SBC Man Profibus DP Owner's manual

Type
Owner's manual
für PROFIBUS-DP
Manual
Document-No. 26-860 │ Version ENG02 │ 2019-01-31
PROFI
®
BUS
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Inhaltsverzeichnis
Contents
0-1
0
0. Table of contents
0.1 Document history .................................................................................. 0-3
0.2 Trademarks ........................................................................................... 0-3
1. Characteristics and fundamentals
1.1 Characteristics ...................................................................................... 1-1
1.2 Basic principles ..................................................................................... 1-4
1.2.1 ISO/OSI reference model ...................................................................... 1-4
1.2.2 PROFIBUS layer 1 (physical layer) ....................................................... 1-5
1.2.3 PROFIBUS layer 2 (data link layer) ...................................................... 1-6
1.2.4 PROFIBUS-DP ...................................................................................... 1-9
2. Modules for the PROFIBUS-DP network
2.1 PROFIBUS-DP master module for PCD1/2.Mxxx ................................. 2-1
2.2 PROFIBUS-DP slave module for PCD1/2.Mxxx ................................... 2-3
2.2.1 PROFIBUS-DP PCD7.F77x slave card ................................................. 2-3
2.3 Ports 2 and 3 of PCD7.F77x slave modules ......................................... 2-5
2.3.1 Port 2 ..................................................................................................... 2-5
2.3.2 Port 3 ..................................................................................................... 2-5
2.4 Connection of PROFIBUS-DP modules ............................................... 2-6
2.4.1 PCD7.F7XX module .............................................................................. 2-6
2.4.2 Meaning of connections: ....................................................................... 2-7
2.4.3 PROFIBUS DP master, PCD7.F750 module ......................................... 2-8
2.4.4 PROFIBUS DP slave, PCD7.F77x module ........................................... 2-10
2.5 PCD7.T160 termination box ................................................................. 2-12
2.5.1 DierencesbetweenthePCD7.T160,PCD7.T161
and PCD7.T162 devices ....................................................................... 2-12
2.6 PCD7.T161 termination box .................................................................. 2-13
2.6.1 Functional description ........................................................................... 2-13
2.6.2 Block diagram/connection diagram ....................................................... 2-13
2.6.3 Technical data ....................................................................................... 2-13
2.7 PCD7.T162 termination box .................................................................. 2-14
2.3.1 Functional description ........................................................................... 2-14
2.7.2 Block diagram/connection diagram ....................................................... 2-14
2.7.3 Technical data ....................................................................................... 2-14
2.8 PROFIBUS-DP for PCD3.Mxxxx ........................................................... 2-15
2.9 PROFIBUS-DP for PCD2.M5_ .............................................................. 2-17
2.9.1 PROFIBUS DP master, PCD7.F7500 module for PCD2.M5xxx .......... 2-17
3. Planning and installation of a PROFIBUS-DP network
3.1 Planning and installation of the physical layer ...................................... 3-2
3.1.1 Line parameters .................................................................................... 3-2
3.1.2 Connectionofnetworkstations ............................................................. 3-3
3.1.3 Stub cables ........................................................................................... 3-5
3.1.4 Networklayout ...................................................................................... 3-6
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Inhaltsverzeichnis
Contents
0-2
0
3.2 Logicalnetworkstructure ...................................................................... 3-8
3.2.1 Denitionofbusparameters ................................................................. 3-8
3.2.2 Congurationofslaves .......................................................................... 3-8
3.2.3 Checking and assessing the performance values required .................. 3-8
4. ThePROFIBUS-DPcongurator
4.1 General ................................................................................................. 4-1
4.2 ProcedureforPROFIBUS-DPconguration ......................................... 4-3
4.3 DescriptionofthePROFIBUS-DPconguratormenus ......................... 4-4
4.3.1 Main screen ........................................................................................... 4-4
4.3.2 ‘Network’submenu ................................................................................ 4-6
4.3.3 ‘Edit’submenu ....................................................................................... 4-7
4.3.4 ‘View’submenu ..................................................................................... 4-25
4.3.5 ‘Library’submenu .................................................................................. 4-26
4.3.6 ‘Project’submenu .................................................................................. 4-28
4.3.6 ‘Window’submenu ................................................................................ 4-28
4.3.8 ‘Help’submenu ...................................................................................... 4-29
4.3.9 Mouse-sensitiveelementsinthecongurator ...................................... 4-29
5. Programming
5.1 AccesstoslaveI/OsandregistersinaPCDuserprogramwithPROFIB-
US-DP ................................................................................................... 5-1
5.2 Description of the PCD commands (SASI, SCON) ............................... 5-4
5.2.1 SASI: Assigning a channel .................................................................... 5-4
5.2.2 SCONcommandstoaectdataexchange ........................................... 5-11
5.2.3 SCONIcommandstoaectdataexchange .......................................... 5-12
5.2.4 History message log .............................................................................. 5-27
5.3 Rulesforwritingtheuserprogram ........................................................ 5-28
5.4 Structure of the user program ............................................................... 5-29
5.4.1 Cold-start program in XOB 16 ............................................................... 5-29
5.4.2 Main program in COB ........................................................................... 5-29
6. Commissioning a PROFIBUS-DP network
6.1 Checkingandtestingthehardwareinstallation(physicallayer) ........... 6-1
6.2 Checking and testing data exchange .................................................... 6-2
6.2.1 Checking data exchange ....................................................................... 6-2
6.2.2 Checking the mapped media ................................................................ 6-4
6.2.3 Use of bus monitors .............................................................................. 6-5
A Appendix
A.1 Icons ...................................................................................................... A-1
A.2 Company address of Saia-Burgess Controls AG ................................. A-2
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Document versions | Brands and trademarks
Contents
0-3
0
0.1 Document history
Version Published Modied Comments
pEN1 2009-01-07 Completely Newedition,partlytakenfromHB26-765
pEN1 2009-06-25 Completely Revision
pEN01 2010-01-14 Completely Chapter numbering
EN01 2013-06-26
2013-08-07
Ch. 2.5
Completely
- PCD7.T161 and PCD7.T162 added
- Changed the Logo
ENG01 2019-01-31 Chapter A Newphonenumber(2015)
0.2 Trademarks
Saia PCD
®
is a registered trademark of Saia-Burgess Controls AG.
Technical changes are subject to the state of technology.
Saia-Burgess Controls AG, 2008. © All rights reserved.
PublishedinSwitzerland
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Characteristics
Characteristics and fundamentals
1-1
1
1. Characteristics and fundamentals
PROFIBUSisthesuccessful,open,industrialeldbusstandardforabroadappli-
cation spectrum.
1.1 Characteristics
Open
PROFIBUSenablestheexchangeofdatabetweendevicesfromdierentmanu-
facturers,withoutspecialinterfaceadjustments.PROFIBUShasbeenstandard-
ised under the stable German standard DIN 19 245 and European standard pr
EN 50 170.
Vendor-independent
PROFIBUSdevicesareoeredbymanyqualiedmanufacturers.Thisenables
the user to select the most suitable device from a preferred manufacturer for the
application in question.
Optimisedforawideeldofuse
PROFIBUScomprisesthefollowingthreeapplication-specicversions:
EN 50170 Volume 2
Device Profiles
Application Profiles
Process
Automation
PROFIBUS-PA
- Powering over the bus
- Intrinsic safety
Factory
Automation
PROFIBUS-DP
- Plug and play
- Efficient an cost effective
Fast
General Purpose
Automation
PROFIBUS-FMS
- Large variety of applications
- Multi-master communication
Universal Appication Oriented
PROFIBUS has been standardised under European standard EN 50170 and the
earlier German standard DIN 19245 parts 1 - 4.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Characteristics
Characteristics and fundamentals
1-2
1
PROFIBUS-FMS(FMS=FieldbusMessageSpecication)
Thisisthegeneralpurposesolutionforcommunicationstasksattheeldandcell
levelsoftheindustrialcommunicationshierarchy.PowerfulFMSservicesopenup
awiderangeofapplications,providegreatexibilityandenablecomprehensive
communicationtaskstobemanagedwithcyclicoracyclicdatacommunicationat
medium speed.
