Hiflex
8 All Versions
English
Here is a summary list of the peculiar features of the different versions:
Heat exchange Refrigerating circuit Installation
A
The unit cools the air by an air/refrigerant
coil (direct expansion).
The refrigerating circuit condenser is ex
ternally mounted, air-cooled.
The refrigerating circuits are not
pre-charged with refrigerant.
There is a liquid receiver on
which the safety valve is instal
led.
The Constant units are equiped
with hot gas by-pass valve.
The unit must be connected
to the external condenser
and the refrigerant must be
charged.
W
The unit cools the air by an air/refrigerant
coil (direct expansion).
The refrigerating circuit plate condenser is
indoor, cooled by a water flow.
The refrigerating circuits are
pre-charged with refrigerant.
The safety valve is installed
downstream the condenser.
The Constant units are equiped
with hot gas by-pass valve.
The unit must be connected
to the piping of the cooling
water of the water/refrigerant
condenser.
D
The dualfluid unit cools the air flow by
means of an air/refrigerant coil (direct ex
pansion) or, as an alternative, an air/water
coil.
The refrigerating circuit condenser is ex
ternally mounted, air-cooled.
The refrigerating circuits are not
pre-charged with refrigerant.
There is a liquid receiver on
which the safety valve is instal
led.
It is necessary to connect
the unit to the external con
denser, to charge it with re
frigerant and to connect the
chilled water piping for the
air/water coil.
H
The dualfluid unit cools the air flow by
means of an air/refrigerant coil (direct ex
pansion) or, as an alternative, an air/water
coil.
The refrigerating circuit plate condenser is
indoor, cooled by a water flow.
The refrigerating circuits are
pre-charged with refrigerant.
The safety valve is installed
downstream the condenser.
The unit must be connected
to the chilled water piping
for the air/water coil and to
the cooling water piping of
the water/refrigerant con
denser.
F
The freecooler unit cools the air flow by
means of an air/refrigerant coil (direct ex
pansion) or, as an alternative, an air/water
coil. The water flow is cooled by an exter
nal rad-cooler. When the external tempe
rature is higher than the ZET, the water
exchanges heat with the refrigerant in the
internal water/refrigerant plate condenser.
When the external temperature is lower
than the ZET, the water is cooled as much
as sufficiently to cool the air directly in the
air/water coil.
The refrigerating circuits are
pre-charged with refrigerant.
The safety valve is installed
downstream the condenser.
The unit must be connected
to the closed water circuit
with the rad-cooler.
C
The unit cools the air flow by an air/water
coil.
The unit has no refrigerating cir
cuit.
The unit must be connected
to the chilled water piping.