Secutron MR-2300 series Operating instructions

Category
Fire protection
Type
Operating instructions
Installation and Operation Manual
LT-906SEC Rev. 3.2
January 2020
MR-2300 Series
LCD Fire Alarm Control Panel
3
Contents
1.0 Industry Canada and FCC Notice 9
1.1 Notice for all MR-2300 Series Built-In UDACTs Sold in Canada ................................... 9
2.0 Introduction 11
2.1 Overall Features ............................................................................................................ 11
3.0 Conventions 12
3.1 Circuits ........................................................................................................................... 12
3.2 Zone ............................................................................................................................... 12
3.3 Events ............................................................................................................................ 12
3.4 Wiring Styles .................................................................................................................. 12
4.0 System Components, Sub-Assemblies & Accessories 13
4.1 Main Fire Control Panel ................................................................................................. 13
4.2 Relay Module: 12 Relays ............................................................................................... 14
4.3 Relay Modules: Six Relays ............................................................................................ 14
4.4 Polarity reversal/city tie .................................................................................................. 14
4.5 Remote Annunciator ...................................................................................................... 14
4.6 Smart Relay Module ...................................................................................................... 15
4.7 Input Class A converter: Six Circuits .............................................................................. 15
4.8 Output Class A converter: four circuits .......................................................................... 15
4.9 Output Class A converter: two circuits ........................................................................... 15
4.10 Active end-of-line ........................................................................................................... 16
4.11 MR-2312-AT Remote Annunciator ................................................................................. 16
4.12 Additional Fire Alarm System Accessories .................................................................... 16
5.0 Mechanical Installation 17
5.1 Installing the Enclosure .................................................................................................. 17
5.2 MMX-BBX-1024DS and MMX-BBX-1024DSR Mechanical Installation ......................... 20
5.3 Installing the Adder Modules .......................................................................................... 21
6.0 DIP Switch and Jumper Selections for Main Board and
Adder Modules 23
6.1 Main Fire Alarm Board ................................................................................................... 23
6.2 MR-2300-A Input Class-A Converter Adder Module ...................................................... 25
4
Contents
6.3 MR-2300-NC4/2 Output Class-A Converter Adder Module ........................................... 26
6.4 Relay Adder Modules (Models MR-2312-R12 and MR-2306-R6) .................................. 26
6.5 MR-2306-R6 Six Relay Adder Module .......................................................................... 27
6.6 Polarity Reversal and City Tie Module (Model MR-2300-PR) ........................................ 28
7.0 Field wiring 29
7.1 Main Fire Alarm Board Field Wiring ............................................................................... 29
7.2 Relay Adder Module Wiring .......................................................................................... 33
7.4 Polarity Reversal and City Tie Module (MR-2300-PR) Wiring ....................................... 35
7.5 Power supply connection ............................................................................................... 35
7.6 Wiring Tables and Information ...................................................................................... 37
7.7 Four-Wire Smoke Power (regulated) ............................................................................. 37
7.8 Supervised Auxiliary Power (regulated) ......................................................................... 38
7.9 Auxiliary Power (unregulated) ........................................................................................ 38
8.0 Turning on the Panel 39
8.1 Before Connecting the Power ........................................................................................ 39
8.2 Connecting the Power .................................................................................................... 39
8.3 Troubleshooting ............................................................................................................. 41
9.0 Indicators, Controls and Operations 42
9.1 Common Indicators ........................................................................................................ 43
9.2 Common Controls .......................................................................................................... 44
9.3 Common Relays ............................................................................................................. 45
9.4 Circuit Types .................................................................................................................. 46
9.5 Evacuation codes ........................................................................................................... 48
9.6 Fire Alarm Operation ...................................................................................................... 49
10.0 Supported Protocols/Devices 50
10.1 Synchronous Strobes ..................................................................................................... 50
10.2 Signal silence on strobes ............................................................................................... 50
10.3 System Sensor’s i3 Devices ........................................................................................... 50
11.0 Configuration 53
11.2 Command Menu ............................................................................................................. 54
11.3 Panel Config (Command-Menu) .................................................................................... 56
11.4 Config Info (Command-Menu) ........................................................................................ 64
11.5 Set Time (Command-Menu) ........................................................................................... 65
11.6 Set Password (Command-Menu) ................................................................................... 66
5
Contents
11.7 View Event Log (Command-Menu) ................................................................................ 66
11.8 Clear Event Log (Command-Menu) ............................................................................... 67
11.9 Walk Test (Command-Menu) ......................................................................................... 67
11.10 8. i3 Loop Test (Command-Menu) ................................................................................. 68
11.11 Dialer Config (Command-Menu) .................................................................................... 70
11.12 Test Dialer (Command-Menu) ....................................................................................... 76
11.13 Bypass Det Ckt (Command-Menu) ................................................................................ 78
11.14 Bypass NAC Ckt (Command-Menu) .............................................................................. 78
11.15 Aux. Disconnect (Command-Menu) ............................................................................... 79
11.16 Exit (Command-Menu) ................................................................................................... 79
12.0 Appendix A: Compatible Receivers 85
13.0 Appendix B: Reporting 86
13.1 Ademco Contact-ID ........................................................................................................ 86
13.2 Security Industries Association SIA-DCS ...................................................................... 87
14.0 Appendix C: Specifications 88
15.0 Appendix D: Power Supply and Battery Calculations
(Selection Guide) 91
16.0 Warranty and Warning Information 93
6
List of Figures
Figure 1 Box dimensions, surface mount ..................................................................................... 17
Figure 2 MR-2312-DDR Box dimensions, semi-flush mounting with trim ring ............................. 18
Figure 3 Flush Trim Detail\ ........................................................................................................... 18
Figure 4 MR-2306-DDR/MR-2306-DR Box dimensions, mounting and trim ring ......................... 19
Figure 5 MMX-BBX-1024DS and MMX-BBX-1024DSR Installation Instructions and Dimensions 20
Figure 6 Installation of Adder Modules for MR-2312 LCD Panels ................................................ 21
Figure 7 Installation of Adder Modules for MR-2306 LCD Panels ................................................ 22
Figure 8 Main Fire Alarm Board DIP switch and jumper settings for MR-2312 LCD Panels ........ 23
Figure 9 Main Fire Alarm Board DIP switch and jumper settings for MR-2300 LCD Panels ........ 24
Figure 10 MR-2300-A Input Class-A Converter Adder Module ...................................................... 25
Figure 11 MR-2300-NC4/2 Output Class-A Converter Adder Module ........................................... 26
Figure 12 MR-2312-R12 twelve relay adder module ...................................................................... 26
Figure 13 MR-2312/06-R12/6 Relay programming ........................................................................ 27
Figure 14 MR-2306-R6 six relay adder module ............................................................................. 27
Figure 15 Polarity reversal and city tie module .............................................................................. 28
Figure 16 Initiating circuit – Class B or Style B wiring .................................................................... 29
Figure 17 Initiating circuit– Class A or Style D wiring ..................................................................... 30
Figure 18 Indicating circuit – Class B or Style Y wiring .................................................................. 31
Figure 19 Indicating circuit – Class A or Style Z wiring .................................................................. 31
Figure 20 Four-wire smoke detector wiring .................................................................................... 32
Figure 21 Dialer wiring ................................................................................................................... 32
Figure 22 Relay per zone (MR-2312-R12) Terminal connection .................................................... 33
Figure 23 Relay per zone (MR-2306-R6) Terminal connection ...................................................... 33
Figure 24 Connecting an FACP to a 3G4010CF Interface Device ................................................. 34
Figure 25 Polarity reversal and city tie module terminal connection .............................................. 35
Figure 26 Power supply connection ............................................................................................... 36
Figure 27 Power supply connection ............................................................................................... 40
Figure 28 LCD Display and control buttons .................................................................................... 42
Figure 29 Evacuation Codes .......................................................................................................... 48
Figure 30 MR-2300 Configuration .................................................................................................. 53
Figure 31 Enter passcode .............................................................................................................. 54
Figure 32 Command Menu ............................................................................................................. 55
Figure 33 MR-2300 Config menu ................................................................................................... 56
Figure 34 Feature Config menu ..................................................................................................... 56
Figure 35 The event log ................................................................................................................. 66
Figure 36 Walk test confirmation .................................................................................................... 67
Figure 37 Walk test zones .............................................................................................................. 68
Figure 38 Walk test active .............................................................................................................. 68
Figure 39 i3 loop test confirmation ................................................................................................. 69
Figure 40 i3 test zones ................................................................................................................... 69
Figure 41 i3 test not ready .............................................................................................................. 69
Figure 42 The selected zone is not i3 type ..................................................................................... 69
Figure 43 Dialer Config menu ........................................................................................................ 70
7
List of Figures
Figure 44 Account info menu ......................................................................................................... 70
Figure 45 Telephone Line menu .................................................................................................... 72
Figure 46 Report Options menu ..................................................................................................... 73
Figure 47 Time Parameters ........................................................................................................... 74
Figure 48 Detection circuit message .............................................................................................. 80
Figure 49 Indicating circuit message .............................................................................................. 80
Figure 50 AC Power Fail message ................................................................................................ 81
Figure 51 Battery trouble message ................................................................................................ 81
Figure 52 Ground Fault message .................................................................................................. 82
Figure 53 Remote Annunciator message ....................................................................................... 82
Figure 54 Four-wire smoke detector supply message ................................................................... 83
Figure 55 Supervised auxiliary supply message ............................................................................ 83
Figure 56 Module missing message .............................................................................................. 84
Figure 57 Module trouble message ................................................................................................ 84
8
List of Tables
Table 1 Connectors and Jumpers on the Main Fire Alarm Board ............................................... 24
Table 2 Jumpers on the Core Board ........................................................................................... 25
Table 3 MR-2300-PR jumper settings ......................................................................................... 28
Table 4 Power Supply Ratings .................................................................................................... 35
Table 5 Initiating Circuit Wiring ................................................................................................... 37
Table 6 Indicating Circuit Wiring ................................................................................................. 37
Table 7 Troubleshooting ............................................................................................................. 41
Table 8 i3 Detector Status ........................................................................................................... 52
Table 9 Feature Config Menu ..................................................................................................... 57
Table 10 i3 Detector LEDs while in test mode .............................................................................. 69
Table 11 Auto Test Time and Cellular Report Date ...................................................................... 75
Table 12 MR-2300 LCD Series Specifications .............................................................................. 88
Table 13 FA-300 LCD System Modules and Annunciators ........................................................... 89
9
1.0 Industry Canada and FCC Notice
1.1 Notice for all MR-2300 Series Built-In UDACTs Sold in Canada
Secutron's MR-2300 SERIES BUILT-IN UDACT Communicator described in this manual is
listed by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction
with a Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units
for Fire Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling
Systems and Services). These Communicators should be installed in accordance with this
manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having
Jurisdiction (AHJ).
1.1.1 Industry Canada Notice
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
1.1.2 Notice for all MR-2300 Series Built-in UDACTs Sold in the U.S.A.
Secutron's MR-2300 SERIES BUILT-IN UDACT Digital Communicator described in this
manual is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in
conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire
Protective Signalling Systems). These Communicators comply with the National Fire
Protection Association (NFPA) performance requirements for DACTs and should be installed
in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
Caution: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate.
Note: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a
decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is
separately shown on the label.
!
i
10
Industry Canada and FCC Notice
1.1.3 FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request
information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number and the
ringer equivalence number (REN); both of these items are listed on the equipment label. The
sum of all of the REN’s on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Secutron
Fire Alarm System’s or an authorized representative of Secutron Fire Alarm System. For
information contact Secutron Fire Alarm System at the address and phone numbers shown on
the back page of this document.
11
2.0 Introduction
Secutron's MR-2300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP)
based fire panel. The MR-2300 provides a maximum of 12 supervised Class B or A (Style B or
D) Initiating circuits, and maximum of four supervised Class B or A (Style Y or Z) indicating
circuits. All circuits are supervised for opens and ground faults, and indicating circuits are
supervised for shorts. Optional modules include Relay, Polarity Reversal and City Tie and
Class A Converters for initiating and indicating circuits. Semi-flush or surface mountable
enclosures can be used for retrofits and on new installations.
2.1 Overall Features
Basic unit has six Class B (Style B) initiating circuits, which may be configured as Class
A (Style D) using input Class A converter adder module. Each initiating circuit can be
configured as Alarm, Verified Alarm, Water flow Alarm, Sprinkler Alarm, Latching or
Non-Latching Supervisory, Monitor or Trouble-Only circuits.
Basic unit has two Power Limited Class B (Style Y) indicating circuits. Each indicating
circuit may be configured as Class A (Style Z) using output Class A converter adder
module. Each indicating circuit may be configured as Silenceable signal, non
Silenceable signal, Silenceable strobe, non Silenceable strobe. The audible signal may
be Steady, Temporal Code, California Code, or March Time.
Each initiating and indicating circuit can be individually disconnected via the keypad and
LCD display with Password Access.
Configurable Signal Silence Inhibit, Auto Signal Silence, and One-Man Walk Test.
Four-wire resettable smoke power supply 300mA maximum.
Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnect-able and Auxiliary Alarm Relay (disconnectable).
RS-485 Interface for MR-2300 Series Remote Multiplex Annunciators, LCD
Annunciators and Smart relay adder.
Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
Extensive transient protection.
With or without built-in UDACT (Digital Alarm Communicator Transmitter).
Easy configuration of the panel using front LCD display and keypad.
Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
Laptop programmer for direct configuration changing and log checking.
Note: Installation of the MR-2300 series fire alarm control panel should be in
accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire
Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final
acceptance subject to the Local Authority Having Jurisdiction (AHJ).
i
12
3.0 Conventions
3.1 Circuits
Refers to an actual electrical interface for Initiating (Detection) and Indicating (Signal) or
Relays.
3.2 Zone
Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.
Often the terms Zone and Circuit are used interchangeably, but in this Manual the term Circuit
is used.
3.3 Events
There are events associated with every initiating, indicating and common circuit of the fire
panel displayed via the LCD.
3.4 Wiring Styles
Initiating and indicating circuits are Class B (Style B and Y). Changing the initiating circuits to
Class A requires an MR-2300-A adder board which will convert SIX initiating zones from Class
B (Style B) circuits to Class A (Style D). This is done without penalizing the number of circuits,
which remains the same as in Class B (Style B). Changing the indicating circuits to Class A
requires an MR-2300-NC4 adder board which will convert FOUR indicating zones from Class
B (Style Y) circuits to Class A (Style Z) or an MR-2300-NC2 adder board which will convert
TWO indicating zones from Class B (Style Y) circuits to Class A (Style Z).
13
4.0 System Components, Sub-
Assemblies & Accessories
4.1 Main Fire Control Panel
Model Description
MR-2312-DDR
Twelve-Zone Fire Alarm Control Panel with
LCD display and dialer (red door, black box).
12 Class B (Style B) Initiating circuits, and four
Power Limited Class B (Style Y) Indicating
circuits (up to 1.70 amperes each, 5 amperes
total). Two six zone MR-2300-A Input Class
A Converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
One MR-2300-NC4 Output Class A
Converter adder module may be used for
Class A (Style Z) wiring of the Indicating
circuits. The MR-2312-DDR contains
Common Alarm, Common Supervisory &
Common Trouble Relays, auxiliary alarm relay
(disconnectable), an RS-485 Interface for
Remote Annunciators and a Resettable Four
Wire Smoke Detector Power Supply. The unit
has a dialer on the main board. Used with BA-
110 (10 ampere-hour) (Sota Enertech model
SA12120) batteries (two are required).
MR-2306-DDR
Six-Zone Fire Alarm Control Panel with LED
display and dialer (Red enclosure). Six Class
B (Style B) Initiating circuits, and two Power
Limited Class B (Style Y) Indicating circuits
(up to1.70 amperes each, 5 amperes total).
One six zone MR-2300-A Input Class A
converter adder module may be used for
Class A (Style D) wiring of Initiating circuits.
One MR-2300-NC2 Output Class A
Converter adder module may be used for
Class A (Style Z) wiring of the Indicating
circuits. The MR-2306-DDR contains
Common Alarm, Common Supervisory &
Common Trouble Relays, auxiliary alarm relay
(disconnectable), an RS-485 Interface for
Remote Annunciators and a Resettable Four
Wire Smoke Detector Power Supply. The unit
has a dialer on main board. Used with BA-110
(10 ampere-hour) (Sota Enertech model
SA12120) batteries (two required).
MR-2306-DR
Same as the MR-2306-DDR except without
dialer.
14
System Components, Sub-Assemblies & Accessories
4.2 Relay Module: 12 Relays
4.3 Relay Modules: Six Relays
4.4 Polarity reversal/city tie
4.5 Remote Annunciator
Model Description
MR-2312-R12
Twelve-relay
adder module
Model Description
MR-2306-R6
Six-relay adder
module
Model Description
MR-2300-PR
Polarity Reversal
and/or City tie
Module
Model Description
MR-2300-LCDR
Remote Annunciator Module, LCD display, red
enclosure
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4
C
RELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8
C
RELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NC NO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4
C
RELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW1
JW2
JW4
MR-2300 SERIES
Remote Annunciator
SYSTEM
RESET
SIGNAL
SILENCE
FIR E
DRILL
BUZZER
SILENCE
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
ME NU
CANCEL
INFO
ABC DEF
GHI JK L MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
7.2"
7.7"
1.25"
15
System Components, Sub-Assemblies & Accessories
4.6 Smart Relay Module
4.7 Input Class A converter: Six Circuits
4.8 Output Class A converter: four circuits
4.9 Output Class A converter: two circuits
Model Description
MR-2312-SR12/
MR-2312-SW12
Smart Relay Module (12 relays) with red or white
enclosure
Model Description
MR-2300-A
Input Class A converter Module (six circuits). This
module has built in Active End-of-Line resistors
Model Description
MR-2300-NC4 Output Class A converter module (four circuits)
Model Description
MR-2300-NC2 Output Class A converter module (two circuits)
MR-2300 SERIES REMOTE RELAY
BLK RED
BLK RE DBLK REDBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- DET6 OUT+
- DET1 RET+- DET2 RET +- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RET+
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET +- SIG2 RET +
BLK RED
BLK RED
16
System Components, Sub-Assemblies & Accessories
4.10 Active end-of-line
The MR-2300-X are power-saving End-of-Line resistors that eliminate the need for an
additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
4.11 MR-2312-AT Remote Annunciator
4.12 Additional Fire Alarm System Accessories
Model Description
MR-2300-X Active end-of-line resistor without plate
Model Description
MR-2312-ATW/
MR-2312-ATR
16 Zone remote annunciator
MR-2306-ATW/R Eight Zone Remote Annunciator ULC and ULI Approved
MR-2605-T Remote Trouble Indicator ULC and ULI Approved
BLACK
RED
A.C.
ON
COMMON
TROUBLE
SIGNA L
SILEBCE
BUZZER
SILENCE
SIGNA L
SILENCE
LAMP
TEST
SYSTEM
RESET
SWITCH
ENABLE
FIRE ALARM
ANNUNCIATOR
17
5.0 Mechanical Installation
5.1 Installing the Enclosure
Install the MR-2300 Series Fire Alarm Panel enclosure as shown below for the twelve zone
models. Mount enclosure surface mount using the four mounting holes, as shown and the
screws provided. The backbox may be semi-flush mounted using the trim ring model MR-
2312-FT (BLACK), see Figure 2. Remove the door (also disconnect the ground strap), the
dead front (if supplied) and mount the backbox in between the studs. Place the trim ring
around the backbox. The trim ring is glued in place to the wall surface, after the wall is
finished. Replace the front door and ground strap.
Figure 1 Box dimensions, surface mount
11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole
18
Mechanical Installation
Figure 2 MR-2312-DDR Box dimensions, semi-flush mounting with trim ring
Figure 3 Flush Trim Detail\
The figure below shoes a cross-section of the semi-flush mounted backbox and the trim ring. Make sure to allow
a minimum depth of 1” above the wall surface for proper door opening.
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" is the maximum
depth for semi-flush
mounting using the
flush trim ring
1" is the minimum depth
above the wall required for
semi-flush mounting using the
flush trim ring
17"
28.5"
Adhere trim ring to
wall surface around
MR-2306 backbox.
PLACE MR-2312-FT TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL STUD
BACKBOX
19
Mechanical Installation
Figure 4 MR-2306-DDR/MR-2306-DR Box dimensions, mounting and trim ring
17"
22.5"
Adhere trim ring to
wall surface around
the MR-2306 backbox.
PLACE MR-2306-FT TRIM RING OVER BACKBOX
14.5"
4
.
5
"
11"
20.0"
1.5"
5.425"
14.5"
3.5"
1"
3.5" is the maximum depth
for semi-flush mounting
using the flush trim ring
1" is the minimum depth
above the wall required
for semi-flush mounting
using the flush trim ring
4 Mounting
Holes for
Surface
Mounting
20
Mechanical Installation
5.2 MMX-BBX-1024DS and MMX-BBX-1024DSR Mechanical
Installation
The MMX-BBX-1024DS and MMX-BBX-1024DSR are suitable for flush or surface mounting,
and have a built-in trim ring.
Figure 5 MMX-BBX-1024DS and MMX-BBX-1024DSR Installation Instructions and
Dimensions
Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26”
Distance between horizontal mounting screws 12”
Distance between vertical mounting screws 23.5”
Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
26.0 "
14.5 "
4.2 "
External Dimensions
12.0 "
23.5 "
Mounting Dimensions
2.1 "
1.3 "
6.0 "
9.5 "
Side View
1.3 "
1.7 "
2.0 "
Top View
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Secutron MR-2300 series Operating instructions

Category
Fire protection
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI