The LVCN1700 Series is a generalpurpose ultrasonic level switch that provides the end user the ability to
control up to three unique devices (pump, valves and/or alarms) through an advanced noncontact
technology.LVCN1700Seriesfeaturespushbuttonconfigurationthatusesrealengineeringvaluesforsetting
uptherelayoperation(s).OnerelayhasSPDTForm“C”contactsuseful forcontrollingavalveandtheother
tworelaysareSPSTForm“A”.Alloftherelayscanbeusedforcontrollingvalves,pumpsoralarms.
Features
Simpledigitalpushbuttonconfiguration.
Pumpsimplex,duplexandtriplexoption.
Integratedtimerforpump/valvedelayandpumpalternation.
Availableina3m(9.8’),5.5m(18.0’)or8m(26.2’)maximumrange.
Isolated4/20mAloopoutputforindicatinglevel.
ACpowered
TableofContents
Specifications:.........................................................................................................................................................4
Dimensions:.............................................................................................................................................................4
SafetyPrecautions:.................................................................................................................................................5
GettingStarted:.......................................................................................................................................................7
GettingaroundtheMENU:.........................................................................................................................8
Configuration........................................................................................................................................................11
HowtoentertheMENU...........................................................................................................................11
HowtoconfigureUNITS............................................................................................................................11
HowtoconfiguretheOperationalrangeofLVCN1700Series.................................................................12
HowtosetaHIGHALARM........................................................................................................................13
HowtosetaLOWALARM........................................................................................................................13
HowtoFillatank/vesselwithapump......................................................................................................14
HowtoEmptyatank/vesselwithapump................................................................................................15
HowtoFillatank/vesselwithavalve.......................................................................................................16
HowtoEmptyatank/vesselwithavalve.................................................................................................17
HowtoDuplextwo
relays.........................................................................................................................18
HowtoAlternatetworelays.....................................................................................................................18
HowtoTriplexthreerelays.......................................................................................................................19
HowtoturnoffMPLEX(DUPLEXorTRIPLEX)..........................................................................................20
HowtoTimeAlternaterelays...................................................................................................................20
Electrical................................................................................................................................................................21
InputPowerandRelayConnections.........................................................................................................21
AnalogOutput
(4/20mA).........................................................................................................................22
Installation............................................................................................................................................................23
MountingGuide........................................................................................................................................23
Installationinexistingfittings...................................................................................................................24
Appendix...............................................................................................................................................................27
Troubleshooting........................................................................................................................................29

4
SPECIFICATIONS/DIMENSIONS StepTwo
Range: LVCN1710:4"to9.8' LVCN1718:8"to18.0’ LVCN1726:8"to26.2'
(10cmto3m) (20cmto5.5m) (20cmto8m)
Repeatability: 0.25"(6.35mm)
LoopOutput: Isolated,Sinking
12to28VDC
Deadband: LVCN1710:4”(10cm)
LVCN1718:8”(20cm)
LVCN1726:8”(20cm)
LCDindication: Levelandrelaystatus,6
character
Configuration: Pushbutton,digital(3)
Supplyvoltage: 95250VAC,20W@120VAC
Contacttype: Relay1,SPDTrelays
Relay2and3,SPST,N.O.
Allcommonsconnected
together
Contactrating: 2A,30VDC
60W(DC),125VA
220VDC,250VAC
Contactfailsafety: Programmable/selectable
Temp.comp.: Automatic
Electronicstemp.: F:‐40°to140°
C:‐40°to60°
Pressure: MWP=30PSI
Enclosurerating: NEMA4X(IP65)
Enclosurevent: Watertightmembrane
Encl.material: Polycarbonate
Encl.hardware: Brassandstainless
Trans.material:
PVDF
Processmount: LVCN1710:1”NPT(G)
LVCN1718:2”NPT(G)
LVCN1726:2”NPT(G)
Mount.gasket: FKM
Conduitentrance: Dual,1/2”NPT
Classification: Generalpurpose
Compliance: RoHS
Approvals: CE
SideView
LVCN1710Series
SideView
LVCN1718&LVCN1726Series
TopView
AllModels

5
SAFETYPRECAUTIONS StepThree
AboutthisManual:PLEASEREADTHEENTIREMANUALPRIORTOINSTALLINGORUSINGTHISPRODUCT.This
manualincludesinformationontheLVCN1700SeriesUltrasonicLevelControllerfromOMEGAENGINEERING.
Pleaserefertothepartnumberlocatedontheswitchlabeltoverifytheexactmodelconfiguration,whichyou
havepurchased.
User’s Responsibility for Safety:OMEGA ENGINEERING manufactures a broad range of level sensing
technologies. While each of these sensors is designed to operate in a wide variety of applications, it is the
user’sresponsibilitytoselectasensormodelthatisappropriatefortheapplication,installitproperly,perform
tests of the installed system, and maintain all components. The failure to do so could result in property
damageorseriousinjury.
ProperInstallationandHandling:Onlyproperlytrainedstaffshouldinstalland/orrepairthisproduct.Install
theswitchwiththeincluded FKMgasketandneverovertightentheswitchwithinthefitting.Alwayscheckfor
leakspriortosystemstartup.
WiringandElectrical:Asupplyvoltageof95250VACisusedtopowertheLVCN1700Series.Electricalwiring
oftheswitchshouldbeperformedinaccordancewithallapplicablenational,state,andlocalcodes.
Material Compatibility:The enclosure is made of Polycarbonate (PC).The transducer is made of
PolyvinylideneFluoride(PVDF).Make surethatthemodel,whichyouhaveselected,ischemicallycompatible
withtheapplicationmedia.
Enclosure:While theswitchhousingisliquid resistanttheLVCN1700Seriesisnotdesignedtobeoperational
when immersed.It should be mounted in such a way that the enclosure and transducer do not come into
contactwiththeapplicationmediaundernormaloperationalconditions.
The enclosure has a flip cover with dual 1/2” NPT female conduit ports and an internal terminal strip for
wiring.Toopentheenclosure,youwillneedasmallinsertiontoolsuchasascrewdriver.Loosenthelocking
screwlocatedatthe topfrontoftheenclosure.Rotatethehingedcoverupfor135°accesstothefaceplate
andterminal strips.Beforeclosingtheenclosure,makesurethattheenclosuregasketisproperlyseated,and
thatanyconduitfittings,cableconnectorsorplugsareinstalledcorrectlyandsealed.
HandlingStaticSensitiveCircuits/Devices:Whenhandlingthetransmitter,thetechnicianshouldfollowthese
guidelines to reduce any possible electrostatic charge buildup on the technician’s body and the electronic
part.
1. Always touch a known good ground source before handling the
part. This should be repeated while
handling the part and more frequentlyafter sitting down from a standing position, sliding across the
seatorwalkingadistance.
2. Avoidtouchingelectricalterminalsofthepartunlessmakingconnections.
3. DONOTopentheunitcoveruntilitistimetocalibrate.
4. Wipeunitwithadampclothwhencleaning.

6
SAFETYPRECAUTIONS(cont.) StepThree
MakeaFailSafeSystem:Designafailsafesystemthataccommodatesthepossibilityofswitchand/orpower
failure.OMEGAENGINEERINGrecommendsthe use of redundant backup systems and alarmsinaddition to
the primary system.Adding a redundant high level float switch to the system is a cost effective means to
preventcostlytankoverflows.
The switch has (3) relay channels.Normally open (NO) or normally closed (NC) operation is user selected
basedonthedesiredsystemcontrolandfailsafelogicwhentheultrasonicinstrument lossesitsreturnsignal
due to situations such as foam in the tank.Always design a failsafe system that accommodates for the
possibility of functional and/or powerfailuretotheinstrument.The"normal"relaystateiswheretherelay
coil is deenergized and the relay indicator is OFF. Therefore, if power is cut OFF to the switch it will de
energizetherelay.Makesurethatthedeenergizedstateisthesafestatein yoursystemdesign.Assuch,if
switchpowerislost,apumpwillturnOFFifitisconnectedtothenormallyopensideoftherelay.
Flammable,ExplosiveorHazardousApplications:LVCN1700Seriesshouldnotbeusedwithinclassified
hazardousenvironments.
Components:LVCN1700Seriesisofferedinthreedifferentmodels.ComecompletewithLVCN1700Series
LevelController,FKMGasketandOwner’sManual.
LVCN1700Series
o LVCN1710‐9.8’(3m)range, Type4Xencl., 1”NPT
o LVCN1710G‐9.8’(3m)range, Type4Xencl., 1”G
o LVCN1718 18.0’(5.5m)range, Type4Xencl., 2”NPT
o LVCN1718‐G 18.0’(5.5m)range, Type4Xencl., 2”G
o LVCN1726 26.2’(8m)range, Type4Xencl., 2”NPT
o LVCN1726G 26.2’(8m)range, Type4Xencl., 2”G
FKMGasket
o Part#200128forLVCN1710series
o Part#220129forLVCN1718orLVCN1726series
Owner’sManual

7
GETTINGSTARTED StepFour
LVCN1700Seriescanbe configured before installation.The switch features nonvolatile memory, so theset
pointsconfiguredbeforeinstallationwillnotbelostwhentheswitchispowereddown.Tostart,allyouneed
isthefollowinginformation:
BasicTankInformation
o HEIGHTDistancefromthetransducer
face
tothebottomofthetank.
o FILLHMaximumfillheightofthe liquid
fromthebottomofthetank.
SetPoints:
o Youwillneedthemeasureddistance
fromthebottomofthetanktoeachset
point.Thesevalueswillallbeinthesame
distancevalue(inches,centimeters,feet
ormeters)andwillallbemeasuredfrom
thebottomofthetank.
Power:
o ProvideinputpowertotheLVCN1700
Series
Note: The Height and FillHeight settings also
determine the 4 to 20 mA current span.The
Height setting determines the 4mA position and
theFillHsettingdeterminesthe20mAposition.


8
GETTINGSTARTED(continued) StepFour
GettingAroundtheMenu:LVCN1700Seriesisconfiguredbytheuseofthreepushbuttons(UP,DOWNand
SELECT)andaLCDdisplay.Asa lockoutfeature,thebuttonsareinactiveuntiltheSELECTbuttonishelddown
for5seconds,andthenthedisplaywillbegintoscrollthroughthetopleveloftheconfigurationmenu.
TopLevel
TheConfigurationmenuwillcontinuetoscrollthroughtheitemsbelowuntiltheSELECTbuttonispressed.
o UNITSTANKRELAY1RELAY2RELAY3SAFE(MPLEX)‐HELP‐RUN
ToreturntotheOperationalmodeofLVCN1700Series,pressSELECTwhileRUNappearsinthedisplay.
UNITSAllowsendusertoselecttheunitsforconfigurationandoperation.SelectbetweenInches,
Centimeters,Feet,MetersorPercent.PressEXITtoreturntotheTopLevelmenu.
TANKAllowstheendusertoconfiguretheoperationalrangefortheswitch.
o HEIGHTDistancefromthetransducerfacetothebottomofthetank.
o FILLHMaximumfillheightoftheliquidfromthebottomofthetank.
o Note:The4/20mApointsaresetbysettingthesetwopoints.The20mApointisattheFillHand
the4mApointisatthebottomofthetank.
o PressExittoreturntotheToplevelMenu
o Note:ifUNITSissettoPercent,thenTANKwillnotappear.ToviewTANK,setUNITStoanyofthe
following:Inches,Centimeters,FeetorMeters
RELAY1,RELAY2orRELAY3Allowsendusertoconfigurethefunctionandoperationofeachrelay.
Eachrelayhasasmallblackcirclethatappearswhentherelayisenergized.Whentherelayisde
energized,theblackcircledisappears.
o PUMPPumpoperationallowsfortwoseparatelevelsetpoints(RelayONandRelayOFF).
ChoosebetweentheEMPTYorFILLoperation.BothoperationsrequiresettingalevelforONand
anotherlevelforOFF
EMPTYusedtocontrolapumpthatemptiesatank.
Typically,RelayONistheHIGHsetpointandRelayOFFtheLOWsetpoint.Relaywill
energizeatthehighsetpoint(ON)andremainonuntilthelevelreachesthelowset
point(OFF)andwillremainoffuntilthelevelreturnsto
thehighsetpoint(ON).