PROFIBUS-DP(DP=DecentralisedPeripherals)
Optimised for high speed, this PROFIBUS version has been especially tailored for
communicationbetweenautomationsystemsandlocalperipherals,enablingplug-
and-playforelddevices
PROFIBUS-FMS and PROFIBUS-DP use the same transmission technology and
the same bus access protocol. Both versions can therefore run simultaneously and
in combination on a single cable.
PROFIBUS-PA(PA=ProcessAutomation)
PROFIBUS-PA is the PROFIBUS version for process automation applications.
PROFIBUS-PAusestheintrinsicallysafetransmissiontechnologydenedinIEC
1158-2 and enables the remote supply of stations through the bus.
The protocol functions of PROFIBUS-FMS, PROFIBUS-DP and PROFIBUS-PA
arecomplementedbyproleswhichdescribehowPROFIBUSisusedinspecial
eldsofapplication,suchasprocessautomation,buildingcontroltechnologyor
automated production.
Deviceprolesdenedevice-specicfunctions.Thedevicedescriptionlanguage
(DDL) and function blocks ensure that devices are fully interoperable.
Transparent Communication from
Sensor/Actuator up to Area
CNC
VME/PC
PLC
DCS
Ethernet/TCP/IP TCP/IP/Ethernet
Factory
Level
Field-
Level
Cell
Level
Bus Cycle
Time
< 1000 ms
Bus Cycle
Time
< 100 ms
Bus Cycle
Time
< 10 ms
PROFIBUS-DP PROFIBUS-PA
PROFIBUS-FMS
PC/VME
Area
Controller
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Characteristics
Characteristics and fundamentals
1-3
1
Proven
PROFIBUSisacomplete,proventechnologywhichhasalreadystoodthetestof
morethan100,000applicationsintheeldsofbuildingautomation,automated
production, process automation and drive technology.
Certicated
Tests of conformity and interoperability performed in laboratories authorised by the
PROFIBUSuserorganisation(PNO),combinedwithPNOdevicecertication,give
the user an assurance of guaranteed quality and functionality, even in multi-vendor
installations.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-4
1
1.2 Basic principles
ToconstructaPROFIBUSnetworkandexchangedataoverit,itisnotimperative
toreadthroughandunderstandthefollowingchapterinfull.IfyouplanPROFI-
BUScommunicationwithSaiaPCDdevicesonly,thisinitselfisaverysimple
undertakingandyoucancontinuedirectlywithchapter2.
However,ifyouwouldalsoliketoimproveyourknowledgeandunderstandingof
PROFIBUStheory,youwillcertainlyndthefollowingchapteruseful.
1.2.1 ISO/OSI reference model
PA-Profiles
FMS
Device
Profiles
IEC Interface*
FMS
IEC 1158-2
User
Layer
(3)-(6)
Application
(7)
Data Link
(2)
Physical
(1)
not used
PA
DP
DP-Extensions
Fieldbus Data Link (FDL)
Fieldbus Message
Specification (FMS)
DP-Profiles
RS-485 / Fiber Optic
DP Basic Functions
EN 50 170 PROFIBUS profiles
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-5
1
1.2.2 PROFIBUSlayer1(physicallayer)
PROFIBUSprotocolarchitecturefollowstheISO/OSI(OpenSystemInterconnec-
tion)referencemodel,inlinewithinternationalstandardISO7498.
Inthismodeleachlayertakesonpreciselydenedtasks.Layer1(physicallayer)
denesthephysicaltransmissiontechnology.Layer2(datalinklayer)denesthe
busaccessprocedureLayer7(applicationlayer)denestheuserlevel.
Aeldbussystem’seldofuseisessentiallydeterminedbythechoiceoftrans-
mission medium and the physical bus interface. Apart from the requirements of
transmission security, expenditure on purchasing and installing the bus cable is
crucially important. The PROFIBUS standard therefore provides for various forms
oftransmissiontechnology,whileretainingauniformbusprotocol.
Cable-based transmission:ThisversioncomplieswithUSstandardEIARS-485
andwasdenedasthebasicversionforapplicationsintheeldofproduction
engineering, building control technology and drive technology. It uses a shielded,
twisted-paircoppercable.
Fibre-optic cable: For applications in very interference-prone environments, and
toextendworkingrangeathightransmissionspeeds,thePNOhasworkedouta
specicationforbre-opticbasedtransmissiontechnology.
Intrinsically safe transmission: PROFIBUS-PA enables the intrinsically safe
transmission and supply of stations via the bus. The transmission technology is
described in international standard IEC 1158-2.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-6
1
1.2.3 PROFIBUSlayer2(datalinklayer)
The second layer of the OSI reference model realises the functions of bus access
control, data protection and the transaction of transmission protocols and tele-
grams.InPROFIBUS,layer2iscalledtheeldbusdatalink(FDL).
Busaccesscontrol(mediumaccesscontrol,MAC)denestheprocedureforwhen
a station on the bus can transmit data. The MAC must ensure that, at any one
time, only one station ever has authorisation to transmit.
The PROFIBUS bus access method therefore includes a token passing proce-
dureforcommunicationbetweencomplexstations(masters)andanunderlying
master-slaveprocedureforthecommunicationofcomplexstationswithlow-ex-
pense peripheral devices (slaves). This combined procedure is called a hybrid bus
access procedure.
InPROFIBUS,thetoken-passingprocedureonlyappliesbetweencomplexsta-
tions (masters).
Themaster-slaveprocedureallowsthemaster(activestation)currentlyhold-
ing transmission authorisation to speak to its assigned slave devices (passive
stations). This gives the master the opportunity of transmitting messages to the
slaves or uploading messages from them.
WiththishybridaccessmethodforPROFIBUS,thefollowingsystemcongura-
tions can be realised:
●Straight master-slave system
●Straight master-master system (token passing)
●A system combining both methods
ThefollowinggureshowsaPROFIBUSstructurewiththreeactivestations(mas-
ters) and seven passive stations (slaves). The three master devices form a logical
token ring.
If an active station receives the token telegram, it can exercise for a certain time
thefunctionofmasteroverthebus,communicatingwithallslavestationsina
master-slaverelationshipandwithallmasterstationsinamaster-masterrelation-
ship.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-7
1
PROFIBUS
Passive Stationes, Slave Devices are polled
Active Stationes, Master Devices
PLC
PLC
PC
The term «token ring» refers to the organisational stringing together of active sta-
tionswhichformalogicalringbasedontheirbusaddresses.Inthisring,thetoken
(busaccessauthorisation)ispassedfromonemastertothenextinapredened
order (ascending addresses).
The task of the bus access controller (MAC) of the active stations is to recognise
thislogicalassignmentinthebussystem’s«run-upphase»andestablishthe
tokenring.Whileoperatingin«run»,any(active)stationwhichisfaultyorswitched
oisdisconnectedfromtheringandanynewlyaddedactivestationisconnected
toit.Theseperformancecharacteristics,togetherwiththerecognitionoffaultsin
the transmission medium, line receiver and errors relating to station addressing
(e.g. multiple occupation) or token passing (e.g. multiple tokens or token loss), are
typical features of PROFIBUS access control.
Another important task of layer 2 is data protection. The PROFIBUS layer 2 tele-
gram formats enable high transmission security. All telegrams have a Hamming
distance of HD = 4. This is achieved by application of the rules under international
standard IEC 870-5-1, selecting special start and end characters for telegrams,
slip-free synchronisation, parity bits and control bytes.
PROFIBUS-FMSandPROFIBUS-DPbothusetheirownspecicsubsetoflayer2
services(seetablebelow).Servicesarecalledfromhigher-rankinglayersviathe
service access points (SAPs) of level 2. With PROFIBUS-FMS these service ac-
cess points are used for addressing the logical communication relationships. With
PROFIBUS-DPapreciselydenedfunctionisassignedtoeachserviceaccess
point used. For all active and passive stations, several service access points can
beusedinparallel.Adierenceisdrawnbetweensource(SSAP)andreceiving
service access points (RSAP).
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-8
1
Services of the PROFIBUS data protection layer (layer 2).
Service Function Used with
SDA SendDatawithAcknowledge FMS
SRD SendAndRequestDataWithAcknowledge FMS→DP
SDN SendDataWithNoAcknowledge FMS→DP
CSRD CyclicSendAndRequestDataWithAcknowledge FMS
ThefollowingSAPsareoccupiedbyPROFIBUS-DPandcannotbeusedforFMS
inamixedFMS-DPnetwork:
Function SSAP DSAP Service
Data_Exchange Default Default SRD
Chk_Cfg 62 62 SRD
Set_Prm 62 61 SRD
Slave_Diag 62 60 SRD
Get_Cfg 62 59 SRD
Global_Control 62 58 SDN
RD_Outp 62 57 SRD
RD_Inp 62 56 SRD
Set_Slave_Add 62 55 SRD
Reserved 54
Reserved 53
Reserved 52
Reserved 51
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-9
1
1.2.4 PROFIBUS-DP
PROFIBUSlayer7(applicationlayer)
Layer 7 of the ISO/OSI reference model is not used in PROFIBUS-DP.
PROFIBUS-DP characteristics
ReplacescostlyparallelcablingbetweenPLC/PCandI/Os
Fast: transmits 1 kbyte of input and output data in less than 2 ms
Powerfultoolsreduceengineeringcosts
Supported by all main PLC manufacturers
Great diversity of products available,
e.g. PLCs/PCs, I/Os, drives, valves, encoders
Cyclic and acyclic data transmission possible
Monomasterandmultimasternetworkscanbecreated
Up to 246 bytes of input and output data possible per station
PROFIBUS-DP device types
PROFIBUS-DPdenesthreedevicetypes:
DPmasterclass1(DPM1)
CentralcontrolwhichexchangesdatawiththelocalI/Os(DPslaves)Several
DPM1sareallowed,typicaldevicesarePLCs,PCs,VMEs
DPmasterclass2(DPM2)
Projectplanning,monitoringorengineeringtoolwhichisusedforcommission-
ing or parameter setting/monitoring of DP slaves
DP slave
Localdevicewithdirectinterfacetoinput/outputsignals;typicaldevicesareI/
Os, drives, valves, control units, etc.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-10
1
PROFIBUS-DP systems
PROFIBUS-DP can operate either as a monomaster or multimaster system:
Monomaster system
DP - Slaves
SPS
Profibus DP
PROFIBUS-DP Monomaster System
Monomaster Systems reach the
shortest bus cycletime
They consist of:
- 1 DP-Master (Class 1)
- 1 to max. 125 DP-Slaves
- DP-Master (Class 2) - optional
DP-Master (Class 1)
Distributed inputs and outputs
PROFIBUS-DPusuallyworksasamonomastersystem.Thismeansthatamaster
device,e.g.aPLC,isnetworkedviaPROFIBUS-DPwithdistributedperipheral
devices, e.g. inputs and outputs. PROFIBUS-DP replaces the parallel cabling be-
tweenthePLCandlocalperipherals.
APROFIBUS-DPmonomastersystemconsistsofbetween1and125slaves,a
class1master(i.e.thePLC)andanoptionalclass2master(i.e.acongurator).
Monomastersystemsachievetheshortestbuscycletimes;theytransmit1kbyte
of input and output data in less than 2 ms.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-11
1
Multimaster system
PROFIBUS - DP
PC
PROFIBUS-DP Multimaster System
DP-Master
(Class 2)
DP-Master
(Class 1)
DP-Master
(Class 1)
PLC
CNC
Several DP-Masters may access a
DP-Slave with read functions
distributed inputs and outputs distributed inputs and outputs
PROFIBUS-DP Multi-Master systems consist of:
- multiple Masters (Class 1 or 2)
- 1 to max. 124 DP-Slaves
- max. 126 devices on the same bus
DP - Slaves
PROFIBUS-DPcanalsobeusedinamultimasterconguration.
Thegureshowstwoactivedevices,aPLCandaCNC.Eachstationhasas-
signed input and output devices.
The advantage of PROFIBUS-DP is that active devices can access the data of
jointlydeneddevices.
The DP class 2 master has the possibility of reading the diagnostic data of all de-
vices on the bus.
PROFIBUS-DP communication functions
PROFIBUS-DPcommunicationfunctionsaredierentiatedaccordingtothefollow-
ing communication relationships:
Class 1 master and DP slaves
Class 2 master and DP slaves
Class 2 master and class 1 master
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-12
1
Possible communication relationships:
Function DPM1DP
slaves
DPM2 DP
slaves
DPM1 DPM2
Parametersetting/conguration -
Transmission of slave diagnostic data -
Transmission of master diagnostic data - -
Cyclic data communications -
Sync + freeze commands -
Set slave address - -
Acyclic read of input/output images - -
Acyclicread/writeofdata
*)
*)
-
Alarm handling functions
*)
*)
-
Upload/downloadofmasterparameterrecords - -
*)
TheseextendedPROFIBUS-DPfunctionsarespeciedintechnicalinstructionno.2.082.
PROFIBUS-DPdoesnotsupportcommunicationbetweenseveralDPM1s.Ifthis
functionality is required, PROFIBUS-FMS should be used in addition.
TheextendedDPfunctionsaremainlyusedforintelligentslaveswithmanydif-
ferentparameterswhichhavetobemodiedduringoperation.Thenewreadand
writefunctionsweredenedforthispurpose.
ItisimportantthattheextendedDPprotocolisdownwardcompatiblewithbasic
DPfunctions.Thatmeansthatdevicesonwhichthenewfunctionshavebeen
implementedarefullyinteroperablewithdeviceslackingthisextendedfunction-
ality.Theonlyrestrictionisthatdeviceswhichlacktheextendedfunctionscannot
executethenewfunctions.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-13
1
PROFIBUS-DP data transmission
DatatransmissionwithPROFIBUS-DPisbasedonahighlyecienttelegram
structure.
SYN SD2 LE SD2 DA SA FC DU FCS EDLEr
SD2 LE LEr DA SA FC DU FCS EDSD2
Request Frame
Frames
SRD-Request, variable lenght of user data
SRD-Response, variable lenght of user data
DP-Slave
DP-Master
immediate
response
Syn = Synchronisation Time
SD2 = Start Delimitter 2
LE = Length
DU = Data Unit
FCS = Frame Check Sequence
ED = End Delimitter
LEr = repeated Length
DA = Destination Address
SA = Source Address
FC = Function Code
DP-Master
Header
Input-Data
Trailer
Trailer
Header
DP-Slave
SYN SD2 LE SD2 DA SA FC DU FCS EDLEr
SD2 LE LEr DA SA FC DU FCS EDSD2
Output-Data
PROFIBUS-DP
Principle of User Data Transfer
Response Frame
The input and output data of a device is transferred in a single bus cycle. The
mastersendsacallingtelegramwhichcontainsoutputdatafortheDPslave.Inits
reply telegram, the DP slave transmits its input data to the master. After receipt of
thecallingtelegram,theDPslaveanswersdirectly.Eachtelegramcantransmitup
to 244 bytes of input or output data.
If the calling or reply telegrams have been corrupted by electromagnetic interfer-
ence, the master immediately repeats the message cycle. The number of repeti-
tionscanbecongured.
AllPROFIBUStelegramshavehightransmissionsecuritywithaHammingdis-
tanceofHD=4.TheHammingdistanceisameasureofasystem’serrorpro-
tection. This means that the higher the Hamming distance, the better the system
security. HD = 4 meets the requirements for security-related applications.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-14
1
PROFIBUS-DP bus cycle time
The bus cycle time of a PROFIBUS-DP system depends mainly on the baud rate
used.Abaudrateofbetween9.6kbit/sand12Mbit/scanbeselectedinincre-
ments.
Conditions: Each DP-Slave has 2 byte input and 2 byte output data
The minimum Slave Interval time is 200 micro seconds
Tsdi = 37 Bit times, Tsdr = 11 Bit times
Typical Bus Cycle Time of a
PROFIBUS-DP Monomaster System
Bus cycle time
[ms]
DP-Slaves
12 MBit/s
1.5 MBit/s
500 kBit/s
Example:
Inasystemcongurationof30DPslavesworkingat12Mbit/s,andinwhicheach
slave has 2 bytes of input and output data, a bus cycle time of approx. 1 ms is
achieved.
ThisshowsthatPROFIBUS-DPcanbeusedeveninverytime-criticalapplications.
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
Basic principles
Characteristics and fundamentals
1-15
1
Project planning with PROFIBUS-DP bus cycle time
PROFIBUSnotonlydescribesthecommunicationofdeviceswitheachother;it
alsoprovidesaframeworkforopen,vendor-independentprojectplanning.
SPS
PROFIBUS-DP
Open Configuration permits Plug and Play
PROFIBUS
configuration tool
System configuration
Electronic Device Data Sheets (GSD-file)
Project planning tools, e.g. SNET, use electronic data sheets for the devices.
TheseelectronicdatasheetsarecalleddevicedatabaselesorGSD(General
StationDescription)les.Theselesareusuallysuppliedonadiskettewiththe
device.FormanyPROFIBUSdevices,theselescanalsobedownloadedfrom
the PROFIBUS homepage http://www.probus.com.
ManufacturersdescribethefunctionalityoftheirdeviceswiththehelpofaGSD
le.TheformatofGSDleshasaxeddenitionwithinthePROFIBUSstandard.
TheprojectplanningtoolreadstheGSDleintoitsinternaldatabaseandtakes
into consideration all the characteristics of the device in question.
Thissimpliesprojectplanningandcanbecarriedoutwithavendor-independent
project planning tool. PROFIBUS-DP therefore permits genuine plug-and-play
solutions and reduces engineering costs.
2. Modules for the PROFIBUS-DP network
2.1 PROFIBUS-DP master module for PCD1/2.Mxxx
PROFIBUS-DP PCD7.F750 master card
Dual port
RAM
Opto
RS
485
Driver
DC
+5V
S+5V
PCD
CPU
PCD7.F750
Siemens
ASPC2
µC
C165
RAM
Flash
Quarz
RUN
ERR
OR
LED
DP+5
V
PGN
D
DPGN
D
SGN
D
DC
Block diagram of PCD7.F750
Manual PROFIBUS DP │ Document-No. 26-860│ Version ENG 02│ 2019-01-31
Saia-Burgess Controls AG
PROFIBUS-DP master module for PCD1/2.Mxxx
Modules for the PROFIBUS-DP network
2-1
2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114