Board Dimensions (L x W x H) (approximate):
5.2” (132.08mm) x 7.6” (193.04mm) x 2.5” (63.5mm)
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
0.25”
(6.35mm)
6.7
(170.18mm)
3.7
(93.98mm)
5.1
(129.54mm)
7.6
(193.04mm)
0.12”
(3.05mm)
Ø
0.156”
(3.96mm)
UL Recognized component for Access Control System Units (UL 294)
Standard for Safety for Fire Protective Signaling Systems (UL 1481).
Agency Approvals
Specifications
Input:
• Input115VAC,60Hz,4.4amp.
• Inputfuserated@3.5amp/250V.
Output:
• 24VDCoutput.
•10ampofcontinuoussupplycurrentfor
Access Control applications.
• 8ampofcontinuoussupplycurrentfor
Fire Alarm applications.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidor
gel type batteries.
• Automaticswitchovertostand-bybattery
whenACfails.
Battery Backup (cont’d):
• Maximumchargecurrent3.6amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• 91BTU/Hr.
• SystemACinputVArequirement:506VA.
Mechanical:
• Productweight(approx.):2.45 lbs. (1.11 kg.).
• Shippingweight(approx.):2.75lbs.(1.25kg.).
AL1024ULXBisaULRecognizedpowersupply/chargerwhichconvertsa
115VAC,60Hzinputintoasingle24VDCnon-powerlimitedoutput.
AL1024ULXB
Off-line Switching Power Supply/Charger
Rev.DSAL1024ULXB_04262012
Overview
AL1024ULXB
1/1