65821003 / 40228K016Issue 1810Page 2 of 6
Installation
WARNING
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualied service personnel should install or service
this equipment. Installation and service performed by
unqualied persons can result in property damage,
personal injury, or death.
General
Evaporator coils are designed for use with AC condensing
units or heat pump units. These instructions are intended
as a general guide and do not supersede local codes in
any way. Consult with local authorities having jurisdiction
before installation. This installation must comply with all
local and state laws as well as national electrical codes for
the U.S. or Canada where applicable.
Verify the efciency performance requirements, such
as SEER, EER, and/or HSPF, are appropriate with the
matched condensing or heat pump units. Check outdoor
unit manufacturer for proper line sizing.
WARNING
Coils are shipped with a 10 psi dry air holding charge.
Puncture rubber plug on suction line to release charge
before removing plugs. The absence of pressure does
not verify a leak. Check the coil for leaks before installing
or returning it to your wholesaler.
Inspection of Shipment
Before installation, inspect the coil for any shipping
damage. Notify the carrier or the distributor of any damaged
equipment; do not install a damaged coil.
WARNING
Before performing maintenance operations on system,
turn off all main power switches to indoor and outdoor
units. Turn off accessory heater power switch, if
applicable. Electrical shock could cause personal injury
or death.
Air Leakage
All indoor cabinets MUST be taped after installation to seal
against any air leaks. System performance and efciency
will be reduced if air leakage exists.
Air Filters
Properly-sized air lters MUST be installed on all return air
ducts. If air lters are not used or maintained regularly as
required, equipment damage can occur, system capacity
and efciency will be reduced and the warranty coverage
may be void.
Filter Dryer
A new lter dryer MUST be installed on all systems. The
lter dryer is typically shipped with the outdoor unit; if not,
add one. Do not install more than one lter dryer in the
system; it can reduce the system capacity and efciency.
Metering Device
The indoor coils are shipped with either a piston or
expansion valve (TXV) based on the coil model. The
selection of the metering device type and size must follow
the outdoor unit technical specication and the AHRI listing.
Pistons
The piston shipped with the indoor coil may not be the
correct size for the outdoor unit being installed. The
outdoor unit specication gives the correct size and the
correct piston is usually shipped with the outdoor unit.
To replace the piston with another piston, perform the
following procedure:
1. Loosen the piston housing hex nut on coil liquid tube.
Use TWO wrenches to avoid damage to the distributor
tubes.
2. Replace the existing piston with the new piston
3. Always use a new Teon O-ring
4. Re-assemble the housing and torque to 10-20 ft-lb
using TWO wrenches