9
GETTINGSTARTED(continued) StepFour
FILLusedtocontrolapumpthatfillsatank.
Typically,RelayONistheLOWsetpointandRelayOFFtheHIGHsetpoint.Relaywill
energizeatthelowsetpoint(ON)andremainonuntilthelevelreachesthehighset
point(OFF)andwillremainoffuntilthelevelreturnstothelowsetpoint(ON).
DELAYusedasastartpumpdelaywhentheONsettingisreached.Thedelaypump(in
seconds)willdelaythestartofthevalueforthisperiod.
o VALVEValveoperationallowsfortwoseparatelevelsetpoints(RelayONandRelayOFF).Choose
betweentheEMPTYorFILLoperation.BothoperationsrequiresettingalevelforONandanother
levelforOFF
EMPTYusedtocontrolavalvethatemptiesatank.
Typically,RelayONistheHIGHsetpointandRelayOFFtheLOWsetpoint.Relaywill
energizeatthehighsetpoint(ON)andremainonuntilthelevelreachesthelowset
point(OFF)andwillremainoffuntilthelevelreturnstothehighsetpoint(ON).
FILLusedtocontrolavalvethatfillsatank.
Typically,RelayONistheLOWsetpointandRelayOFFtheHIGHsetpoint.Relaywill
energizeatthelowsetpoint(ON)andremainonuntilthelevelreachesthehighset
point(OFF)andwillremainoffuntilthelevelreturnstothelowsetpoint(ON).
DELAYusedasastartvalvedelaywhentheONsettingisreached.Thedelayvalue(in
seconds)willdelaythestartofthevalueforthisperiod.

10
GETTINGSTARTED(continued) StepFour
o ALARMAlarmoperationallowsforasinglesetpoint(RelayONandOFFatthesamelevel).
ChoosebetweenHIGHandLOWoperation.Bothoperationswillrequireasinglesetpointanda
settingfortheHysteresis(HYSTER)
HIGHusedtocontrolaHighLevelalarm.Relaywillenergize(ON)whenthelevelisabove
thesettingandwilldeenergize(OFF)whenthelevelfallsbelowthesettingplustheadded
distancefromthehysteresis(HYSTER).
LOWusedtocontrolaLowLevelalarm.Relaywillenergize(ON)whenthelevelisbelow
thesettingandwilldeenergize(OFF)whenthelevelrisesabovethesettingplustheadded
distancefromthehysteresis(HYSTER).
HYSTERUsedtoreducechatterbycreatingahysteresisordifferentialfortheAlarmset
point.TheHYSTERvaluewilladjusttheOFFpositionoftheAlarmsettingbytheHYSTER
value.
SAFEEachrelaycanbeindividuallyconfiguredtoitsindependentfailsafesetting.ChoosebetweenON,
OFForHOLD
o ONEnergizestherelaywhenafailsafeconditionoccurs
o OFFDeenergizestherelaywhenafailsafeconditionoccurs
o HOLDKeepstherelayinitscurrentstatewhenafailsafeconditionoccurs
o OUTPUTSetsthe4/20mAoutputstatewhentheechoislost.Theoptionsare4mA,21mAand
holdlastvalue.
MPLEXwhentwoorthreerelaysareconfiguredaspumps,theycanbeinter–connectedtoalternate
betweeneachcycle.MPLEXisonlyavailablewhen2ormorerelaysaresetforpumps.MPLEXwillnot
appearwhenonly1relayissetforapumporwhentherelayfunctionsdonotmatch(ex:Relay1set
fora
fillingpumpandRelay2setforanemptyingpump).SelectingNOALTwillturnOFFtheMPLEX.
HELPProvidessetupinformation,theabilitytoresettheLVCN1700Seriesandasimulationmodetotest
therelayfunction
o SETUPWilldisplaythesettingforallfunctionsofLVCN1700Series
o RESETWillresettheLVCN1700Seriesbacktoitsoriginalfactorysetting
o SIMTSIM(ulation)T(est)willallowtheendusertosimulatechangestoleveltoverifytherelay
settings.UsingtheUPandDOWNbuttonswillincrease
o TESTPThisisaproductiontestfeatureusedbythefactorytoconfirmoperation.Thismode
shouldonlybeusedwhensupervisedbyaOMEGAEngineeringrepresentative.
RUNReturnstheunittonormalmeasurementandcontrolmode

11
CONFIGURATION StepFive
ThissectionwilltakeyouthroughthekeystepsinthesetupandconfigurationoftheLVCN1700Series:
1) Selecttheunitsforconfiguration.
a. Determinethemeasurementunitsthatwillbeusedtoconfigurethesensor.
2) Measurethedistancefromthebottomofthetank(emptylevel)tothebottomofthesensor.
a. Besuretoincludetheaddedheightofinstallationfittings.
3) Measurethedistancefromthebottomofthetank(emptylevel)tothefulllevelofliquid.
a. Takeintoaccountthedeadbandofthesensor.
4) Determinehowmanyrelaysyouwilluseandwhateachoftheirfunctionswillbe.
a. Example:relaywillfillatankwithapumpandrelay2willprovideahighalarm.
5) Measurethedistancesfromthebottomofthetank(emptylevel)tothepositionsforalloftherelay
functions.
a. PumpandValvefunctionswillhavetypicallyhavetwosetpoints,thelevelwherethepump
turnsonandwhereitturnsofforthelevelwherethevalveopensandcloses.
HowtoentertheMENU
1. PressandholdSELECTkey(approximately5seconds)untilMENUisdisplayed.
2. Themenuitemswillrotatethroughdisplay.
3. PressSELECTtochangeanitem.
HowtoconfigureUNITS
1. IntheMENUmode,pressselectwhenUNITSisdisplay.
2. PressSELECTtochoosebetweenINCHES,CM(centimeter),FEET,METERSorPERCENT.
3. SelectEXITtoreturntotheTopLevelMenu.
Note:ReadingthelevelofliquidinPercent
OMEGAEngineeringrecommendsthatwhenselectingPERCENT,configuretheHeightandFill_H
settingsbeforeselectingPERCENTinordertospantheLVCN1700Seriesforyourapplication
requirements.
WheninPERCENT,theoperationalspanwillbebaseduponthelastTANKsettings,100%willoccurat
theFillHleveland0percentatthebottomofthetank.
WhenPERCENTisselected,theTANKsettings(HeightandFill_H)willbedisabled.

12
CONFIGURATION(cont.) StepFive
HowtoconfiguretheOperationalrangeofLVCN1700Series
NocumbersomemeasurementisrequiredviaTargetCalibration
toestablishsetpoints.Allsetpointdistancesarerelativetothe
tankbottom
1. InMENUmode,selecttheTANKitem
2. SelectHEIGHT.
3. UsingtheUPandDOWNbuttons,settheHEIGHTofthe
tankfromthetransducerfacetothebottomofthetank.
4. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
5. WhenFILLHappears,pressSELECT.
6. UsingtheUPandDOWNbuttons,settheFillHeight(FILL
H)
tothemaximumfillheightoftheliquidfromthe
bottomofthetank.
7. PressandholdSELECT(2seconds)toenterthevalue.
8. SelectEXITtoreturntoTopLevelMenu.
Note:TheHeightandFillHeightsettingsalsodeterminethe4to
20mAcurrentspan.
TheHeightsettingdeterminesthe4mA
positionandtheFillHsettingdeterminesthe20mAposition.
Note:Tospeedupthescrollingofthevaluesonthedisplay,hold
downtheSELECTbuttonwhileholdingdowntheUPorDOWN
buttons.

13
CONFIGURATION(cont.) StepFive
HowtosetaHIGHALARM
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenALARMappears,pressSELECT.
3. WhenHIGHappears,pressSELECT.
4. UsingtheUPandDOWNbuttons,settheHIGH(ON)set
pointfortherelay.
5. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
6. WhenHYSTERappears,pressSELECT.
7. Hysteresis[HYSTER]isthedistanceawayfromtheoriginal
ONsettingwheretheAlarmwillturnOFF.
8. UsingtheUPandDOWNbuttons,settheHYSTER(OFF)
set
pointfortherelay.
9. PressandholdSELECT(2seconds)toenterthevalue.
10. SelectEXITtoreturntoTopLevelMenu.
Note:Thehysteresis(HYSTER)settingcanbeusedtoeliminate
chatteringoftherelay.
Note:Tospeedupthescrollingofthevaluesonthedisplay,
hold
downtheSELECTbuttonwhileholdingdowntheUPorDOWN
buttons.
HowtosetaLOWALARM
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenALARMappears,pressSELECT.
3. WhenLOWappears,pressSELECT.
4. UsingtheUPandDOWNbuttons,settheLOW(ON)set
pointfortherelay.
5. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
6. WhenHYSTERappears,pressSELECT.
7. Hysteresis[HYSTER]isthedistanceawayfromthe
originalONsettingwheretheAlarmwill
turnOFF.
8. UsingtheUPandDOWNbuttons,settheHYSTER(OFF)
setpointfortherelay.
9. PressandholdSELECT(2seconds)toenterthevalue.
10. SelectEXITtoreturntoTopLevelMenu.
Note:Thehysteresis(HYSTER)settingcanbeusedtoeliminate
chatteringoftherelay.
Note:Tospeedupthescrollingofthevaluesonthedisplay,hold
downtheSELECTbuttonwhileholdingdowntheUPorDOWN
buttons.
14
CONFIGURATION(cont.) StepFive
HowtoFillatank/vesselwithapump.
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenPUMPappears,pressSELECT.
3. WhenFILLappears,pressSELECT.
4. WhenONappears,pressSELECT.
5. UsingtheUPandDOWNbuttons,settheONsetpointfor
therelay.TheONsettingisalwaysthelevelwherethe
relaywillenergizeandwillbethelowerlevelbetween
thetwosetpoints.
6. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
7. WhenOFFappears,pressSELECT.
8. UsingtheUPandDOWNbuttons,settheOFFsetpoint
fortherelay.TheOFFsettingisalwaysthelevelwhere
therelaywilldeenergizeandwillbethehigherlevel
betweenthetwosetpoints.
9. PressandholdSELECT(2seconds)toenterthevalue.
IfyouwanttoaddadelaywhenthePUMPstarts,continue
ontostep10.Ifnodelayisrequired,jumptostep13.
10. WhenDELAYappears,pressSELECT.
11. UsingtheUPandDOWNbuttons,settheDELAYtimein
seconds.Pumpdelaycanbesetfrom0to600seconds.
12. PressandholdSELECT(2seconds)toenterthevalue.
13. SelectEXITtoreturntoTopLevelMenu.
Note:Tospeedupthescrollingofthevaluesonthedisplay,
holddowntheSELECTbuttonwhileholdingdowntheUPor
DOWNbuttons.

15
CONFIGURATION(cont.) StepFive
HowtoEmptyatank/vesselwithapump.
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenPUMPappears,pressSELECT.
3. WhenEMPTYappears,pressSELECT.
4. WhenONappears,pressSELECT.
5. UsingtheUPandDOWNbuttons,settheONsetpointfor
therelay.TheONsettingisalwaysthelevelwherethe
relaywillenergizeandwillbethehigherlevelbetween
thetwosetpoints.
6. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
7. WhenOFFappears,pressSELECT.
8. UsingtheUPandDOWNbuttons,settheOFFsetpoint
fortherelay.TheOFFsettingisalwaysthelevelwhere
therelaywilldeenergizeandwillbethelowerlevel
betweenthetwosetpoints.
9. PressandholdSELECT(2seconds)toenterthevalue.
IfyouwanttoaddadelaywhenthePUMPstarts,continue
ontostep10.Ifnodelayisrequired,jumptostep13.
10. WhenDELAYappears,pressSELECT.
11. UsingtheUPandDOWNbuttons,settheDELAYtimein
seconds.Pumpdelaycanbesetfrom0to600seconds.
12. PressandholdSELECT(2seconds)toenterthevalue.
13. SelectEXITtoreturntoTopLevelMenu.
Note:Tospeedupthescrollingofthevaluesonthedisplay,
holddowntheSELECTbuttonwhileholdingdowntheUPor
DOWNbuttons.

