LG TBNH488RSS5.ANWBAEC ceiling duct type air conditioner offers powerful cooling and heating capabilities with a rated cooling capacity of 14kW and a heating capacity of 15.2kW. It features inverter technology for energy efficiency and precise temperature control. The unit has a soft dry operation mode to maintain a comfortable humidity level without over-cooling the room. Additionally, it comes with a wired remote controller for convenient operation and a built-in timer for scheduling on and off times.

LG TBNH488RSS5.ANWBAEC ceiling duct type air conditioner offers powerful cooling and heating capabilities with a rated cooling capacity of 14kW and a heating capacity of 15.2kW. It features inverter technology for energy efficiency and precise temperature control. The unit has a soft dry operation mode to maintain a comfortable humidity level without over-cooling the room. Additionally, it comes with a wired remote controller for convenient operation and a built-in timer for scheduling on and off times.

Ceiling Duct Type
Air Conditioner
SERVICE MANUAL
MODELS:
TB-H488RSS5
Contents
Functions ..................................................................................................................................3
Product Specifications .............................................................................................................5
Dimensions ..............................................................................................................................11
Refrigeration Cycle Diagram ..................................................................................................31
Wiring Diagram .......................................................................................................................35
Operation Details ....................................................................................................................51
Installation of Indoor, Outdoor Unit ......................................................................................54
Test running ............................................................................................................................66
Optional Operation .................................................................................................................68
External Static Pressure & air Flow ......................................................................................70
3-way Valve .............................................................................................................................71
Cycle ........................................................................................................................................74
Cycle Troubleshooting Guide ................................................................................................78
Electronic Parts Troubleshooting Guide ..............................................................................79
Electronic control device .......................................................................................................82
Exploded View and Replacement Parts List ........................................................................83
–2–
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Auto Operation(Auto Change Over)
Deice (defrost) control (Heating)
Auto Restart
–3–
Hot-start Control (Heating)
• The indoor fan does not start until the evaporator piping
temperature will be reached at 28°C.
High head height Drain pump(Optional)
• A standard drain-head height of up to 700mm is possible.
Central Control(Optional)
It is operating individually or totally by central control function.
Group Control(Optional Wiring)
Radio Frequency Control (Optional)
Each controller can control 16 units and 8 controllers can be connected.
It operates maximum 16 units with the help of only one wired remote
controller and each unit can be randomly started to prevent overcurrent.
• Room temperature sensor. (Thermistor)
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Medium, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted automati-
cally previous operation mode after power supply.
• The setting temperature and desired operation mode are auto-
matically set by fuzzy rule.
• Both the indoor and outdoor fan stop during defrosting.
• Hot start after defrost ends.
–4–
Remote Controller
Operation ON/OFF
Operation Mode Selection
Fan Speed Selection
Room Temperature Display
Temperature Setting
Setting the Timer
Weekly Program
(Cooling
model only)
(Heating
model only)
(Low) (Med) (High)
Cooling Operation Mode ( )
Heating Operation Mode ( ) Auto Operation Mode ( )
Soft Dry Operation Mode ( )
Fan Operation Mode
HIMEDLO
Program Holiday
SET/CLR
MinHour
Week
Timer CancelTimer Cancel
: High:39°C ļ LOW:11°C
: Only the Fan is in operation.
Cooling Heating
Down to 18°C
Up to 30°C
Down to 16°C
Up to 30°C
1. Specifications
1.1 Indoor unit
-5-
5
5
1. Specifications
1.2 Outdoor Unit
-6-
Note :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB
- Piping Length : Interconnected Pipe L
ength = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during opration.
TBUH488RSS5
Rated kW 14.0
Rated Btu/h 48,000
Rated kW 15.2
Rated Btu/h 52,000
Cooling Rated kW 5.30
Heating Rated kW 5.00
W / W 2.65 / 3.05
V / Ø / Hz 380-415 / 3 / 50
Cooling Rated A 9.0
Heating Rated A 8.0
Cooling Max. A -
Heating Max. A -
Wiring Connections Power Supply Cable (included Earth)
No. x mm
2
(AWG)
5C x 3.5 (12)
- White
W x H x D mm 900 × 1,165 × 370
W x H x D inch 35-7/16 × 45-7/8 × 14-9/16
kg (lbs) 95.0 (209.4)
- Scroll
Model x No. SB061YAB x 1
- Three Phase Induction Motor
W x No. 4,050 x 1
- R22
g (oz) 3,600 (141.1)
m (ft) 7.5 (24.6)
g/m (oz/ft) 65 (0.76)
- Capillary
- SUNISO 4GSI or NM56M
cc
x No. 1,650 x 1
- (2 × 26 × 17) × 2
- Propeller
m
3
/min x No.
52.5 x 2
- AC
W x No. 77 x 2
Cooling Rated dB(A) 61
Heating Rated dB(A) 61
Liquid Outer Dia. mm(inch) Ø 9.52 (3/8)
Gas Outer Dia. mm(inch) Ø 19.05 (3/4)
Max. m (ft) 50 (164)
Maximum Height
Difference
Outdoor Unit ~ Indoor Unit Max. m (ft) 30 (98.4)
Cooling Min. ~ Max.
DB ( DB)
21 (69.8) ~ 54 (129.2)
Heating Min. ~ Max.
DB ( DB)
-5(23.0) ~ 24 (75
.2)
Heat Exchanger (Row x Column x Fins per inch) x No.
Operation Range
(Outdoor Temperature)
Fan
Fan Motor
Sound Pressure Level
Pipin
g Connections
Pipi
ng Length
Type
Air Flow Rate
Type
Type
Dimensions
Casing Color
EER / COP
Type
Refrigerant Oil
Type
Precharged Amount
Charged volume
Power Input
Running Current
Starting Current
Power Supply
Output
Compressor
Refrigerant
Net Weight
Motor type
Motor Output
Chargeless-Pipe Length
Mo
del
Additional Charging Volume
Control
Outdoor unit
Capacity
Cooling
Heating
5
8
5
–9–
Description
PCB Connector
CN-PIPE
CN-ROOM
Model No.: TB-H488RSS5
High
Pressure
Switch(By-Pass)
High
Pressure
Switch
Compressor
MM
Outdoor Unit
Indoor Unit
Ø9.52 / 3 way
Flare Connection
Ø19.05 / 3 way
Flare Connection
Ø19.05 / 2 way
Flare Connection
Ø9.52 / 2 way
Flare Connection
: Cooling
: Heating
BY-PASS
4 way
Valve
Accumulator
Condenser out
Capillary Tube
Cooling
Capillary Tube
Evaporator in
Capillary Tube
Heating
Capillary Tube
MM MM
Thermistor for
Suction
Air
temperature
Thermistor for evaporator
outlet temperature
Thermistor for evaporator outlet temperature
Thermistor for Suction Air temperature
5
65
3.Piping diagrams
Operation Details
(1) The function of main controls/controller
1. Time Delay Safety Control
• 3min
...
The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 30sec
...
The 4-way valve is ceased for 30sec. to prevent the abnormal noise of the refrigerant gas when the
Heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by Micom Control.
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to remote controller settings and
the operation diagram is as following.
–10–
Intake Air temp.
SET TEMP.+0.5°C
(COMP. ON)
SET TEMP. -0.5°C
nahteroMnahteroM)FFO.PMOC(
setunim3setunim3
gnitceleSgnitceleSgnitceleS
deepsnafdeepsnafdeepsnaf
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN Low Low
–11–
Intake Air temp.
Setting temp.+3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
FFOwoLwoLFFOwoLNAFROODNI
COMPRESSOR ON OFF ON OFF
• A point; While the Indoor Heat-Exchanger temperature is higher than 40°C, the fan operates at low speed,
and when it becomes lower than 40ÛC fan stops.
• B point; When the Indoor Heat-Exchanger temperature is higher than 42°C, fan operates at seleted fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
4. Heating Mode Operation (Except Cooling Model)
The unit will operate according to the remote controller settings and the operation diagram is shown as following.
Hot Start
Low
Selecting
Fan Speed
minimum 3min
Selecting fan
speed
minimum
10sec.
1min
AA
minimum
10sec.
B
5. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature reaches to 31°C.
• The operation diagram is as following.
PIPING
TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
ON
28°C
: Selected Fan : Low Fan : Fan Stop
31°C
–12–
6. Defrost Control
• Defrost control is available for 45 minutes since heating mode operation is started, and it will not prolong over
10 minutes.
• Defrost control is carried out when the outdoor pipe temp. falls below -6°C for more than 3 minutes after 45
minutes are passed from starting of heating operation.
• Defrost ends after 10 minutes are passed from starting of defrost operation or when the outdoor pipe temp.
rises to 12°C after 5 minutes are passed from starting of defrost.
7. Self-diagnosis Function
• 'CHECK' : Please contact your dealer if the remote controller displays this message 'CHECK'.
• Rectify the problem as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
Remote controller LCD Accident Point
CH 01 Indoor room temperature thermistor error
CH 02 Indoor piping thermistor error
CH 03
Indoor main body / Remote controller unit communication error
CH 04(Optional) Water level float switch error
More than 45 minutes
of heating operation
Within
9min. 45sec.
ON OFF
NONO
ON
ON OFF
OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6°C ON
12°C OFF
The outdoor
piping Temp.
ON
More than 10 min.
running of compressor
More than 45 minutes
of heating operation
5sec.
HOT-
START
ON
–13–
Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satis-
fies the following conditions.
Place should easily bear a load exceeding four
times the indoor unit’s weight.
The place should enable the unit to be inspected
as shown in fig.
• The place should be such that leveled.
The place should allow easy water drainage.(Suit-
able dimension “H” is necessary to get a slope to
drain as figure.)
The place should easily connect with the outdoor
unit.
The place where the unit is not affected by an
electrical noise.
The place where air circulation in the room will be
good .
There should not be near the unit any heat source
or steam.
2) Outdoor unit
If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat
transfer from the condenser is not restricted.
There should be no animals or plants in vicinity of
the hot discharged air.
Ensure the space indicated by arrows from the
wall, ceiling, fence or other obstacles.
More than
30cm
More than
30cm
More than
70cm
Sunroof
Fence or
obstacles
Top view
(unit: mm)
H
Front view
450
Front
Inspection hole
(450X450)
Control box
0001
–14–
2. Indoor unit installation
Installation of Unit
Install the unit above the ceiling correctly.
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
Install the unit leaning to a drainage hole side as
shown in figure for easy water drainage.
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
A
B
C
1-3 mm
D
(G)
H
I
E F
NOTE:
• Throughly study the following installation locations:
1. In places such as restaurant and kitchen, considerable amount of oil steam and flour adhere to the fan, the fins of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In such cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories,etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
–15–
3. The Indoor Unit Installation
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.
Insert the set anchor and washer onto the suspen-
sion bolts for locking the suspension bolts on the ceil-
ing.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
4. Remote Controller Installation
Although the room temperature sensor is in the indoor unit, the remote controller should be installed
in such places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
Select control position after receiving customer's consent.
The room temperature sensor is built in the indoor unit.
This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
Keep the remote controller cord away from the refrigerant pipe and drain pipe.
To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment, television set, etc.)
If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
Tighten the nut and bolt to prevent the unit from falling.
CAUTION
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
• Local supply
Set anchor
Plate washer - M10
Spring washer - M10
Nut - W3/8 or M10
Suspension bolt - W3/8 or M10
–16–
Remote control
box body
Cord clamp
(accessory)
Lever carefully
the box open
using a screw
driver, etc.
Front case
The lower part
Face of wall
Under plate
Screw (accessory)
Remove the battery cover from the remote con-
troller.
• Slide the cover according to the arrow direction.
Insert the two batteries.
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
• Fix the under plate on the wall
• Separate the under plate from Remote control box.
• Fix the cord clamps on the wall by ø 3 tapping
screws (accessory).
• Fix the remote control cord.
WIRED REMOTE CONTROL INSTALLATION
REMOTE CONTROL PREPARATION(OPTIONAL)
DISASSEMBLING
ELECTRICAL WIRING
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
Wire and make sure that terminal
numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
use a wire size greater than 0.5mm
2
.
Remote controller
(Main board)
CN REMO
Do not use rechargeable batteries,
such batteries differ from standard dry
cells in shape, dimensions, and per-
formance.
• Remove the batteries from the remote
controller if the air conditioner is not
going to be used for some long time.
HOW TO INSERT BATTERIES
5. Connecting Cables between Indoor Unit and Outdoor Unit
–17–
1) Connecting cables to the Indoor Unit
Connect the wires to the terminals on the control board individually according to the
outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as
2
) Clamping of cables
Make sure that the terminal screws are not loose.
WARNING
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 1.25mm
2
cable(thinner cable) on the clamp and tighten it with a
plastic clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the
middle of live pin on the power plug should be over 1.8m.
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
CAUTION
2 0 m m
2 0 m m
N/YLG
N/YLG
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(18k/24k/30k/36k/42k)
1.25mm
2
(48k/60k)
Capacity
48kBtu/h
1 Phase
-
3 Phase
3.5mm
2
NORMAL CROSS-SECTIONAL AREA
The connecting cable connected to the indoor and outdoor unit should be
complied with the following specifications (Rubber insulation, type H05RN-
F approved by HAR or SAA).
The power cord connected to the outdoor unit should be complied with
the following specifications (Rubber insulation, type H05RN-F approved by
HAR or SAA).
Therminals on the indoor unit
1(L) 2(N) 3
R
POWER INPUT
S T N
Therminals on the outdoor unit
1(L) 2(N) 3
(380-415V 3N~ 50Hz)
Heating Pump type
4
4
48k Btu/h
–18–
Outdoor
Indoor
Control terminal board
Control box
Control box cover
(On which the Electric
Wiring Connection is put)
Main terminal board
Control terminal board
Cover control
A A view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Cord clamper
1
1
Main
power source
Switch box
Circuit Breaker
Use a 35A(60K)
circuit breaker or time
delay fuse.
ELECTRICAL WIRING
INDOOR UNIT
• Remove the control box cover for electrical con-
nection between the indoor and outdoor
unit.(Remove two screws
.)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to the electrical wiring
connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supply-
ing the current required by the air conditioner.
• Use a recognized circuit breaker between the
power source and the unit. A disconnection
device to adequately disconnect all supply lines
must be fitted.
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring connection.
Use the cord clamper to fix the cord.
Earthing work
Connect the cable of diameter 1.6mm
2
or more to
the earthing terminal provided in the control box
and do earthing.
Please check !!
Capacity 1 Phase 3 Phase
48kBtu/h - 30A
–19–
• Preparation of Piping
6. Connecting Pipes to the Indoor Unit
–20–
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42

LG TBNH488RSS5.ANWBAEC User guide

Category
Split-system air conditioners
Type
User guide

LG TBNH488RSS5.ANWBAEC ceiling duct type air conditioner offers powerful cooling and heating capabilities with a rated cooling capacity of 14kW and a heating capacity of 15.2kW. It features inverter technology for energy efficiency and precise temperature control. The unit has a soft dry operation mode to maintain a comfortable humidity level without over-cooling the room. Additionally, it comes with a wired remote controller for convenient operation and a built-in timer for scheduling on and off times.