseries:........................................................................................................................19
2.TankShapeSelection:..........................................................................................................................22
3.LevelConfiguration:.............................................................................................................................27
4.WritetoUnit:.......................................................................................................................................29
Wiring: .......................................................................................................................................................30
WiringDiagram:.......................................................................................................................................30
WireConnections:....................................................................................................................................31
SwitchInductiveLoads:............................................................................................................................32
Installation: .......................................................................................................................................................33
MountingGuide:......................................................................................................................................33
FittingSelection:......................................................................................................................................34
TankAdapter:...............................................................................................................................34
Riser:............................................................................................................................................34
Flange:..........................................................................................................................................35
SideMountFitting:......................................................................................................................35
StandPipe:...................................................................................................................................36
AdvancedFeature:...............................................................................................................................................37
Appendix: .......................................................................................................................................................38
SampleProgram:......................................................................................................................................38
UpdatingSoftware:..................................................................................................................................39
UpdatingTransmitterFirmware:.............................................................................................................40
StrappingTable:.......................................................................................................................................41
Linervs.NonLinear:................................................................................................................................42
Troubleshooting....................................................................................................................................................44
FactoryDefaults........................................................................................................................................44
DemoPage:..............................................................................................................................................45
SolutionTable:.........................................................................................................................................46
4
SPECIFICATIONS StepTwo
Range: LVCN414I/LVCN414/LVCN414
R/LVCN414V:49.2”(1.25m)
LVCN210:9.8’(3.0m)
LVCN318:18.0’(5.5m)
Accuracy: LVCN414I/LVCN414/LVCN414
R/LVCN414V:0.125”(3mm)
LVCN210:+/‐0.2%ofrange
LVCN318:+/‐0.2%ofrange
Resolution: LVCN414I/LVCN414/LVCN414
R/LVCN414V:0.019”(0.5mm)
LVCN210:0.039”(1mm)
LVCN318:0.079”(2mm)
Deadband: LVCN414I/LVCN414/LVCN414
R/LVCN414V:2”(5cm)
LVCN210:4”(10cm)
LVCN318:8”(20cm)
Beamwidth: LVCN414I/LVCN414/LVCN210/
LVCN414R/LVCN414V:2”(5cm)
dia.
LVCN318:3”(7.6cm)dia.
Configuration: LVCN414SW(software)PC
WindowsUSB®2.0
Memory: Nonvolatile
Supplyvoltage: LVCN414I/LVCN414/LVCN210/
LVCN318:24VDC(loop)
LVCN414R:1224VAC/VDC
LVCN414V:1228VDC
Consumption: 0.5W
Loopresistance:LVCN414I/LVCN414/LVCN210/
LVCN318:400Ohmsmax
Signaloutput: LVCN414I/LVCN414/LVCN210/
LVCN318:420mA,twowire
LVCN414V:05V,010V,976
2000Hz
Frequency: LVCN414Vonly:sinkcurrent,15
mAnominal
Signalinvert: LVCN414I/LVCN414/LVCN210/
LVCN318:420mAor204mA
LVCN414V:50V,100V,2000
976Hz
Signalfailsafe: LVCN414I/LVCN414/LVCN210/
LVCN318:4mA,20mA,21mA,22
mAorholdlast
LVCN414V:Full,emptyorhold
last
Contacttype: LVCN414/LVCN210/LVCN318/
LVCN414R:(4)SPSTrelays
Contactrating: LVCN414/LVCN210/LVCN318/
LVCN414R:60VA,1Amaximum
Contactfail
safe:
LVCN414/LVCN210/LVCN318/
LVCN414R:Powerloss:Holdlast,
Poweron:Open,closeorholdlast
Hysteresis: LVCN414/LVCN210/LVCN318/
LVCN414R:Selectable
Processtemp.: F:20°to140°
C:‐to60°
Temp.comp.: Automatic
Ambienttemp.: F:‐31°to140°
C:‐35°to60°
Pressure: MWP=30PSI
Enclosurerating: Type6Pencapsulated,corrosion
resistance&submersible
Encl.material: Polycarbonate
Strainrelief
mat’l.:
ThermoplasticElastomer(TPE)
Trans.material: PVDF
Cablejacket
mat’l:
Polyurethane
Cabletype: 9conductor,shielded
Cablelength: 48”(1.2m)
Processmount: LVCN414I/LVCN414/LVCN414
R/LVCN414V/LVCN210:1”NPT
LVCN318:2”NPT
Mountgasket: FKM
Classification: Generalpurpose
Compliance: CE,RoHS

5
DIMENSIONS StepThree
LVCN318Series LVCN210Series
LVCN414I,LVCN414,LVCN414R&LVCN414VSeries

6
SAFETYPRECAUTIONS StepFour
About this Manual:PLEASE READ THE ENTIRE QUICK START PRIOR TO INSTALLING OR USING THIS
PRODUCT.ThismanualincludesinformationonthesmalltankseriesUltrasonicLevelSwitch,controllerand
transmitterfromOMEGAENGINEERING.Pleaserefertothepartnumberlocatedontheswitchlabeltoverify
theexactmodelconfiguration,whichyouhavepurchased.
User’s Responsibility for Safety:OMEGA ENGINEERING manufactures a broad range of level sensing
technologies. While each of these sensors is designed to operate in a wide variety of applications, it is the
user’sresponsibilitytoselectasensormodelthatisappropriatefortheapplication,installitproperly,perform
tests of the installed system, and maintain all components. The failure to do so could result in property
damageorseriousinjury.
ProperInstallationandHandling:Onlyprofessionalstaffshouldinstalland/orrepairthisproduct.Install
thetransmitterwiththeincludedFKMgasketandneverovertightenthetransmitterwithinthefitting.Always
checkforleakspriortosystemstartup.
WiringandElectrical:Asupplyvoltageof12to28VDC(VACforLVCN414Rseriesonly)isusedtopower
the ultrasonic sensor.Electrical wiring of the transmitter should be performed in accordance with all
applicablenational,state,andlocalcodes.
Material Compatibility:The enclosure is made of Polycarbonate (PC).The transducer is made of
PolyvinylideneFluoride(PVDF).Makesurethatthemodel,whichyouhaveselected,ischemicallycompatible
withtheapplicationmedia.
Enclosure: While the transmitter housing is liquidresistant the Ultrasonic sensor is not designedto be
operationalwhenimmersed.Itshouldbemountedinsuchawaythattheenclosureandtransducerdonot
comeintocontactwiththeapplicationmediaundernormaloperationalconditions.
Safety
Installationshouldbedonebyproperlytrainedstaff
Supplyvoltageshouldneverexceedamaximumof28VDC
Makesurethesensorischemicallycompatiblewithyourapplication
Designafailsafesystemthataccommodatesthepossibilityofsensorand/orpowerfailure
Thissensorshouldnotbeusedinclassifiedhazardousenvironments
Make a FailSafe System:Design a failsafe system that accommodates the possibility of transmitter
and/orpowerfailure.OMEGAENGINEERINGrecommendstheuseofredundantbackupsystemsandalarms
inadditiontotheprimarysystem.
Flammable, Explosive or Hazardous Applications:The sensor should not be used within classified
hazardousenvironments.
Warning: Always use the FKM gasket when installing the ultrasonic sensor, and make sure that all
electricalwiringoftheswitchisinaccordancewithapplicablecodes.
7
COMPONENTS StepFive
Thesmalltankultrasonicsensorisofferedindifferentmodels.Dependingonthemodelpurchased,youmay
ormaynothavebeenshippedallthecomponentsshownbelow.Youdohowever,needasensor,USB® Fob
andFKMgaskettoconfigure,installandoperatetheultrasonicsensor.
FKMGasket
o Part #204038 used with LVCN414I,
LVCN414,LV
CN414R&LVCN414Vseries
o Part#200128usedwithLVCN210series
o Part#200129usedwithLVCN318series
USB® Fob (Part #LVCN414USB) included with
LVCN414I, LVCN414, LVCN210, LVCN318,
LVCN414RandLVCN414Vseries.
o Fob is not in
cluded with theLVCN414IB,
LVCN414B, LVCN210B, LVCN318B,
LVCN414RBandLVCN414VBseries.
QuickStartGuide
*Outputs
1. 420mA,looppoweredoutput
2. 4SPST60VArelays
3. Voltage(0to2.5,5or10VDC)output
4. Frequency(9762000Hz.)output
P/N Max.Range DeadBand Thread Fob *Outputs
LVCN414IB
LVCN414I
4.1’(1.25m) 2”(5cm)
1”NPT
NoFob
1
FobIncluded
LVCN414IGB
LVCN414IG
1”G
NoFob
FobIncluded
LVCN414B
LVCN414
4.1’(1.25m) 2”(5cm)
1”NPT
NoFob
1,2
FobIncluded
LVCN414GB
LVCN414G
1”G
NoFob
FobIncluded
LVCN210B
LVCN210
9.8’(3.0m) 4”(10cm)
1”NPT
NoFob
1,2
FobIncluded
LVCN210GB
LVCN210G
1”G
NoFob
FobIncluded
LVCN318B
LVCN318
18.0’(5.5m) 8”(20cm)
2”NPT
NoFob
1,2
FobIncluded
LVCN318GB
LVCN318G
2”G
NoFob
FobIncluded
LVCN414RB
LVCN414R
4.1’(1.25m) 2”(5cm)
1”NPT
NoFob
2
FobIncluded
LVCN414RGB
LVCN414RG
1”G
NoFob
FobIncluded
LVCN414VB
LVCN414V
4.1’(1.25m) 2”(5cm)
1”NPT
NoFob
3,4
FobIncluded
LVCN414VGB
LVCN414VG
1”G
NoFob
FobIncluded
8
GETTINGSTARTED StepFive
The small tank ultrasonic sensor is configured through a free PC software program (LVCN414SW).The
software is a free download from OMEGA ENGINEERING’s website.You must download and install the
softwarepriortopluggingintheUSB®Fob.
Pleasegotohttp://www.omega.com/ftp.
ClickonFlow,Level,pH,Environmental,andPressureSectionandpressonProducts
SelecttheLVCN414folder
Selecttheinstaller‐LVCN414InstallerverXpXX.zip
o Thiswilldownloadtheinstallerontoyourcomputer.
o Oncecompleted,runtheinstaller.
LVCN414SWSoftwareSystemRequirements
Windows®2000,XP,Vista,7,8
32or64bitsystem
1USB®2.0port
10mBharddrivespace
256mBRAM
Internetconnection
USB®FobInterface
The ultrasonic sensor communicate
s with LVCN414SW software through a USB® interface called a Fob.
Beforepluggingyour Fobintoyour computer’sUSB®port, be surethatyou have installed the LVCN414
SW
softwareonyourcomputer.
Connectthered,green,whiteandblackwiresfromsensorintothecorrectterminalsontheFob.Tightenthe
screwsontheterminalsandplugyourFobintotheUSB®portofyourcomputer.
WiringidenticalforallseriesUseonlytheRed,Black,GreenandWhitewires.
Themaximumcabledistancebetweenthecomputerandultrasonicsensoris15’.Thisonlyapplieswhen
configuringthesensor.
Oncetheultrasonicsensorisconfiguredandpriortoinstallation,isolate thewhiteandgreenwiresfrom
activepowertopreventashortoftheconfigurationcircuit.
Note:When
usingtheFob,donotaddVDCpower.TheFob,whenconnectedtothecomputer,willprovide
therequiredpowertotheultrasonicsensor.
9
LVCN414SWSOFTWARE StepSix
With the ultrasonicsensor connectedto your computer,open the LVCN414SWsoftware byclickingon the
software’sicon.Followsteps13toconfigurethetransmitter.Click“Help”inthelowerrighthandcornerand
openthehelpmenuforadditionalinstructions.Ifyouneedadditionalassistanceusingthesoftware,please
contactanOMEGAENGINEERINGApplicationsengineer.
TabsforConfiguration,
UpdatesandDemomode
ModelSelector
(SampleProgramOnly)
ConfigurationSelector
SensorDetails
LevelConfiguration
ActionButtons
TankSelector
AboveScreenCaptureisfortheLVCN414Series.
ConfiguringLVCN414,LVCN210&LVCN318SerieswithLVCN414SWSoftware
1. OutputConfiguration
a. Configurestherela
ysintermsofpump/valveoperationsaswellashighorlowalarms.
b. Setsfailsafefortherelaysandthesensor’soutput(current,voltageorfrequency).
2. TankShapeSelection
a. Definestheshapeofthetankaswellasthedimensionalinformationforthetankwithrespect
tothesensor’slocationonthetank.
3. LevelConfiguration
a. Entersthedist
ancevaluesfortheoperationalrangeofthesensor.
4. WritetoUnit
a. Uploadstheconfigurationintothesensor.
b. Providesacustomwiringdiagram.

10
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
1.OutputConfiguration
Thissectioniswhereyouselecttheapplication’sconfigurationsettings.Startfromthetopandworktothe
bottom,choosingtheselectionsthatareapplicabletoyourconfiguration.NotApplicablewillautomatically
showwhenaselectiondoesn’tapplytoyourconfigurationsettings,andyoumaymoveon.Allconfiguration
settingsmustbeselectedorhaveNotApplicablebeforeyoucancontinuetothenextstep.Note:Pressing
theClearScreenbuttonwillresettheconfigurationtableandallowaccesstoallofthefeatures.
NumberofPumps
Thisfeatureallowsyoutoselectthenumberofpumpsorvalvesused.
This is the setting that activates the control capabilities of up to two
relays.ControlrelaysareoftenreferredtoasLatchingrelays.
o Switch/Alarms Only The relayswill be standard single point
relays(Highand/orLowalarms).Relaysarenonlatching.
o 1‐ Pump/Valve One relay will be configured as a control or
latchingrelay(relay will have a start level and a separate stop
level).Use this setting to control one pump or valve for
automaticfillingoremptyingofatank.
o 2Pumps/Valves Two relays are configured as control or
latchingrelays.Eachrelaywillhavea unique start leveland a
common stop level.Use thissetting to control two pumpsor
valvesforautomaticfillingoremptyingofatank.
o 420mATransmitterOnlyThissettingwilldisengageallofthe
relays.Use this function if you are not using any relays and
usingonlythe420mAcurrentoutput.
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

11
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
Pump/ValveAction
Thisfeatureallowsyoutoselectifthepumpsorvalveswillbeusedto
automatically fill or empty the tank.For 2Pump/Valve mode, both
devices must be the same (automatic fill or empty).You cannot set
onerelayforfillandtheotherforempty.
o EmptiesTank Willsetrelay(s)toautomaticallyemptyatank.
StartlevelwillbeabovetheStoplevelforeachrelay.
o Fills Tank Will set relay(s) to automatically fill a tank.Start
levelwillbebelowtheStoplevelforeachrelay.
o Not Applicable Appears when this function is not available
(such as when Switch/Alarms Only or 420mA Transmitters
Onlyareselected).
 
EmptiesTank FillsTank
(AutoEmpty) (AutoFill)
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

12
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
Pump/ValveMode
This feature allows you to select the mode for a control or latching
relay.Pump/ValvemodeisnotactiveforSwitch/AlarmsOnlyor420
mATransmitterOnly.
o SimplexAllowsfortherelaytobeusedasanautomatic fillor
empty.This is the default and only configuration when 1
Pump/Valveisselected.
SimplexusedtoEmptyTank(example)
o Lead/LagAllowsforth
etworelaystohaveuniquestartlevels
and a common stop level.The first relay will be identified as
the lead relay and thesecond relay asthe lag.Each time the
lead level is reached, the first relay will always start.Th
e lag
relaywillonlystartwhenthelaglevelisreached.Allrelayswill
stopatthecommonofflevel.
Lead/LagusedtoEmptyTank(example)
o Duplex‐Allowsforthetworelaystohavetwodifferentstartlevels,acommonstoplevelandwill
alternatetherelayswhenthefirststart levelis reached.The tworelayswillalternateeach time
theleadlevelisreachedandtheremainingrelaywillstartwhenthelaglevelisreached.Allrelays
willstopatthecommonofflevel.
DuplexusedtoEmptyTank(example)
o NotApplicab
leAppearswhenthisfunctionisnotavailable(suchaswhenSwitch/AlarmsOnlyor
420mATransmittersOnlyareselected).
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

13
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
RelayFailSafe
This feature allows you to select the failsafe state for the relays.
Whenthesensorregainssignal,theoutputcurrentwillrevertbackto
thecurrentlevelcondition.
o Relays Off ‐ The relays will revert to the OFF state.Appears
whenSwitch/AlarmsOnlyisselected.
o Relays On ‐ The relays will revert to the ON state.Appears
whenSwitch/AlarmsOnlyisselected.
o Hold State‐The relay(s) will remain in the same state as the
lastechodetected.Whenthesensorregainssignal,therelays
willreverttothelevelwhenthesignalwasregain.
o Pump/Valves Off ‐ The relays will revert to the OFF state.
Appearswhen1Pump/Valveor2Pumps/Valvesareselected.
o Pump/Valves On ‐ The relays will revert to the ON state.
Appearswhen1Pump/Valveor2Pumps/Valvesareselected.
o Not Applicable Appears when this function is not available
(suchaswhenTransmittersOnlyareselected).
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

14
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
Switch/AlarmConfiguration
This feature allows you to select the operation for the switches /
alarms(usedasahighorlowalarm).Thissettingadjuststhenumber
ofavailablerelaysbasedupontheprevioussettings.
o NoAlarmTurnsoffalloftheremainingrelays.
o High Alarm Options Set from1 to 4 HighAlarms (1High, 2
High,3High,4High).
o Low Alarm Options Set from 1 to 4 Low Alarms (1Low, 2
Low,3Low,4Low).
o Combination Alarms Set a combination of High and Low
Alarms (1Low 1High, 1Low 2High, 2Low 1High, 2Low 2
High,1Low3High,3Low1High).
o Not Applicable Appears when this function is not available
(suchaswhenTransmittersOnlyisselected).


HighAlarmOptions LowAlarmsOptions CombinationAlarms
(4High) (4Low) (2Highand2Low)
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

15
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
SwitchHysteresis/Deadband
This feature allows you to select a hysteresis or dead band for the
remaininghighand/orlowalarms.
o OptionsforHysteresis/DeadbandNoHysteresis,¼”,½”,1”,
2”,½cm,1cm,2cm,5cmorNotApplicable.
o High Alarms Relay activates above set point.Relay will
deactivatewhenlevelgoesbelowthesetpointplusthevalueof
thehysteresis.
o Low Alarms Relay activates below set point.Relay will
deactivatewhenlevelgoesabovethesetpointplusthevalueof
thehysteresis.

HighAlarmw/Hysteresis
LowAlarmw/Hysteresis
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

16
SOFTWARE‐OUTPUTCONFIG.LVCN414,LVCN210,LVCN318andLVCN414RSeriesonly StepSix
LoopFailSafe‐(NotAvailablewithLVCN414Rseries)
This feature allows you to select the failsafe current output if the
sensor fails todetect a returnsignal. Whenthe sensorregains signal,
theoutputcurrentwillrevertbacktothecurrentlevelcondition.
o Hold Last Value‐The outputwill remainin the samestate as
thelastechodetected.Example:Iftheoutputwas6.7mAjust
prior to the lost signal, the device will continue to output 6.7
mA.Sensorwillindicatethelevelwhensignalwasregain.
o Empty‐ The output will revert to the current value for an
emptycondition. When4mAatBottomisselected,thesensor
willoutput4mAwhenafailsafeconditionoccurs.If20mAat
Bottom is selected, the sensor will output 20 mA when a fail
safeconditionoccurs.
o Full ‐ The output will revert to the current value for a full
condition.When 4 mA at Bottom is selected, the sensor will
output 20 mA when a failsafe condition occurs.If 20 mA at
Bottomisselected,thesensorwilloutput4mAwhenafailsafe
conditionoccurs.
o Overfill(21mA)‐Theoutputcurrentwillgoto21mAwhenthe
returnsignalislost.
o Overfill(22mA)‐Theoutputcurrentwillgoto22mAwhenthe
returnsignalislost.
OutputatEmpty‐(NotAvailablewithLVCN414Rseries)
This featureallows you to select the orientation of the 4 to20mA output (4 to 20mA or 20 to 4mA).
Choosewhichoutputsettingbestfitstheapplication.Typicalinstallationsaresetwith4mAatBottom.
Thiswillnotaffectthe performance of the sensor other than the output.The factory defaultis4mAat
bottom and 20mA at top. When connecting your sensor to a display, yo
u must account for your output
settings.
o 4mAat Bottom‐Theoutputcurrentwillbe4mAwhenthesensormeasuresanemptytankand
20mAwhenthesensormeasuresafulltank.
o 20mAatBottom‐Theoutputcurrentwillbe20mAwhenthesensormeasuresanempty tankand
4mAwhenthesensormeasuresafulltank.
Note:Right
clickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

17
SOFTWARE‐OUTPUTCONFIGURATIONLVCN414ISeriesonly StepSix
LoopFailSafe
This feature allows you to select the failsafe current output if the
sensor fails todetect a returnsignal. Whenthe sensorregains signal,
theoutputcurrentwillrevertbacktothecurrentlevelcondition.
o Hold Last Value‐The outputwill remainin the samestate as
thelastechodetected.Exampl
e:Iftheoutputwas6.7mAjust
prior to the lost signal, the device will continue to output 6.7
mA.Sensorwillindicatethelevelwhensignalwasregain.
o Empty‐ The output will revert to the current value for an
emptycondition. When4mAatBottomisselected,thesensor
willoutput4mAwhenafailsafeconditionoccurs.If20mAat
Bottom is selected, the sensor will output 20 mA when a fail
safeconditionoccurs.
o Full ‐ The output will revert to the current value for a full
condition.When 4 mA at Bottom is selected, the sensor will
output 20
mA when a failsafe condition occurs.If 20 mA at
Bottomisselected,thesensorwilloutput4mAwhenafailsafe
conditionoccurs.
o Overfill(21mA)‐Theoutputcurrentwillgoto21mAwhenthe
returnsignalislost.
o Overfill(22mA)‐Theoutputcurrentwillgoto22mAwhenthe
returnsignalislost.
OutputatEmpty
This featureallows you to select the orientation of the 4 to20mA output (4 to 20mA or 20 to 4mA).
Choosewhichoutputsettingbestfitstheapplication.Typicalinstallationsaresetwith4mAatBottom.
Thiswillnotaffectthe performance of the sensor other than the output.The factory defaultis4mAat
bottom and 20mA at top. When connecting your sensor to a display, you must account for your output
settings.
o 4mAat Bottom‐Theoutputcurrentwillbe4mAwhenthesensormeasuresanemptytankand
20mAwhenthesensormeasuresafulltank.
o 20mAatBottom‐Theoutputcurrentwillbe20mAwhenthesensormeasuresanempty tankand
4mAwhenthesensormeasuresafulltank.
Note:Right
clickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

18
SOFTWARE‐OUTPUTCONFIGURATIONLVCN414ISeriesonly StepSix
StartupCondition
Thisfeatureallowsyoutoselectthestartupcurrentwhenpowerisfirst
appliedtothesensor.TheLVCN414Iwillconsumetheselectedpower
whileitisacquiringtheleveloftheliquid.Whenthecorrectlevelhas
beenidentified,theoutputwilladjusttothecorrectoutput.Usethis
feature to avoid false alarms with the controller when power is first
applied.
o Empty‐Thecurr
entoutputwillreverttothecurrentvaluefor
an empty condition.When 4 mA at Bottom is selected, the
sensorwilloutput4mAwhilethesensorpowersup.If20mA
at Bottom is selected,the sensor willoutput 20mA whilethe
sensorpowe
rsup.
o Mid Tank (12 mA) The output will hold at 12 mA until the
correctlevelisread.
o Full ‐ The output will revert to the current value for a full
condition.When 4 mA at Bottom is selected, the sensor will
output20mAwhilethesensorpowersup.If20mAatBottom
isselected,thesensorwilloutput4mAwhilethesensorpowers
up.
o Overfill(22mA)‐Theoutputcurrentwillgoto22mAwhilethe
sensorpowersup.
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

19
SOFTWARE‐OUTPUTCONFIGURATIONLVCN414VSeriesonly StepSix
SelectOutput
ThisfeaturesetstheoutputfortheLVCN414Vseries.Theoutputcan
eitherbeavoltageoutputorafrequencyoutput.
o Voltage Selectthis option for a voltage output.You will be
abletoselectvoltagescaleof02.5V,03.3V,05Vor010V.
o Frequency Select this option for a frequency/pulse output.
Theoutputwillbefixedfrom976to2000Hz.
MaximumOutput
This sets the maximum output for the LVCN414V series.If Voltage
was selected above, then the maximum value will be in Volts.If
Frequencyisselected,thenthemaximumvaluewillbeinHertz.
o VoltageChoosefrom:2.5Volts,3.3Volts,5Voltsor10Volts.
o FrequencyThisvalueisfixedat2000Hz.
MinimumOutput
ThissetstheminimumoutputfortheLVCN414Vseries.IfVoltagewas
selectedabove,thentheminimumvalue willbeinVolts.IfFrequency
isselected,thentheminimumvaluewillbeinHertz.
o VoltageChoosefrom:0.25Volts,0.5Volts,0.833Volts,1Volt
or2Volts.
o FrequencyThisvalueisfixedat976Hz.
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.

20
SOFTWARE‐OUTPUTCONFIGURATIONLVCN414VSeriesonly StepSix
OutputatEmpty
This feature allows you to select the orientation of the voltage or
frequencyoutput(ex.Empty=1voltandfull=10voltsvs.empty=10
volts and full = 1 volt).Choose which output setting best fits the
application.Typical installations areset with Minimum Output.This
will not affect the performance of the sensor other than the output.
When connecting your sensor to a display, you must account for your
outputsettings.
o
Minimum Output ‐ The output current will be the smallest
value.If reading in Voltage, this will be the minimum output
voltage.IfreadinginFrequency,thiswillbe976Hz.
o Maximum Output ‐ The output current will be the largest
value.Ifreadingin Voltage, this willbe the max
imum output
voltage.IfreadinginFrequency,thiswillbe2000Hz.
FailSafeOutput
Thisfeatureallowsyoutoselectthefailsafeoutputifthesensorfails
to detecta return signal. When the sensor regains signal, the output
currentwillrevertbacktothecurrentlevelcondition.
o Hold Last Value‐The outputwill remainin the samestate as
thelastechodetected.Example:Iftheoutputwas6.7voltsjust
prior to the lost signal, the device will continue to output 6.7
volts.Sensorwillindicatethelevelwhensignalwasregain.
o Empty‐The output will revert to the current value for an empty condition.When Minimum
Output isselected,thesensor will output the lowestvoltageorfrequencyvaluewhena failsafe
condition occurs.If Maximum Output is selected, the sensor will output the highest voltage or
frequencyvaluewhenafailsafeconditionoccurs.
o Full ‐ Theoutput will revert tothe currentvalue for afull condition.When Minimum Output is
selected,thesensorwilloutputthehighest
voltageorfrequencyvaluewhenafailsafecondition
occurs.If Maximum Output is selected, the sensor will output the lowest voltage or frequency
valuewhenafailsafeconditionoccurs.
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClear
Screenbutton.

  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48