16
CONFIGURATION(cont.) StepFive
HowtoFillatank/vesselwithavalve.
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenVALVEappears,pressSELECT.
3. WhenFILLappears,pressSELECT.
4. WhenONappears,pressSELECT.
5. UsingtheUPandDOWNbuttons,settheONsetpointfor
therelay.TheONsettingisalwaysthelevelwherethe
relaywillenergizeandwillbethelowerlevelbetween
thetwosetpoints.
6. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
7. WhenOFFappears,pressSELECT.
8. UsingtheUPandDOWNbuttons,settheOFFsetpoint
fortherelay.TheOFFsettingisalwaysthelevelwhere
therelaywilldeenergizeandwillbethehigherlevel
betweenthetwosetpoints.
9. PressandholdSELECT(2seconds)toenterthevalue.
IfyouwanttoaddadelaywhentheVALVEstarts,continue
ontostep10.Ifnodelayisrequired,jumptostep13.
10. WhenDELAYappears,pressSELECT.
11. UsingtheUPandDOWNbuttons,settheDELAYtimein
seconds.Valvedelaycanbesetfrom0to600seconds.
12. PressandholdSELECT(2seconds)toenterthevalue.
13. SelectEXITtoreturntoTopLevelMenu.
Note:Tospeedupthescrollingofthevaluesonthedisplay,
holddowntheSELECTbuttonwhileholdingdowntheUPor
DOWNbuttons.

17
CONFIGURATION(cont.) StepFive
HowtoEmptyatank/vesselwithavalve.
1. InMENUmode,whentherelayyouwishtoprogramis
appears,pressSELECT.
2. WhenVALVEappears,pressSELECT.
3. WhenEMPTYappears,pressSELECT.
4. WhenONappears,pressSELECT.
5. UsingtheUPandDOWNbuttons,settheONsetpointfor
therelay.TheONsettingisalwaysthelevelwherethe
relaywillenergizeandwillbethehigherlevelbetween
thetwosetpoints.
6. Toenterthevalue,pressandholdSELECT(Approximately
2seconds)untilSAVEDisdisplayed.
7. WhenOFFappears,pressSELECT.
8. UsingtheUPandDOWNbuttons,settheOFFsetpoint
fortherelay.TheOFFsettingisalwaysthelevelwhere
therelaywilldeenergizeandwillbethelowerlevel
betweenthetwosetpoints.
9. PressandholdSELECT(2seconds)toenterthevalue.
IfyouwanttoaddadelaywhentheVALVEstarts,continue
ontostep10.Ifnodelayisrequired,jumptostep13.
10. WhenDELAYappears,pressSELECT.
11. UsingtheUPandDOWNbuttons,settheDELAYtimein
seconds.Valvedelaycanbesetfrom0to600seconds.
12. PressandholdSELECT(2seconds)toenterthevalue.
13. SelectEXITtoreturntoTopLevelMenu.
Note:Tospeedupthescrollingofthevaluesonthedisplay,
holddowntheSELECTbuttonwhileholdingdowntheUPor
DOWNbuttons.

18
CONFIGURATION(cont.) StepFive
HowtoDuplextworelays
Duplex enables LVCN1700 Series to use two relays to alternate after each cycle while performing a leadlag
operation.Tobegin,configuretworelaysinthesamemode(ex:tworelaysaresetasPUMPsthatFILLortwo
relayssetasPUMPsthatEMPTY).BesuretosetonerelaywithanONSetPointatthePrimaryLevelandthe
otherrelayONSetPointattheBackupLevel.Settingthe relayswiththesameONlevelwillhavecauseboth
relaystoturnonatthesametime.Oncethisiscompleted,see
thestepsbelow.Examplebelowshowstwo
relays(AandB)usedtoAutoEmptyatank:
1. Makesureatleasttworelaysareinthesamemodeforpumps.Ifthisisnottrue,thenMPLEXwillnot
appear.
2. WhenMPLEXappears,pressSELECT.
3.
WhenDUPLEXappears,pressSELECT.
Ifthreerelaysareconfiguresinthesamemode,continuetostep4.Ifnot,jumptostep5.
4. LVCN1700Serieswillallowyoutoselectwhichtwoofthreerelaysyouwouldliketoduplex.Whenthe
correctcombinationofrelays(R1_R2,R2_R3orR1_R3)isshown,pressSELECT.
5. SelectEXITtoreturntoTopLevelMenu.
HowtoAlternatetworelays
Alternate enables LVCN1700 Series to use two relays to alternate after each cycle.The configuration of
AlternateisidenticaltoDuplexwiththeexceptionoftheBackuplevelisatasettingwherethelevelwillnever
achievesetpoint.Tobegin,configuretworelaysinthesamemode(ex:tworelaysaresetasPUMPsthatFILL
ortworelayssetasPUMPsthatEMPTY).BesuretosetonerelaywithanONSetPointatthe PrimaryLevel
and
the other relay ON Set Point at the Backup Level.Setting the relays with the same ON level will have
causebothrelaystoturnonatthesametime.TheBackuplevelmustbesettoaleveloutofrange(levelwill
neverreachthissetting).Oncethisiscompleted,seethestepsbelow.Examplebelowshowstworelays(A
andB)usedtoAutoEmptyatank:

19
CONFIGURATION(cont.) StepFive
1. Makesureatleasttworelaysareinthesamemodeforpumps.Ifthisisnottrue,thenMPLEXwillnot
appear.
2. WhenMPLEXappears,pressSELECT.
3. WhenDUPLEXappears,pressSELECT.
Ifthreerelaysareconfiguresinthesamemode,continuetostep4.Ifnot,jumptostep5.
4. LVCN1700Serieswillallowyoutoselectwhichtwoofthreerelaysyouwouldliketoduplex.Whenthe
correctcombinationofrelays(R1_R2,R2_R3orR1_R3)isshown,pressSELECT.
5. SelectEXITtoreturntoTopLevelMenu.
HowtoTriplexthreerelays
TriplexenablesLVCN1700Seriestousethreerelaystoalternateaftereachcyclewhileperformingaleadlag
lagoperation.Tobegin,configure allthreerelaysinthesamemode(ex:allrelaysaresetasPUMPsthatFILL
or all relays set as PUMPs that EMPTY).Be sure
to set all three relay with different ON Set Point, one for
Primary,oneforBackupandtheotherforBackup2).SettingallthreerelayswiththesameONlevelwillhave
causetherelaystoall turnonatthe sametime.Examplebelowshowsthreerelays(A,
BandC)usedtoAuto
Emptyatank:
1. Makesureallthreerelaysareinthesamemode.Ifthisisnottrue,thenTRIPLXwillnotappear.
2. WhenMPLEXappears,pressSELECT.
3. WhenTRIPLXappears,pressSELECT.
4. SelectEXITtoreturntoTopLevelMenu.

20
CONFIGURATION(cont.) StepFive
HowtoturnoffMPLEX(DUPLEXorTRIPLEX).
1. WhenMPLEXappears,pressSELECT.
2. WhenNOALTappears,pressSELECT.
3. SelectEXITtoreturntoTopLevelMenu.
HowtoTimeAlternaterelays
This function is only operational when two or more relays are configured as pumps performing the same
function (either filling or emptying).This function is useful when a complete cycle of the pumps cannot be
guaranteedsuchasacontinuousinflowtoasump.Thusonepumpmayrunlongerthantheotherpump.To
insureequalwearofbothpumps,thealternatingcyclecanbesetupona timer.Thustheleadandlagpumps
willbeswitchedbasedontimeratherthanacyclebasis.
1. Makesureatleasttworelaysareinthesamemode.(ex:tworelaysaresetasPUMPsthatFILLor
threerelaysaresetasPUMPsthatEMPTY.Ifthisisnottrue,thenMPLEXwillnotappear.
2. WhenMPLEXappears,pressSELECT.
3. ChoosebetweenDUPLEXorTRIPLXandpressSELECT.
4. WhenATIMEappears,pressSELECT.
5. WhenHOURSappears,pressSELECT.
6. UsingtheUPandDOWNbuttons,settheAlternatingTimeinHours.AlternatingTimecanbesetfrom
0to600hours.
7. PressSELECTtoenterthevalue.
8. SelectEXITtoreturntoTopLevelMenu.

  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Omega LVCN1700 Series Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI