Eaton GHG 273 Operating Instructions Manual

Type
Operating Instructions Manual
2 EATON’s Crouse-Hinds Business
Explosionsgeschützte
Installationsschalter
Typ GHG 273
Explosion protected
installation switches
type GHG 273
Interrupteurs d’éclairage
pour atmosphères explosives
type GHG 273
Inhalt:
Inhalt ....................................................... 2
Maßbild ................................................... 3
Anschlussbilder. ...................................... 3
1 Technische Angaben ............................... 3
2 Sicherheitshinweise ................................ 3
3 Normenkonformität ................................. 3
4 Verwendungsbereich .............................. 3
5 Verwendung / Eigenschaften .................. 4
6 Installation ............................................... 4
6.1 Montage .................................................. 4
6.2 Öffnen des Gerätes /
Elektrischer Anschluss
............................ 4
6.3 Kabel- und Leitungseinführungen;
Verschlussstopfen
................................... 5
6.4 Flansche und Metallplatten ..................... 5
6.5 Schließen des Gerätes ............................ 5
6.6 Inbetriebnahme ....................................... 5
7 Instandhaltung / Wartung ........................ 5
8 Reparatur / Instandsetzung /
Änderungen
............................................ 5
9 Entsorgung / Wiederverwertung ............. 5
Konformitätserklärung separat beigelegt.
Contents:
Contents ................................................. 2
Dimensional drawings ............................. 6
Wiring diagrams ...................................... 6
1 Technical Data ......................................... 6
2 Safety instructions .................................. 6
3 Conformity with standards ...................... 6
4 Field of application .................................. 6
5 Use / Properties ...................................... 7
6 Installation ............................................... 7
6.1 Mounting ................................................. 7
6.2 Opening the device /
Electrical connection ............................... 7
6.3 Cable entries (KLE);
blanking plug ........................................... 8
6.4 Flange and metal plates .......................... 8
6.5 Closing the device / cover closure .......... 8
6.6 Taking into operation ............................... 8
7 Maintenance / Servicing .......................... 8
8 Repairs / Overhaul /
Modification ............................................ 8
9 Disposal / Recycling ................................ 8
Declaration of conformity, enclosed separately.
Contenu:
Contenu .................................................. 2
Plans cotés .............................................. 9
Schéma des connexions ......................... 9
1 Caractéristiques techniques ................... 9
2 Consignes de sécurité ............................ 9
3 Conformité avec les normes ................... 9
4 Domaine d’utilisation .............................. 9
5 Utilisation / Propriétés ............................10
6 Installation ..............................................10
6.1 Montage .................................................10
6.2 Ouverture du dispositif /
Raccordement électrique ....................... 10
6.3 Entrées de câble (KLE);
bouchons de fermeture .........................11
6.4 Plaques à brides ..................................... 11
6.5 Fermeture de l’appareil ..........................11
6.6 Mise en service ......................................11
7 Maintien / Entretien ...............................11
8 Réparation /
Remise en état ....................................... 11
9 Évacuation des déchets / Recyclage ......11
Déclaration de conformité, jointe séparément.
6 EATON’s Crouse-Hinds Business
GB
Explosions protected installation switches
type GHG 273
Dimensions in mm
Wiring diagrams
X = Fixing dimensions
1 Technical data
Marking acc. to 94/9/EC and directive:
D II 2 G Ex de II C T6
D II 2 D Ex tD A21 IP66 T 80° C
EC type examination certifi cate: PTB 98 ATEX 3121
Rated voltage: up to 250 V; 50/60 Hz
Rated current: max. 16 A
Short circuit back-up fuse: max. 20 A gL
Switching capacity EN 60947-4-1 AC 5a: 230 V / 16 A
Switching capacity EN 60947-4-2 AC 5b: 230 V / 16 A
Perm. ambient temperature:
(Special versions permit deviating temperature ranges)
-20° C up to +40° C (catalogue version)
Perm. storage temperature in original packing: -20° C up to +40° C
Protection category acc. to EN/IEC 60529: IP 66 ( catalogue version)
Insulation class acc. to EN/IEC 61140: I - is complied with by the installation switches
Cable entry (catalogue version): 1 x M25 or 2 x M25 (Ø 10 - 15 mm)
2 x drilling M20
suitable cables and test torques of the
pressure srew
Ø Nm
seel 1+2
1 2
min.
max.
(1)(2)
10.0
13.0
2.3
2.6
seel 2
1 2
min.
max.
(2)
13.5
15.0
1. 5
2.3
Supply terminal: 2 x 1.5 - 2.5 mm²
PE-terminal: 4 x 1.5 - 2.5 mm²
Test torques:
Test torque for screw in thread cable entry 3.0 Nm
Cover screws 2.0 Nm
Terminals 2.5 Nm
Weight (catalogue version): approx. 0.32 kg
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any
future maintenance work on the cable entry.
GHG 273
85
X75
85
115
53
5.6
20
6.7
55
85
X75
85
115
35
X52
5.6
20
6.7
64
55
The switch function is only realized
with closed enclosure cover
On-Off switch 2-pole
Change over switch
1S+1Ö
Push button switch
1S+1Ö
L
L(N)
L
L(N)
L
2 Safety instructions
a
The operations must be carried
out by electrical suitably trained in
hazardous area with knowledge of
increased safety explosion protection
IEC/EN 60079-14.
The installation switches are not suitable for
Zone 0 and Zone 20 hazardous areas.
The temperature class and explosion group
marked on the installation switches shall be
observed.
They shall be used for their intended
purpose and in perfect and clean condition.
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the user.
Prior to taking the installation switches
into operation, they shall be checked in
accordance with the instruction as per
section 6.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
3 Conformity with standards
Das Betriebsmittel ist gemäß
DINENISO9001:2008 und
EN ISO/IEC 80079-34:2011 entwickelt, gefertigt
und geprüft worden.
Es entspricht den aufgeführten Normen, in der
separat beigelegten Konformitätserklärung.
4 Field of application
The installation switches are suitable for use in
Zones 1 and 2 as well as in Zones 21 and 22
hazardous areas acc. to IEC/EN 60079-10-1 and
IEC/EN 60079-10-2!
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical
substances corresponding to the requirements
in a “normal industrial atmosphere”:
– impact resistant polyamide
– special steel AISI 316 L
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
7EATON’s Crouse-Hinds Business
GB
Explosions protected installation switches
type GHG 273
5 Use / Properties
The installation switches are designed for
switching on and off light circuits in hazardous
areas up to 16 A (see technical data). The
temperature class, explosion group and
permissible ambient temperature, see technical
data.
The installation switches can also be used in
a ”normal industrial area“.
The switch rocker is provided with a lumines-
cent label in acc. with § 7 of the Workshop
regulations and free from any radioactive
additives.
The data as per point 3 and 4 shall be taken
into account with the use.
Applications other than described are not
permitted without Cooper Crouse Hinds
prior written consent.
For the operation, the instructions stated in
section 7 of the operating instructions shall
be observed.
The user alone is responsible for the
appropriate use of this installation switch in
consideration of the basic conditions
existing at the plant (see technical data).
6 Installation
For the mounting and operation, the respective
national regulations (e. g. Betr.Si.V., equipment
safety law for Germany) as well as the general
rules of engineering shall be observed
(IEC/EN 60079-14).
The improper installation and operation
of switches may result in the invalidation
of the guarantee.
6.1 Mounting
The installation switches can be mounted
without opening their enclosure.
In case the switches are mounted directly onto
the wall, they may rest evenly only at the
respec tive fastening points. The chosen screw
shall match the fastening hole (see dimensional
drawing) and it must not damage the hole (e. g.
use of a washer). The device shall be fastened
diagonally with at least 2 screws.
If the screws are overtightened, the
apparatus can be damaged.
When the installation switch is mounted with
the cable entries on bottom side, the switch
insert and the enclosure cover must be turned
through 180° (see fi g.2).
The installation switch is suitable for fi xing onto
CEAG apparatus holders size 1 by means of
self-cutting screws (see fi g. 1).
The respective mounting instructions shall
be observed.
6.2 Opening the device /
Electrical connection
The electrical connection of the device may
only be carried out by skilled staff
(IEC/EN 60079-14).
Before opening the apparatus, ensure that
it has been isolated from the voltage supply,
or take appropriate protective measures.
Taking into account the respective regulations,
the properly bared conductors of the cables
shall be connected.
The insulation of the conductors shall reach
up to the terminal. The conductor itself shall
not be damaged.
If the installation switch is mounted with the
cable entries on bottom, point 6.1 and fi g. 2 will
have to be observed.
After dismantling the switch base in order to
facilitate the introduction of cables, such switch
base will have to be properly fi tted in again prior
to the electrical connection.
The connectible min. and max. conductor
cross-sections will have to be observed (see
technical data).
All screws and/or nuts of the supply terminals,
also of those remaining vacant, shall be
tightened down.
Excessive tightening may affect or damage
the connection.
The conductors shall be connected with
special care in order to maintain the
explosion category.
The supply terminals are designed for the
connection of copper conductors.
If multi- or fi ne-wire connecting cables are
used, the wire ends will have to be handled in
acc. with the applicable national and inter-
national rules (e. g. use of ferrules).
B
for wall-
and channel
xing
for pipe
xing
Fastening holes “B”
Enclosure base
- entry from
bottom side -
Switch basel
(Testing the switch socket
with a hard object (screwdriver)
is not permitted.)
- PE-terminal -
on the bottom
Enclosure cover
- type label -
on bottom
Size 1 apparatus holder
Fig. 1
Fig. 2
8 EATON’s Crouse-Hinds Business
GB
Explosions protected installation switches
type GHG 273
6.4 Flange and metal plates*
If fl ange plates have to be removed in case of
installation switches (e.g. for drilling entry
holes), attention shall be paid to the proper fi t of
the fl ange plate when mounting them in order
to maintain the minimum protection category
(see fi g. 3).
Flange plates shall be fi tted so that the
IP protection in maintained. Pay attention to
the proper seat of the sealing.
Attention: Metal fl anges, metal plates and
metal cable glands shall be included in the
equipotential earth connection.
Attention: When tightening the cap nut of
the metal cable entry (e.g.type ADE;
CMDEL), the screwing is to be protected
against twisting by means of a suitable tool.
PE conductors fed from outside are to be
connected to the PE terminal provided on the
ange. The maximum cross-section is 6 mm²
category.
* not yet certifi ed for category II D
6.5 Closing the device/
cover closure
The enclosure cover shall be fi tted so that the
protective collar is on the upper part.
Any foreign matter shall be removed from
the apparatus.
In order to ensure the required minimum
protection category, the cover screws are to
be tightened down.
Overtightening might impair the protection
category.
6.6 Taking into operation
Prior to taking the apparatus into operation, the
tests specifi ed in the relevant national
regulations will have to be carried out. Apart
from that, the correct functioning and installa-
tion of the apparatus in accordance with these
operating instructions and other applicable regu-
lations will have to be checked.
Testing the switch socket with a hard object
(screwdriver) is not permitted.
Incorrect installation and use of the
installa tion switches can invalidate the
guarantee.
7 Maintenance / Servicing
The relevant national regulations which
apply to the maintenance/servicing of
electrical apparatus in explosive atmo-
spheres, shall be observed
(e. g. IEC/EN 60079-17).
Before opening the enclosure make sure
that the apparatus is disconnected from the
voltage, or take the appropriate protective
measures.
The required maintenance intervals depend on
the respective application and will therefore
have to be determined by the user dependent
on the conditions of use.
When servicing the apparatus, particularly
those parts that are decisive for the type of
protection against explosion, will have to be
checked (e. g. intactness of fl ameproof
enclosed components, enclosure, cable glands,
effi cacy of the cover gaskets).
If during servicing repairs prove to be neces-
sary, section 8 of these operating instructions
will have to be observed.
8 Repairs / Overhaul /
Modifi cation
Repairs may only be carried out with genuine
CCH/CEAG spare parts.
In case of a damaged fl ameproof enclosure,
only its replacement is permitted. In case of
doubt, the respective apparatus will have to be
returned for repair to CCH/CEAG.
Repairs that affect the explosion protection,
may only be carried out by CCH/CEAG
or a qualifi ed electrician in compliance
with the applicable national rules
(e. g. IEC/EN 60079-19).
Modifi cations to the apparatus or changes
of its design are not permitted.
Except for the mounting of additional cable
entries in accordance with the approval of the
apparatus.
9 Disposal / Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed.
In order to facilitate the recycling of individual
components, plastic parts have been provided
with the identifi cation mark of the plastic
material used.
Subject to modifi cations or supplement of the
product range.
Metal fl ange for
metal cable glands
Enclosure base
Fig. 3
6.3 Cable entries (KLE);
blanking plugs
Generally, only certifi ed cable entries and
blanking plugs are permitted for use.
Flexible cables shall be used with trumpet-
shaped cable glands or other suitable
entries with additional pull-relief.
When using cable entries with a lower IP
protection than that which applies to the device
(see page 6, technical data), the IP protection of
the whole device will be reduced.
The mounting directives applicable to the cable
entries used shall be observed.
Unused holes shall be closed with a certifi ed
blanking plug in order to establish the minimum
protection category. In case of sealing inserts
that are cut out, it shall be ensured that the
insert is properly adapted to the cable diameter.
Care has to be taken that when fi tting the cable
entries, sealing inserts appropriate to the cable
diameter are used.
In order to ensure the required minimum
protection category, the cable glands are to be
tightened down.
Overtightening might impair the protection.
All vacant metric CEAG cable entries shall be
closed with the certifi ed CEAG blanking plug for
metric cable entries.
PE-connection
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2015 Eaton
All Rights Reserved
Printed in Germany
dd
Publication No.
GHG 270 7003 P0001 D/E/F (n)
Auflage/11.15/CS
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12