Altronix ALTV248UL3 Series CCTV Power Supplies Installation guide

Category
Electrical enclosures
Type
Installation guide

Altronix ALTV248UL3 Series CCTV Power Supplies provide distributed 24VAC or 28VAC power via eight (8) fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories. These power supplies are UL Listed for Commercial CCTV Equipment (UL 2044) and CUL Listed - CSA Standard C22.2 No.1-98. They feature surge suppression, an AC power LED indicator, a power ON/OFF switch (ALTV248UL3, ALTV248ULCB3), or an illuminated power disconnect circuit breaker with manual reset (all other models).

Altronix ALTV248UL3 Series CCTV Power Supplies provide distributed 24VAC or 28VAC power via eight (8) fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories. These power supplies are UL Listed for Commercial CCTV Equipment (UL 2044) and CUL Listed - CSA Standard C22.2 No.1-98. They feature surge suppression, an AC power LED indicator, a power ON/OFF switch (ALTV248UL3, ALTV248ULCB3), or an illuminated power disconnect circuit breaker with manual reset (all other models).

ALTV248UL3
- 24VAC @ 3.5A (85VA)
or 28VAC @ 3A (85VA).
- Eight (8) Fuse Protected Outputs.
ALTV248175UL3
- 24VAC @ 7A (175VA)
or 28VAC @ 6.25A (175VA).
- Eight (8) Fuse Protected Outputs.
ALTV248300UL3
- 24VAC @ 12.5A (300VA)
or 28VAC @ 10A (280VA).
- Eight (8) Fuse Protected Outputs.
ALTV248300ULM3
- 24VAC @ 12.5A (300VA)
or 28VAC @ 10A (280VA).
- Eight (8) Fuse Protected Outputs.
ALTV248600UL3
- 24VAC @ 25A (600VA)
or 28VAC @ 20A (560VA).
- Eight (8) Fuse Protected Outputs.
ALTV248ULCB3
- 24VAC @ 3.5A (85VA)
or 28VAC @ 3A (85VA).
- Eight (8) PTC Protected Outputs.
ALTV248175ULCB3
- 24VAC @ 7A (175VA)
or 28VAC @ 6.25A (175VA).
- Eight (8) PTC Protected Outputs.
ALTV248300ULCB3
- 24VAC @ 12.5A (300VA)
or 28VAC @ 10A (280VA).
- Eight (8) PTC Protected Outputs.
ALTV248300ULCBM3
- 24VAC @ 12.5A (300VA)
or 28VAC @ 10A (280VA).
- Eight (8) PTC Protected Outputs.
ALTV248600ULCB3
- 24VAC @ 25A (600VA)
or 28VAC @ 20A (560VA).
- Eight (8) PTC Protected Outputs.
Rev. 040506
More than just power.TM
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Installation Guide
ALTV248UL3 Series
CCTV Power Supplies with
Factory installed 3-wire line cord
Models Include:
- 2 - ALTV248UL3 Series Installation Guide
Agency Listings:
UL Listed for Commercial CCTV Equipment
(UL 2044).
CUL Listed - CSA Standard C22.2 No.1-98,
Audio, Video and Similar Equipment.
CE European Conformity.
Input:
• 115VAC, 50/60Hz.
Output:
• Eight (8) fuse or PTC protected outputs.
• 24VAC or 28VAC output
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Surge suppression.
Features:
AC power LED indicator.
Power ON/OFF switch
(ALTV248UL3, ALTV248ULCB3).
Illuminated power disconnect circuit breaker
with manual reset (all other models).
Features (cont’d):
Unit maintains camera synchronization.
Ease of installation saves time and eliminates
costly labor.
Spare fuses included (on fuse protected models).
Enclosure Dimensions (H x W x D):
• ALTV248UL3 and ALTV248ULCB3:
8.5” x 7.5” x 3.5”
(215.9mm x 190.5mm x 88.9mm)
ALTV248300ULM3 and ALTV248300ULCBM3:
8.5” x 7.5” x 3.875”
(215.9mm x 191mm x 98.4mm).
ALTV248175UL3, ALTV248175ULCB3,
ALTV248300UL3, and ALTV248300ULCB3:
12” x 7.5” x 4.5”
(304.8mm x 190.5mm x 114.3mm).
ALTV248600UL3 and ALTV248600ULCB3:
13.5” x 13” x 3.25”
(342.9mm x 330.2mm x 82.6mm).
Overview:
Altronix ALTV248UL3 Series CCTV Power Supplies provide 24VAC or 28VAC distributed via eight (8) fuse or PTC
protected outputs for powering CCTV cameras, heaters and other video accessories.
Eight (8) Output ALTV248UL3 Reference Chart:
Altronix
Model Number
Output Voltage
Total Output Current
(Power)
Number of Outputs
PTC Protected auto-
resettable Outputs
(Class 2 Rated power-
imited for Dry locations,
Class 3 for Wet locations)
Fuse Protected
Class 1 Outputs
Individual Output
Current (max per
output, not to exceed
total output current)
Fuse Ratings
Main Fuse Ratings
Primary In-line Fuse
Ratings
115VAC 60Hz
Input Current
Agency
Listings
ALTV248UL3 24VAC 3.5A 8 – P3.5A 3.5A 5A/
250V
3.5A/
250V 0.9A
28VAC 3A
ALTV248ULCB3 24VAC 3.5A 8P– 2.5A – 5A/
250V
3.5A/
250V 0.9A
28VAC 3A
ALTV248175UL3 24VAC 7A 8 – P3.5A 3.5A 10A/
250V
3.5A/
250V 1.76A
28VAC 6.25A
ALTV248175ULCB3 24VAC 7A 8P– 2.5A – 10A/
250V
3.5A/
250V 1.76A
28VAC 6.25A
ALTV248300UL3 24VAC 12.5A 8 – P3.5A 3.5A 15A/
32V – 2.7A
28VAC 10A
ALTV248300ULCB3 24VAC 12.5A 8P– 2.5A – 15A/
32V – 2.7A
28VAC 10A
ALTV248300ULM3 24VAC 12.5A 8 – P3.5A 3.5A 15A/
32V – 2.7A
28VAC 10A
ALTV248300ULCBM3 24VAC 12.5A 8P– 2.5A – 15A/
32V – 2.7A
28VAC 10A
ALTV248600UL3 24VAC 25A 8 – P3.5A 3.5A 15A/
32V – 5.4A
28VAC 20A
ALTV248600ULCB3 24VAC 25A 8P– 2.5A – 15A/
32V – 5.4A
28VAC 20A
Specifications:
ALTV248UL3 Series Installation Guide - 3 -
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all
local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in a desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 14-16). Secure enclosure to earth ground.
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL3 or
ALTV248ULCB3 (Fig. 1a, 2a, pg. 4, 5). Set power disconnect circuit breaker to OFF position for all
other models (Fig. 3a-10a, pg. 6-13).
3. All units are factory set for 24VAC operation.
For 28VAC operation adjust unit prior to mounting and applying power as follows:
Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and
the wire marked [24V] is connected to the terminal marked [S].
Note: ALTV248ULCB3 set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Connect AC power to the black and white flying leads of the transformer(s) (Fig. 1-10, pg. 4-13),
secure green lead to earth ground. Use 18 AWG or larger for all power connections.
Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided. Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL3 or
ALTV248ULCB3 (Fig. 1a, 2a, pg. 4, 5). Set power disconnect circuit breaker to RESET (ON) position
for all other models (Fig. 3a - 10a, pg. 6-13).
6. Measure output voltage before connecting devices. This helps avoid potential damage.
Terminals marked [1P] - [8P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL3 or
ALTV248ULCB3 (Fig. 1a, 2a, pg. 4, 5). Set power disconnect circuit breaker to OFF position for all
other models (Fig. 3a - 10a, pg. 6-10).
8. Connect devices to terminals marked [1P] - [1N] through [4P] - [4N] on PD4/PD4CB board (Fig. 9, 10,
pg. 12, 13) or terminals marked [1P] - [1N] through [8P] - [8N] on PD8/PD8CB board (Fig. 1-8, pg. 4-12),
carefully observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL3 or
ALTV248ULCB3 (Fig. 1a, 2a, pg. 4, 5). Set power disconnect circuit breaker to RESET (ON) position
for all other models (Fig. 3a - 10a , pg. 6-13).
10. Green LED will illuminate when power is present.
11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This
installation should be made by qualified service personnel and should conform to the National Electrical
Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains.
Replace fuses with the same type and rating (refer to Eight (8) Output ALTV248UL3 Reference Chart, pg. 2).
Terminal Identification:
PD4/PD4CB - Distribution Module
1P - 4P AC output.
1N - 4N AC output.
PD8/PD8CB - Distribution Module
1P - 8P AC output.
1N - 8N AC output.
- 4 - ALTV248UL3 Series Installation Guide
Primary
In-line
Fuse
XFMR
Green
Lead (ground)
Black Lead
White Lead
non power-
limited
Input 115VAC,
50/60Hz
Class 1 Outputs
24VAC or 28VAC Output 1
Follow same procedure
using terminals
2P & N through 8P & N
for outputs 2 through 8)
LED
INPUT
ON OFF MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
ON OFF
Fig. 1 - ALTV248UL3
Fig. 1a
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of
sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of impor-
tant operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
ALTV248UL3 Series Installation Guide - 5 -
Primary
In-line
Fuse
XFMR
Green
Lead (ground)
Black Lead
White Lead
non power-
limited
Input 115VAC,
50/60Hz
24VAC or 28VAC Output 1
Follow same procedure
using terminals
2P & N through 8P & N
for outputs 2 through 8)
ON OFF
LED
INPUT
ON OFF MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
PD8
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1
Fig. 2 - ALTV248ULCB3
Fig. 2a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
- 6 - ALTV248UL3 Series Installation Guide
Illuminated Power Disconnect
Circuit Breaker with manual reset
Class 1 Outputs
24VAC or 28VAC
Output 1
Follow same
procedure
using terminals
2P & N through
8P & N
for outputs 2
through 8)
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Black Lead
White
Lead
Input 115VAC,
50/60Hz
non power-
limited
Green
Lead (ground)
Fig. 3 - ALTV248175UL3
Fig. 3a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
ALTV248UL3 Series Installation Guide - 7 -
Illuminated Power Disconnect
Circuit Breaker with manual reset
24VAC or 28VAC
Output 1
Follow same
procedure
using terminals
2P & N through
8P & N
for outputs 2
through 8)
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Class 2 Not Wet/Class 3 Wet
Black Lead
White
Lead
Input 115VAC,
50/60Hz
non power-
limited
Green
Lead (ground)
Fig. 4 - ALTV248175ULCB3
Fig. 4a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
- 8 - ALTV248UL3 Series Installation Guide
Fig. 5 - ALTV248300UL3
Fig. 5a
Illuminated
Power Disconnect
Circuit Breaker
with manual reset
24VAC or 28VAC
Output 1
Follow same
procedure
using terminals
2P & N through
8P & N
for outputs 2
through 8)
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Class 1 Outputs
Green Lead
(ground)
White
Lead
Black
Lead
Input 115VAC,
50/60Hz
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
ALTV248UL3 Series Installation Guide - 9 -
Fig. 6 - ALTV248300ULCB3
Fig. 6a
Illuminated
Power Disconnect
Circuit Breaker
with manual reset
24VAC or 28VAC
Output 1
Follow same
procedure
using terminals
2P & N through
8P & N
for outputs 2
through 8)
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Class 2 Not Wet/Class 3 Wet
Green Lead
(ground)
White
Lead
Black
Lead
Input 115VAC,
50/60Hz
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
- 10 - ALTV248UL3 Series Installation Guide
Illuminated Power Disconnect
Circuit Breaker with manual reset
Black Lead
White Lead
Green Lead
(ground)
Input 115VAC,
50/60Hz
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Transformer
underneath
power
distribution
board
Fig. 7 - ALTV248300ULM3
Fig. 7a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
ALTV248UL3 Series Installation Guide - 11 -
Illuminated Power Disconnect
Circuit Breaker with manual reset
Black Lead
White Lead
Green Lead
(ground)
Input 115VAC,
50/60Hz
Transformer
underneath
power
distribution
board
LED
INPUT
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
1234 56 78
P
N
Fig. 8 - ALTV248300ULCBM3
Fig. 8a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
- 12 - ALTV248UL3 Series Installation Guide
Illuminated Power Disconnect
Circuit Breaker with manual reset
Green
Lead
(ground)
Black Lead
White
Lead
Input 115VAC,
50/60Hz
1P 1N 2P 2N 3P 3N 4P 4N
LED
3.5A 250V
3.5A 250V 3.5A 250V
NPS
MAIN FUSE
1P 1N 2P 2N 3P 3N 4P 4N
LED
3.5A 250V
3.5A 250V 3.5A 250V
NPS
MAIN FUSE
Class 1 Outputs
Class 1 Outputs
Fig. 9 - ALTV248600UL3
Fig. 9a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
ALTV248UL3 Series Installation Guide - 13 -
Illuminated Power Disconnect
Circuit Breaker with manual reset
Green
Lead
(ground)
Black Lead
White
Lead
Input 115VAC,
50/60Hz
1P 1N 2P 2N 3P 3N 4P 4N
LED
NPS
MAIN FUSE
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1
1P 1N 2P 2N 3P 3N 4P 4N
LED
NPS
MAIN FUSE
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1
Fig. 10 - ALTV248600ULCB3
Fig. 10a
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
Voltage Selection
Configuration
- 14 - ALTV248UL3 Series Installation Guide
7.25” (184.2mm)
3.625” (92mm)
1.25”
(31.8mm)
3.5” (88.9mm)
6.05” (153.7mm)
1.125”
(28.6mm)
1.125”
(28.6mm)
0.6” (15.2mm)0.6” (15.2mm)
0.6” (15.2mm)0.6” (15.2mm)
2” (50.8mm)2” (50.8mm)
8.125” (206.4mm)
1”
(25.4mm)
1”
(25.4mm)
1”
(25.4mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1”
(25.4mm)
1”
(25.4mm)
5.25” (133.35mm)
6.05” (153.7mm)
3.5” (88.9mm)
Enclosure Dimensions (H x W x D):
• ALTV248UL3
• ALTV248ULCB3
8.5” x 7.5” x 3.5”
(215.9mm x 190.5mm x 88.9mm)
Enclosure Dimensions (H x W x D):
• ALTV248300ULM3
• ALTV248300ULCBM3
8.5” x 7.5” x 3.875”
(215.9mm x 191mm x 98.4mm)
3.63” (92.2mm) 1.25” (31.75mm)
3.85” (97.79mm)
7.25” (184.15mm)
1.75” (44.45mm) 1” (25.4mm)
0.6” (15.24mm) 0.6” (15.24mm)
0.9” (22.86mm)
0.9” (22.86mm)
8.13” (206.5mm)
3.85” (97.79mm)
1.25” (31.75mm)
1” (25.4mm)
1” (25.4mm) 1” (25.4mm)
1” (25.4mm)
1” (25.4mm)
1.25” (31.75mm)
1” (25.4mm)
1.25” (31.75mm)
0.6” (15.24mm) 0.6” (15.24mm)
ALTV248UL3 Series Installation Guide - 15 -
4.5” (114.3mm)
7.5” (190.5mm)
7.5” (190.5mm)
0.5” (12.7mm)
1.11” (28.2mm)
1.11” (28.2mm)
0.5” (12.7mm)1.25”
(31.75mm)
1.25”
(31.75mm)
1.5”
(12.7mm)
1.5”
(12.7mm)
3.5” (88.9mm)
3.5” (88.9mm)
3.5” (88.9mm)
5.75” (146.1mm)
1” (25.4mm)
1.13”
(28.7mm)
5.88”
(149.4mm)
0.88”
(22.4mm)
0.88”
(22.4mm)
4.5” (114.3mm) 4.5” (114.3mm)
2.5” (63.5mm)
12” (304.8mm)
12” (304.8mm)
1” (25.4mm)
1”
(25.4mm)
Enclosure Dimensions (H x W x D):
• ALTV248175UL3 • ALTV248175ULCB3 • ALTV248300UL3 • ALTV248300ULCB3
12” x 7.5” x 4.5” (304.8mm x 190.5mm x 114.3mm)
- 16 - ALTV248UL3 Series Installation Guide
Enclosure Dimensions (H x W x D) for:
• ALTV248600UL3 • ALTV248600ULCB3
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
1.40”
(35.6mm)
1.40”
(35.6mm)
1.40”
(35.6mm)
4.85” (123.2mm) 4.85” (123.2mm)
3.25” (82.6mm)
0.75”
(19.1mm)
0.75”
(19.1mm)
11.0” (279.4mm)
12.5” (317.5mm)
1.20”
(30.5mm)
1.20”
(30.5mm)
0.9375” (23.8mm)
0.9375” (23.8mm)
5.10” (129.5mm)
1.40”
(35.6mm)
5.10” (129.5mm)
6.5625” (166.7mm)
3.25” (82.6mm)3.25” (82.6mm)
3.25” (82.6mm)
10.5” (266.7mm)
1.0”
(25.4mm)
1.0”
(25.4mm)
1.0” (25.4mm)
13.0” (330.2mm)
5.10” (129.5mm)
1.20”
(30.5mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIALTV248UL3 Series K30U MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Altronix ALTV248UL3 Series CCTV Power Supplies Installation guide

Category
Electrical enclosures
Type
Installation guide

Altronix ALTV248UL3 Series CCTV Power Supplies provide distributed 24VAC or 28VAC power via eight (8) fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories. These power supplies are UL Listed for Commercial CCTV Equipment (UL 2044) and CUL Listed - CSA Standard C22.2 No.1-98. They feature surge suppression, an AC power LED indicator, a power ON/OFF switch (ALTV248UL3, ALTV248ULCB3), or an illuminated power disconnect circuit breaker with manual reset (all other models).

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI