Legrand FSP-221B-S-L2-W Installation guide

Type
Installation guide
Wattstopper
®
Low Voltage, High/Low/Off,
PIR Fixture Integrated Outdoor Sensor In IP66 Enclosure
Basse Tension, Haut/Bas/Éteint
Luminaire avec détecteur IRP extérieur intégré dans un boitier IP66
Bajo Voltaje, Alto/Bajo/Apagado
Sensor exterior integrado del aplique PIR en gabinete IP66
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 22833 – 4/19 rev. 7
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: FSP-201B, FSP-201B-S, FSP-201B-D
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
SPECIFICATIONS
Voltage ...............................................................12–32 VDC
Current Consumption ................................. 15 mA maximum
Wiring .......................................................................22 AWG
Length .......... 36” (91.44cm), 30” (76.2cm) from nipple
Primary Voltage .................................. +VDC, Com, Ctrl
Control Output .................................. 100 mA maximum
Dimming Voltage .................Dim + (violet), Dim - (gray)
Operating Temperature ..........-40°F (-40°C) to 167°F (75°C)
Tightening Skirt/Nut Torque ................................25–30 in-lbs
Dimensions
Collar ......................................1.30” diameter (33.0mm)
Collar height ..........................................0.64” (16.3mm)
Body .... 5.7”L x 2.3”W x 3.5”H (145mm x 60mm x 90mm)
Weight ...............................................................2.8 oz (80 g)
Enclosure .................................................IP66 (NEMA STD)
Coverage
FSP-L2 Lens @ 8’ height ................. up to 44’ diameter
FSP-L3 Lens @ 20’ height ............... up to 40’ diameter
FSP-L7 Lens @ 40’ height ............. up to 100’ diameter
Adjustments and Features
High Mode .................................................0 V – 10 V
Low Mode ......................................... 0 V – 9.8 V, Off
Time Delay .................... 30 seconds, 1 min –3 0 min
Cut Off ............... Disable, 1 min – 59 min ,1 hr – 5 hr
Sensitivity .................On-Fix, Off-Fix, Low, Med, Max
Hold Off Setpoint ......................Auto, None, 1–250 fc
Ramp Up .............................. Disable, 1 sec – 60 sec
Fade Down ........................... Disable, 1 sec – 60 sec
Photocell Setpoint for On/Off .......................1–250 fc
Factory Defaults
High Mode .......................................................... 10 V
Low Mode ............................................................ 1 V
Time Delay ........................................................5 min
Cut Off ................................................................. 1 hr
Sensitivity ...........................................................Max
Hold Off Setpoint ...........................................Disable
Ramp Up ........................................................Disable
Fade Down .....................................................Disable
Photocell Setpoint for On/Off .........................Disable
DESCRIPTION AND OPERATION
The FSP-201B is an IP66 rated motion sensor that dims lighting from
high to low based on movement.
Three configurations are available. The FSP-201B mounts inside the
fixture and the PIR lens connects to the FSP-201B through a 1.30”
diameter hole in the bottom of the fixture. The FSP-201B-S mounts to
a fixture/enclosure with a 1/2” knock out, via a nipple on the back. The
FSP-201B-D has a drop mount nipple, for mounting on to a pole, or to
a fixture.
The sensor uses passive infrared (PIR) sensing technology that reacts to
changes in infrared energy (moving body heat) within the coverage area.
Once the sensor stops detecting movement and the time delay elapses,
lights will go from high to low mode and eventually to an OFF position if
it is desired. Sensors must directly “see” motion of a person or moving
object to detect them, so careful consideration must be given to sensor
luminaire placement and lens selection. Avoid placing the sensor where obstructions may block the sensors line of sight.
The FSP-201B operates at 12–32 VDC. It is designed to be installed in indoor and outdoor environments.
NOTE: When the FSP-201B is powered up the first time, it will use factory default parameters to operate. If adjustments are needed,
the FSIR-100 configuration tool must be used.
LENS OPTIONS
Several lenses are available for use with the FSP-201B. Lenses give coverage at mounting heights between 8’–40’ for applications such
as, offices, warehouses and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height.
A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the photocell
function of the sensor. Lens modules are IP-66 rated when combined with an FSP-201B sensor mounted to an outdoor rated fixture.
See the FSP-Lx Coverage Guide for more information.
IR Receiver
IR Transmitte
r
Light Sensor
Motion Indicator
Red LED
PIR Sensor
Sensor Protection Cap
NOTE: Remove Cap before use
2
There are three configurations of the sensor:
The FSP-201B mounts inside the fixture.
The FSP-201B-S mounts to a fixture or an enclosure with a 1/2”
knockout.
The FSP-201B-D mounts to a pole or fixture.
Mounting Inside the Fixture
1. Determine an appropriate mounting location inside the light fixture
minimizing the electric light contribution to the sensors photocell.
Allow a minimum distance of 0.2” (5.1mm) from the wiring end of the
sensor to the wall of the fixture.
2. Drill a hole 1.30” (33.0mm) in diameter through the sheet metal in the
bottom of the fixture.
3. Add the rubber gasket to the threaded collar, and install the sensor
face down, parallel to the mounting surface. Ensure the rubber gasket
touches the inside surface of the fixture. Install the tightening nut
securely against the fixture to a torque of 25–30 in-lbs to ensure IP
rating is maintained.
NOTE: An optional collar can be installed in place of the tightening nut on the FSP-201B. This collar is included with the
FSP-201B-S and FSP201B-D, as shown below.
Mounting to a Fixture/Enclosure–Straight Nipple
1. Determine an appropriate mounting location minimizing the electric light contribution
to the sensors photocell.
2. If there is no knockout, drill a hole 0.875” (22mm) in diameter through the sheet
metal in the fixture or enclosure.
3. Add the rubber gasket to the nipple, and install the sensor face down. Ensure the
rubber gasket touches the surface of the fixture. Install the nipple nut securely
against the fixture to a torque of 25–30 in-lbs to ensure IP rating is maintained.
Mounting to a Pole or Fixture–Drop Nipple
1. Determine an appropriate mounting location on the pole.
2. Drill a hole 0.875” (22mm) in diameter through the pole.
3. Add the rubber gasket to the nipple, and install the sensor face down. Ensure the
rubber gasket touches the surface of the fixture. If needed, add the nut between
the sensor body and the rubber gasket to ensure a secure fit. Install the nipple
nut securely against the fixture to a torque of 25–30 in-lbs to ensure IP rating is
maintained.
Completing the Installation
1. Align the locking features between the sensor and lens module and push the lens
module forward until the o-ring seals firmly. Turn the lens module clockwise to
ensure it locks in place.
2. Connect wires as shown in wiring diagram.
3. Restore power from the circuit breaker.
NOTE: The IP66 rating for this unit is based on proper installation as indicated above.
However, as Fixture housings may vary in thickness, material, and hole
dimensions to accommodate this unit, all precautions to maintain IP66 should be
considered with the combination and installation of the unit to the Fixture Housing.
This includes installation to an IP66 rated Fixture Housing and use of suitable
outdoor rated silicone seals or accessories.
Tightening Nut
(or Optional Collar)
Fixture
Wall
Lens Assembly
Outside
Fixture Wall
Inside Fixture
Wall
Mounting Within Fixture
Tightening Nut
(or Optional Collar)
Rubber
Gasket
Rubber
Gasket
12
NOTE: The Outside Fixture Wall thickness should be
no greater than 0.125” (3.18mm) for optimal
sensor mounting and security.
INSTALLATION
WARNING
TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR.
Straight Nipple Mount
Nipple
Rubber
Gaskets
Nipple
Nut
Drop Nipple Mount
Nipple
Nut
Nipple
Rubber
Gaskets
Drop Nipple Mount
Nipple
Rubber
Gaskets
Nipple
Nut
Nut
CAUTION
WATTSTOPPER RECOMMENDS ADDING A
20KA SURGE SUPPRESSOR TO PROTECT
THE FIXTURE, DRIVER AND FSP SENSOR.
3
WIRING
120 – 277 VAC (1
φ
), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
16A E-Ballast/CFL
1HP @ 120/240VAC
20A 120VAC Plug Load – Receptacle
Class 2 Output
24 VDC, 225 mA
BZ-200 Power Pack
UL 2043 Plenum Rated
16094r1
Appliance
Control
LISTED
88T9
Control
Common
+24VDC
Red
White
Neut.
Power Pack
Red
Black
Blue
Switch
Lighting
Load
Black
Any 3-Wire
24VDC
Sensor
Hot
Red
Ground
Green
Class 2
wiring only
+VDC (Red)
COM (Black)
CTRL (Blue)
Dim– (Gray)
Dim+ (V
iolet)
Non-Dimming
Ballast/Driver
Line (Black
)
Ground
(Green)
Neutral
(White)
www.legrand.us • 800.879.8585
120 – 277 VAC (1
φ
), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
16A E-Ballast/CFL
1HP @ 120/240VAC
20A 120VAC Plug Load – Receptacle
Class 2 Output
24 VDC, 225 mA
BZ-200 Power Pack
UL 2043 Plenum Rated
16094r1
Appliance
Control
LISTED
88T9
Control
Common
+24VDC
Red
White
Neut.
Power Pack
Red
Black
Blue
Switch
Lighting
Load
Black
Any 3-Wire
24VDC
Sensor
Hot
Red
Ground
Green
Class 2
wiring only
+VDC (Red)
COM (Black)
CTRL (Blue)
Neutral
(White)
Line (Black
)
Ground
(Green)
Dim– (Gray)
Dim+ (Violet)
Dimming
Ballast/Driver
www.legrand.us • 800.879.8585
+VDC Output (Red)
COM/GND (Black)
Neutral (White)
Line (Black)Ground (Green)
Dim– (Gray)
Dim+ (Violet)
Dim-to-Off
Ballast/Driver
(Blue)
Wiring with an
external DC
power supply
FSP-201B CONFIGURATION
The configuration process establishes the appropriate parameters for the FSP-201B
operation. This is done through the FSIR-100 configuration tool. If no configuration
steps are taken, the sensor will use its default parameter values.
USING THE FSIR-100 CONFIGURATION TOOL
The FSIR-100 Wireless IR Configuration Tool is a handheld tool for changing defaults
and testing of WattStopper FSP-201B. It provides wireless access to the FSP-201B
sensors for parameter changes and testing.
The FSIR-100 display shows menus and prompts to lead you through each process. The
navigation pad provides a simple way to navigate through the customization fields.
Within a certain mounting height of the sensor, the FSIR-100 allows modification of
the system without requiring ladders or tools; simply with a touch of a few buttons.
The FSIR-100 IR transceiver allows bi-directional communication between the
FSP-201B and the FSIR-100 configuration tool . Simple menu screens let you see
the current status of the sensor and make changes. It can change FSP-201B sensor
parameters such as high/low mode, sensitivity, time delay, cut off and more. With the
FSIR-100 you can also establish and store FSP-201B parameter profiles.
BATTERIES
The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA NiMH
batteries. The battery status displays in the upper right corner of the display. Three bars next to BAT=
indicates a full battery charge. A warning appears on the display when the battery level falls below a
minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off 10 minutes
after the last key press.
If communication is not successful, (if possible) move closer to the sensor.
If still not successful, there may be too much IR interference from other sources. Programming the unit
at night when there is no daylight available may be the only way to communicate with the sensor.
NAVIGATION
Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated by
flashing (alternates) between yellow text on black background and black text on yellow background.
Once active, use the Select button to move to a menu or function within the active field. Value
fields are used to adjust parameter settings. They are shown in “less-than/greater-than” symbols:
<value>. Once active, change them using(left) and(right) arrow keys. The right key increments and
the left key decrements a value. Selections wrap-around if you continue to press the key beyond
maximum or minimum values. Moving away from the value field overwrites the original value. The
Home button takes you to the main menu. The Back button can be thought of as an undo function.
It takes you back one screen. Changes that were in process prior to pressing the key are lost.
NOTE: When you change parameter values on the FSP-201B, you need wait about 3 minutes
before the new parameters are saved into the memory.
FSP-2X1
HBP-111
Home/Main
Menu
Up
Select
Down
Right/Next
Left
Back
Power
On/Off
BAT=
IR tx/rx
4
IR COMMUNICATION
IR communication can be affected by the mounting height of the sensor
and high ambient lighting such as direct daylight or electric light such as
floodlights, and some halogen, fluorescent lamps, LED’s.
When trying to communicate with the FSP-201B, be sure to be positioned
under the sensor without any obstructions. Every time the commissionng
tool establishes communication with the FSP-201B, the controlled load will
cycle.
TROUBLESHOOTING
Lights will not go to High Mode:
Check all wire connections and verify the load and the ground wires are tightly secured.
Make sure that the sensor is not obstructed.
Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensors view for that time period.
To quickly test the unit operation, enable test mode and move out of the sensors view. Lights should fade to low mode after 5
seconds.
If lights still do not fade to Low Mode, call 800.879.8585 for technical support
Lights will not turn OFF:
Cut Off time may be set to “Disable.”
Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor’s view for that time period when
the lights are in Low Mode.
To quickly test the unit operation, enable test mode and move out of the sensors view. Lights should fade to low mode after 5
seconds and then turn OFF (if cut off is enabled) after 10 sec.
If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached its Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached its Photocell Light Level setpoint.
There is no IR communication:
Perform a power cycle on the FSP-201B.
OPERATION DURING POWER-UP
The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm up time if
no motion is detected.
15'-32'
* Distance may vary depending on the lighting environment
15'-32'
5
ORDERING INFORMATION
Catalog # Description
FSP-201B Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enclosure
FSP-201B-S Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enclosure, with Straight Nipple Mount
FSP-201B-D Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enclosure, with Drop Nipple Mount
FSIR-100 Configuration Tool
FSP-L2 360° lens, up to 44’ diameter at 8’ height
FSP-L2-S 360° lens, up to 44’ diameter at 8’ height, with shroud
FSP-L3 360° lens, up to 40’ diameter at 20’ height
FSP-L3-S 360° lens, up to 40’ diameter at 20’ height, with shroud
FSP-L7 360° lens, up to 100’ diameter at 40’ height
FSP-L7-S 360° lens, up to 100’ diameter at 40’ height, with shroud
FSP-C1 Small collar, for use with FSP-L2 and FSP-L3 lenses
FSP-C2 Large collar, for use with FSP-L7 lens
BZ-50 Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent
BZ-150 Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent, with Hold-On and Hold-Off
capability
BZ-200 Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/
CFL/Plug Load
BZ-250 Power Pack: 120/277VAC, 50/60 Hz, 20A, Ballast/ELV/MLV/Incandescent/LED, 16A E-Ballast/
CFL/Plug Load,
with Hold-On/Hold-Off capability
BZ-250-347 Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL,
15A Plug Load,
with Hold-On/Hold-Off capability
Sensor colors indicated by one of the following suffixes at the end of the catalog #:
-W = White; -BL = Black; -BR = Bronze/Brown; -G = Gray/Silver
800.879.8585
www.legrand.us/wattstopper
No. 22833 – 4/19 rev. 7
© Copyright 2019 Legrand All Rights Reserved.
© Copyright 2019 Tous droits réservés Legrand.
© Copyright 2019 Legrand Todos los derechos reservados.
WattStopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of WattStopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
WattStopper garantit que ses produits sont
exempts de défauts de matériaux et de
fabrication pour une période de cinq (5) ans.
WattStopper ne peut être tenu responsable de
tout dommage consécutif causé par ou lié à
l’utilisation ou à la performance de ce produit
ou tout autre dommage indirect lié à la perte de
propriété, de revenus, ou de profits, ou aux coûts
d’enlèvement, d’installation ou de réinstallation.
WattStopper garantiza que sus productos están
libres de defectos en materiales y mano de obra
por un período de cinco (5) años. No existen
obligaciones ni responsabilidades por parte de
Legrand/WattStopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida de
propiedad, renta o ganancias, o al costo de
extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Legrand FSP-221B-S-L2-W Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI