Select Entry Systems TEC1ACL Series is an access controller that provides secure, reliable, and convenient access control for a variety of applications. It features out-of-the-box active cellular capability, allowing for easy installation and use. With its cellular connectivity, the TEC1ACL Series can be managed and controlled remotely, making it ideal for remote locations or applications where real-time monitoring is required.

Select Entry Systems TEC1ACL Series is an access controller that provides secure, reliable, and convenient access control for a variety of applications. It features out-of-the-box active cellular capability, allowing for easy installation and use. With its cellular connectivity, the TEC1ACL Series can be managed and controlled remotely, making it ideal for remote locations or applications where real-time monitoring is required.

TEC1ACL SERIES
2/2021
Covers: T1A2LxxxPRMCL/T1A4LxxxPRMCL
Select Engineered Systems, Inc.
7991 West 26th Ave
Hialeah, FL 33016
Tel: 305 823 5410
Fax: 305 823 5215
www.selectses.com
© 2003 – 2021 All Rights Reserved
TEC1ACL Installer Guide 02/21
RevC
Page1of12
1
Installation – TEC1ACL Series Access Controllers ................................................... 3
1.1
Safety Warnings / Avertissements de Sécurité .................................................... 3
1.1.1
English Language.......................................................................................... 3
1.1.2
Sécurité Avertissements En français ............................................................. 3
1.2
Cellular Services .................................................................................................. 4
1.2.1
Out of the Box Active Cellular Capability - Ready to Install ....................... 4
1.2.2
Checking Cellular Reception at Installation Site .......................................... 4
1.2.3
Select Cellular Module Interface (Router) “SCMI” LED Indications .......... 4
1.2.4
Note on Fallback Services ............................................................................ 5
1.3
Mechanical Mounting .......................................................................................... 6
1.3.1
Installation Heights ....................................................................................... 6
1.3.2
Surface Mount ............................................................................................... 6
1.3.3
Flush Mount .................................................................................................. 6
1.3.4
Optional Weather Hood Recommendation ................................................... 6
1.3.5
Sealing........................................................................................................... 6
1.4
Electrical ............................................................................................................... 7
1.4.1
Grounding ..................................................................................................... 7
1.4.2
Overall Main Board Layout .......................................................................... 8
1.4.3
User Connections .......................................................................................... 9
1.4.4
Reader Card ................................................................................................ 11
1.4.5
Communication Board ................................................................................ 11
1.5
Programming a Directory Record with a PIN into a TEC1ACL ....................... 12
TEC1ACL Installer Guide 02/21
RevC
Page2of12
Figure 1: Installation Height for Pedestrian and Drive-Up Applications ........................... 6
Figure 2: TEC1ACL Location of Back Box Ground Lug .................................................. 7
Figure 3: TEC1ACL Ground Lug Connection ................................................................... 7
Figure 4: Inside Door of TEC1ACL ................................................................................... 8
Figure 5: TEC1ACL User Connections .............................................................................. 9

TEC1ACL Installer Guide 02/21
RevC
Page3of12
1 Installation–TEC1ACLSeriesAccessControllers
1.1 SafetyWarnings/AvertissementsdeSécurité
1.1.1 EnglishLanguage
ForyoursafetypleaseobservethefollowingrecommendationswheninstallingTEC1ACL
seriesproductenclosures:
Neverinstallequipmentduringalightningstormorotherhazardousevent
Donotbringmainsvoltagecablingintotheproductenclosureorattemptto
connectmainsvoltagetoanywiresleadingfromtheproduct,ortheenclosure
housingitself.Onlytheisolatingtransformersuppliedwiththeproductshould
beconnectedtotheelectricalmainssupplybyfollowingtheinstallation
instructionsbelow
Inwetlocations,onlyinstallwiringandcablingratedforwetlocations
Nevertouchun‐insulatedtelephonewiresorterminalsunlessthetelephoneline
hasbeendisconnectedatthetelephonenetworkinterface
Followindustry‐recommendedinstallationpracticeswheninstallingcablesand
groundingwires
Donotattempttousetheprovidedisolatingtransformertosupplyother
equipment‐itisintendedsolelyforthepurposeofpoweringaccesscontrollers
intheTEC1ACLseries
1.1.2 SécuritéAvertissementsEnfrançais
Pour votre sécurité, observez les recommandations suivantes lors de l'installation des
boîtiers pour le produit de la série TEC1ACL :
N'installez jamais l'équipement pendant un orage ou tout autre événement
dangereux
Ne connectez aucun câblage de courant du secteur au boîtier du produit. Ne tentez
pas de connecter le courant du secteur aux fils sortant du produit ou au boîtier lui-
même. Ne connectez au courant du secteur que le transformateur de séparation
fourni avec le produit, en suivant les instructions d'installation ci-dessous
Dans les emplacements mouillés, installez uniquement des fils et câbles
homologués pour les emplacements mouillés
Ne touchez jamais des fils ou des bornes de téléphone non isolés, sauf si la ligne
téléphonique a été déconnectée au niveau de l'interface réseau téléphonique
Suivez les pratiques d'installation recommandée par l'industrie lors de
l'installation des câbles et des fils de mise à la terre
Ne tentez pas d'utiliser le transformateur de séparation à l'alimentation électrique
d'autres équipements. Il est destiné uniquement à l'alimentation électrique des
contrôleurs d'accès de la série TEC1ACL

TEC1ACL Installer Guide 02/21
RevC
Page4of12
1.2 CellularServices
InstallationofTEC1ACLrequirescellularservicefromyourchosencellularservice
provider–eitherAT&TorT‐Mobile.
1.2.1 OutoftheBoxActiveCellularCapability‐ReadytoInstall
TheTEC1ACLisshippedwithanACTIVEcellularSIMcardandisreadytouseoutof‐the‐box.
1.2.2 CheckingCellularReceptionatInstallationSite
Before fully installing the product, check the cellular signal strength at the installation location by
simply applying power to the Select Cellular Module Interface (Router) “SCMI” using the
12VDC/2A transformer supplied by SES. Keep in mind your carrier coverage for the site area (AT
& T or T-Mobile factory options). You can use the SCMI internal LED indicators to check for
cellular service.
Once the SCMI has been powered up for one minute, the
“Mobile” LED (green oval) will illuminate if service is
connected and idle.
In the red box, 1, 2 and 3 vertical dashes below the LEDs
correspond to low*, medium and high signal strengths. One bar
indicated potentially unreliable service, 2 or 3 bars are
recommended.
*An optional External Antenna is available to improve reception.
1.2.3 SelectCellularModuleInterface(Router)“SCMI”LEDIndications
LED Color Condition Meaning
POWER Red Off No DC power
On DC power is on
STATUS Green Steady Off No cellular connection/error
Steady on Cellular phone in use
Long blink on/Long blink
off
Data transfer in progress
Short blink on/long blink off No SIM card or network searching
Long blink on/short blink off In service
MOBILE Green Steady on Cellular phone is idle
Very short blink on /
Very short blink off
Cellular phone is in use
Short blink on/short blink off Cellular circuits busy
Long blink on/long blink off Dialed number is busy
CPE Amber Off Unit phone line is “on-hook”
On Unit phone line is “off-hook”
(Signal Strength)
No bars All off Poor or no useable signal
1-bar LED Green On Low signal but useable*
2-bar LED Green On Good signal
3-bar LED Green On Best signal
WAN Green Off/On SES use only
TEC1ACL Installer Guide 02/21
RevC
Page5of12
1.2.4 NoteonFallbackServices
TheSCMIsearchesforthebestavailablecellularservice,butwillfallbackto3Gservices
if4GLTEandVoLTEservicesarenotavailable.Availabilityoftheseservicesiscontrolled
bycellularcarriers,notSES.

TEC1ACL Installer Guide 02/21
RevC
Page6of12
1.3 MechanicalMounting
1.3.1 InstallationHeights
Figure1showstherecommendedinstallationheightsforTEC1ACLseriesaccess
controllers.
Figure1:InstallationHeightforPedestrianandDrive‐UpApplications
1.3.2 SurfaceMount
Mounttheback‐boxusingtheholesprovided.

1.3.3 FlushMount
Cutaholethesizeofthebackbox8½"(w)x11¾"(h)inthewall,thenmountthe
TEC1ACLinthehole.

1.3.4 OptionalWeatherHoodRecommendation
ItisrecommendedthatanoptionalweatherhoodbeusedwhenmountingaTEC1ACLin
astand‐aloneapplicationtoprotectitfromdirectexposuretorainandsnow.Pleasecall
Factoryforavailability.
1.3.5 Sealing
AllopeningsandpenetrationsoftheTEC1ACLenclosureshouldbesealedwithsuitable
RTVsiliconsealant.
TEC1ACL
TEC1ACL
TEC1ACL Installer Guide 02/21
RevC
Page7of12
1.4 Electrical
1.4.1 Grounding
TheTEC1ACLMUSTBEATEARTHGROUNDPOTENTIAL.
Connecta#16strandedorlargerwirefromthegroundluginthebaseofthebackboxof
theTEC1ACLtoacoldwaterpipeorothersuitableground.Thiswireshouldbelessthan
50feetinlength.SeeFigure2forthelocationofthebackboxgroundlug.
SelectCellular
ModuleInterface
(Router)“SCMI”
BackBoxGround
Lug
Figure2:TEC1ACLLocationofBackBoxGroundLug
Figure3:TEC1ACLGroundLugConnection
TEC1ACL Installer Guide 02/21
RevC
Page8of12
1.4.2 OverallMainBoardLayout
SeeFigure4belowforanimageofthemainboard.
*Microphone(“Mike”)SensitivityAdjustment
*Screwdriveradjustmentthroughhole
*SpeakerVolume
Adjustment
*DisplayContrast
Adjustment
CommunicationBoard
(Factoryinstalledon
PRMversion)
2‐ReaderBoard
(Factoryinstalledon
PRMversion)
UserConnectionStrip
P1A(ConnectorPlug
shown)
UserConnectionStrip
P1(ConnectorPlug
shown)
PostalLockSwitch
DoorGroundStud
Figure4:InsideDoorofTEC1ACL

TEC1ACL Installer Guide 02/21
RevC
Page9of12
1.4.3 UserConnections
Figure5showstheTerminalStripconnectionsP1andP1Aforuserconnections,along
withtheDoorGroundStud.Nootherconnectionsarerequired.
Figure5:TEC1ACLUserConnections
1.4.3.1 TelephoneConnection
The phone cable is already factory-connected to the SCMI at TE-TE in the figure above.
CAUTIONDoNotConnectOtherNon‐SESEquipment
NOOTHERTELEPHONEDEVICESorNON‐SESEQUIPMENTshouldbeattachedtothis
phoneline.
TheexceptioniswhenconnectingadditionalSESaccesscontrollers.Inthiscase,an
MUIplug‐inboard(includedinPRMversion)mustbeused,allowinguptotwoSES
AccessControllerstobeconnectedonthesameline.
TEC1ACL Installer Guide 02/21
RevC
Page10of12
1.4.3.2 TEC1ACLPower
PowermustbeappliedusingtheSES‐supplied12VDC/2Atransformer.TheSES
transformerwiresshouldbeconnectedintotheterminals“+POSXR”and“‐NEGXR”
locatedinthebackboxasshownbelow.
WARNINGDonotuseACpoweronTEC1ACLunit.ThereshouldbeNOconnections
on“AC”and“AC”terminalsofP1connector.DamagetotheTEC1ACLmayoccurand
voidthewarranty.
For12VDCsource,idlecurrentconsumptionisasfollows:
12VDCIDLECurrentTableTEC1ACL
LCDDisplay
IdleCurrent(mA)
2‐Line 490
4‐Line 510

To SES Select Cellular Module
Interface (Router) “SCMI”
TEC1ACL Installer Guide 02/21
RevC
Page11of12
1.4.3.3 Rex(RequesttoExit)Inputs
Therequesttoexitinputs(RX1andRX2)areVOLT‐FREE(dry)contactslocatedon
connectorP1asshowninFigure5.Noexternalvoltageiseitherrequiredordesired.
TouseeitherRexinput,connecttheCOM(betweenRX1andRX2ofconnectorP1)to
onesideoftheexternalrelay’scontactbeingusedtorequestexit,thenconnecteither
RX1orRX2totheothersideoftherelaycontactasdesired.Figure5refers.
WARNING – Rex Inputs
Connecting an external voltage source to either Rex input will cause damage and
void the warranty.
1.4.3.4 Relays
RelaysareconnectedtoterminalsonconnectorP1A.Bothnormallyopen(NO)and
normallyclosed(NC)contactsareavailableforbothrelayswithouttheneedforboard
configuration.
WARNING–RelayContactsMaximumRatingsare2A@24VoltsACorDC
Failuretocomplywiththemaximumratingsshownforrelayswillcausedamage
andvoidthewarranty.
1.4.4 ReaderCard
The TEC1ACL Premium version includes a 2-Reader Board which works with 26 bit
Wiegand format.
The2‐Readerboardinstallationinstructionsareincludedinthisbookletorwiththe
individualcardpackagesiforderedseparately.Additionalinformationcanbefoundon
theSESwebsitewww.selectses.com.
1.4.5 CommunicationBoard
The factory installed Communication Board in the TEC1ACL series includes MUI,
Ethernet and Serial connections, which will allow programming of the unit over the
cellular network using SES Selcom software.
SES will provide a SIM Card IP address and a Port number on a label for use in Selcom
software setup using TCP/IP communications method. For more information, visit SES
website www.selectses.com.

TEC1ACL Installer Guide 02/21
RevC
Page12of12
1.5 ProgrammingaDirectoryRecordwithaPINintoaTEC1ACL
The following steps show how to set a directory record (Code, Name, Phone # and PIN
for entrance 1 with 24/7 access) using the keypad. It assumes the TEC1ACL is powered
on and that the Welcome Page e.g. “Press # to View Directory” is displayed before
starting. Note that Steps 4 and 5 are included to check if PINs are enabled. Once PINs are
enabled, steps 4 and 5 can be skipped for future entries. For all other settings please refer
to “TEC1ACL Series Menus”.
StepstoProgramaDirectoryRecordwithaPINintoaTEC1ACLusingtheKeypad
# StepDescription KeypadAction ResultingDisplay
1 EnterProgramming
Mode
Press*and0atsametime PASSWORD
2 EnterPassword Press6digitpassword(defaultis
“777777”)then*
MAINMENU1‐8
3 SelectCodes&Names Press1 CODES&NAMES
SELECT1‐9
4 Skipthisstepifyouknow
PINsareenabled
Press8 ENABLEPINS=0or
ENABLEPINS=1
5 Completecheckof
EnablePINssetting
IfENABLEPINS=0,press1then*
IfENABLEPINS=1,press*
CODES&NAMES
SELECT1‐9
6 SelectAddNew Press1 CODE=
7 Enteracodee.g.100 Press“100”then*NAME=
8 Enteranamee.g.JOHN. Note:#movescursortonext
character
PressJ#O#H#N#then*
PHONE#=
9 Enterphonenumber e.g.3055551212then*PIN=
10 Enter4‐digitPIN e.g.1234then* ENTRANCE=0
11 SetEntrance1 Press1then* TGGROUP=0
12 SetGroup0(24/7access) Press0then*CODE=
13 Entermorerecords
OR
Repeatasneededfromendofstep6
withnewdata.
Notethatnotwocodesandnotwo
pinscanbeidentical.
14 ExitProgrammingMode Press*0together WelcomePage
 
“BETTER TECHNOLOGY MAKES BETTER SYSTEMS”
2/2021
02/21
Select Engineered Systems, Inc.
Hialeah, FL 33016
Website: www.selectses.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Select Entry Systems TEC1ACL Series Installation guide

Type
Installation guide

Select Entry Systems TEC1ACL Series is an access controller that provides secure, reliable, and convenient access control for a variety of applications. It features out-of-the-box active cellular capability, allowing for easy installation and use. With its cellular connectivity, the TEC1ACL Series can be managed and controlled remotely, making it ideal for remote locations or applications where real-time monitoring is required.