INSTALLATION AND
OPERATION MANUAL
ͷ Do not store or use gasoline or other
ammable vapors and liquids in the vicinity
of this or any other appliance.
ͷ WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from
a neighbors phone. Follow the gas
suppliers instructions.
If you cannot reach your gas supplier,
call the re department.
ͷ Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
This appliance may be installed in
an aftermarket, permanently located,
manufactured home (USA only) or mobile
home, where not prohibited by local codes.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certied kit is used.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d’installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez
www.kozyheat.com
.
DANGER
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED
NEVER ALLOW CHILDREN
TO TOUCH GLASS
A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this
appliance and shall be installed for the protection
of children and other at-risk individuals.
SPRINGFIELD 36
Model #SFD-36
Direct Vent Gas Fireplace
Hussong Mfg. Co., Inc.
SFD-36 Report No: 19-555
Rev. 4, February 2021
Starting Serial Number: 20 403750 15
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
3
Read this manual before installation or operating this appliance.
Please retain this owner’s manual for future reference.
CON GRAT ULAT ION S!
We welcome you as a new own of a Kozy Heat gas feplace. Kozy Heat products e designed
with supi components and matials, and assembled by ained crasmen who take pride in the
wk. To ense you eceive a quality product, the bn and valve assembly e 100 pcent test-
fed, and the complete feplace is thoughly inspected befe packaging. O commitment to quality
and custom satisfaction has emained the same f ov 40 yes. We o a complete line of gas
and wood feplaces, along with stylish accessies to complement any dec. Adding a feplace is
one of the best ways to increase the value of yo home, and we e proud to o a netwk of deals
throughout the couny to help make yo expience evything you imagine. We pride oselves
in being dedicated not only to functionality and eliability, but also custom safety. We o o
continual suppt and guidance to help you achieve the maximum benet and enjoyment om yo
Kozy Heat gas feplace.
Jim Hussong
President
Dudley Hussong
Board Chairman
Homeowner Reference Information
We recommend you record the following information:
Model Name: ____________________________________________
Serial Number: ___________________________________________
Dealership Purchased from: ________________________________
Date purchased/installed: __________________________________
Location of replace: ______________________________________
Dealer phone: ___________________________________________
Notes: ______________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
TABLE OF CONTENTS 5
TABLE OF CONTENTS
TABLE OF CONTENTS .....................................................................5
1.0 INTRODUCTION ......................................................................7
1.1 Appliance Certication ............................................................................. 7
1.2 California Proposition 65 Warning ........................................................ 7
1.3 Requirements for the Commonwealth of Massachusetts ............ 7
2.0 SPECIFICATIONS .....................................................................8
2.1 Heating Specications .............................................................................. 8
2.2 Electrical Specications ............................................................................ 8
2.3 Appliance Dimensions .............................................................................. 9
2.4 Safety Barrier Dimensions ........................................................................ 10
3.0 FRAMING .................................................................................11
3.1 Installation Planning .................................................................................. 11
3.2 Top Stand-o Brackets, Heat Shield, and Insulation Adjustment .....12
3.3 Nailing Flange Installation ....................................................................... 12
3.4 Clearances to Combustibles ................................................................... 13
3.5 Rough Framing ............................................................................................ 14
3.6 Natural Draft Vent Termination Rough Framing .............................. 15
3.7 Outdoor Covered Fireplace Installation .............................................. 17
3.8 Heat Transfer Kit(s) Cover Plate(s) ......................................................... 19
3.9 Heat Transfer Kit Corner Installation Requirements ...................... 20
4.0 FACING AND FINISHING .........................................................21
4.1 Facing and Finishing Requirements .................................................... 21
4.2 Optional Finishing Trim Kit (FTK): #SF36-FTK .................................... 23
4.3 Safety Barrier Installation ......................................................................... 24
5.0 GAS LINE CONNECTION .........................................................26
5.1 Gas Conversion (sold separately) .......................................................... 26
5.2 Gas Line Installation ................................................................................... 26
6.0 TERMINATION LOCATIONS .................................................... 27
6.1 Vertical Vent Cap Termination ................................................................ 27
6.2 Minimum Termination Clearances ........................................................ 28
7.0 VENTING ..................................................................................29
7.1 Approved Vent Systems ............................................................................ 29
7.2 Venting Requirements .............................................................................. 29
7.3 Vent Restriction .......................................................................................... 30
7.4 Vent Heat Shield Assembly Installation .............................................. 31
7.5 Vent Installation ........................................................................................... 32
7.6 Class A Chimney/Masonry Chimney Conversion ............................ 38
7.7 Coaxial to Co-Linear Chimney Conversion ........................................ 39
7.8 #800-1 Series Direct Vent Termination Kit(s) ..................................... 40
8.0 FIREPLACE SETUP ................................................................... 41
8.1 Glass Frame Assembly ............................................................................... 41
8.2 Light Kit .......................................................................................................... 41
8.3 Bottom Frame Removal and Installation ............................................ 41
8.4 #SF36-500 Log Set Installation ............................................................... 42
8.5 Control Board Removal and Installation ............................................. 43
9.0 ELECTRICAL INFORMATION ..................................................44
9.1 Electrical Specications ............................................................................ 44
9.2 Wiring Requirements ................................................................................. 44
10.0 OPERATING INSTRUCTIONS ................................................ 45
10.1 Setup Proame 2 IFC Module .............................................................. 46
10.2 Initialize the Control System................................................................. 46
10.3 Reset the System for Manual Operation .......................................... 46
10.4 Automatic Safety Restart ....................................................................... 46
10.5 Backup Battery Operation .................................................................... 46
10.6 Control System 7 Day Timeout ............................................................ 46
10.7 IFC Module Ignition Sequence ............................................................ 47
10.8 Additional Diagnostic Information .................................................... 47
10.9 Remote Control Operation .................................................................. 48
11.0 ADJUSTMENT ........................................................................51
11.1 Pressure Testing ........................................................................................ 51
11.2 Burner Flame Adjustments ................................................................... 52
12.0 TROUBLESHOOTING.............................................................54
13.0 MAINTENANCE......................................................................56
13.1 Firebox .......................................................................................................... 56
13.2 Fan ................................................................................................................. 56
13.3 Vent System ................................................................................................ 56
13.4 Glass Assembly .......................................................................................... 56
13.5 Burner and Pilot System ........................................................................ 57
14.0 REPLACEMENT PARTS LIST..................................................58
LIMITED LIFETIME WARRANTY ....................................................59
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
INTRODUCTION 7
1.0 INTRODUCTION
1.1 Appliance Certication
Laboratory: PFS in Cottage Grove, Wisconsin
Standards:
ANSI Z21.88-2017/CSA 2.33-2017, Vented Gas Fireplace Heaters
CSA 2.17 2017, Gas-Fired Appliances for Use at High Altitudes
This installation must conform with local codes, or in the absence of
local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
the Natural Gas and Propane Installation Code, CSA B149.1.
1.2 California Proposition 65 Warning
WARNING: This product can expose you to chemicals including
Carbon Monoxide, that is an externally vented by-product of fuel
combustion, which is [are] known to the State of California to
cause cancer, birth defects or other reproductive harm. For more
information, visit www.P65Warnings.ca.gov.
1.3 Requirements for the
Commonwealth of Massachusetts
The following requirements reference various Massachusetts and
national codes not contained in this manual.
For all sidewall horizontally vented gas fueled equipment installed
in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination
is less than (7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
1.3.1 Installation of Carbon Monoxide Detectors
At time of installation of side wall horizontally vented gas fueled
equipment, the installing plumber or gas-tter shall observe that
a hard wired carbon monoxide detector with an alarm and battery
back-up is installed on the oor level where the gas equipment is
to be installed. In addition, the installing plumber or gas-tter shall
observe that a battery operated or hard wired carbon monoxide
detector is installed on each additional level of the dwelling, building
or structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner
to secure the services of qualied licensed professionals for the
installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed
on the next adjacent oor level. In the event that the requirements
of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to
comply with the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
1.3.2 Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
1.3.3 Signage
A metal or plastic identication plate shall be permanently mounted
to the exterior of the building at a minimum of eight (8) feet
above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print no less the one-half inch (½) in size, “GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
1.3.4 Inspection
The state or local gas inspector of the side wall horizontally vented
gas fueled equipment shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248 CMR 5.08
(2) (a) 1 through 4.
1.3.5 Exemptions
The following equipment is exempt from 248 CMR 5.08 (2) (a) 1
through 4: The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as
adopted by the Board; and Product Approved side wall horizontally
vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for
residential purposes.
1.3.6 Manufacturer Requirements
1.3.6.1 Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally
vented gas equipment provides a venting system design or venting
system components with the equipment, the instructions provided
by the manufacturer for installation of the equipment and the
venting system shall include:
Detailed instructions for the installation of the venting system
design or the venting system components; and
A complete parts list for the venting system design or venting
system.
1.3.7 Gas Equipment Venting
System NOT Provided
When the manufacturer of Product Approved side wall horizontally
vented gas equipment does not provide the parts for venting the
ue gases, but identies “special venting systems, the following
requirements shall be satised by the manufacturer:
The referenced “special venting systems instructions shall
be included with the appliance or equipment installation
instructions and;
The “special venting systems” shall be Product Approved by the
Board, and the instructions for that system shall include a parts
list and detailed installation instructions.
A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting
design instructions shall remain with the appliance or equipment at
the completion of the installation.
8 SPECIFICATIONS
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
2.0 SPECIFICATIONS
2.1 Heating Specications
Natural Gas Propane
Maximum
Input Rating
35,000 Btu/h
(10.3 kW)
35,000 Btu/h
(10.3 kW)
Minimum
Input Rating
18,000 Btu/h
(5.3 kW)
18,000 Btu/h
(5.3 kW)
Manifold Pressure
(High)
3.8” WC
(0.95 kPa)
11” WC
(2.74 kPa)
Manifold Pressure
(Low)
1.1” WC
(0.27 kPa)
2.9” WC
(0.72 kPa)
Orice Size (DMS) #37 #51
2.1.1 Altitude Adjustment
This appliance may be installed at higher altitudes. Please refer to
National Fuel Gas Code ANSI Z223.1/NFPA 54, CSA-B149.1 Natural
Gas and Propane Installation Code, local authorities, or codes having
jurisdiction in you area regarding derate guidelines.
2.1.1.1 US Installations
Refer to the American Gas Association guidelines for the gas designed
appliances derating method. For elevations above 2,000’ (610m),
input ratings are to be reduced by 4% for each 1,000’ (305m) above
sea level.
2.1.1.2 Canadian Installations
When the appliance is installed at elevations above 4,500’ (1,372m),
the certied high altitude rating shall be reduced at the rate of 4% for
each additional 1,000’ (305m).
2.2 Electrical Specications
The junction box in this appliance requires 120VAC, 60Hz, and 6
Amps.
Verify the household breaker is shut o prior to working on any
electrical lines.
The AC power supply to this appliance must be hot at all times
and shall not have a switch installed in it.
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
SPECIFICATIONS 9
2.3 Appliance Dimensions
Figure 2.1, Appliance Dimensions
25⁄
(643mm)
8”
(203mm)
21”
(533mm)
36
¾
(933mm)
30”
(762mm)
14
⁄
(364mm)
2
¼
(58mm)
11
⁄
(293mm)
3
⁄
(96mm)
29
⁄
(752mm)
35
¾
(908mm)
21
⁄
(554mm)
33
⁄
(849mm)
14”
(356mm)
19
¾
(502mm)
2”
(50mm)
LEFT SIDE FRONT VIEW RIGHT SIDE
TOP VIEW
Alternate gas line
access hole
Electrical access
Power vent wire harness hole
(see KPV manual for more information)
Preferred gas line
access hole
Power vent wire harness hole
(see KPV manual for more information)
10 SPECIFICATIONS
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
2.4 Safety Barrier Dimensions
WARNING: A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall be installed for
the protection of children and other at-risk individuals.
If the barrier becomes damaged, the barrier shall be replaced with
Hussong Mfg.s barriers for this appliance. Only doors certied with the
appliance shall be used.
IMPORTANT: Consider the height of hearth nish material when
building a replace platform. Proper installation of safety barriers
require the bottom of the replace to be level with nished hearth.
Please refer to Section 4.3 Safety Barrier Installation on page 24 for
installation and removal instructions.
SF36A-PSF SF36-RSF
SF36A-MSF SF36R-MSF SF36A-FPDSF
SF36R-FPSF SF36-FRSF
32⁄
(829mm)
25
⁄
(657mm)
37”
(939mm)
30
¼
(768mm)
30”
(768mm)
32
⁄
(829mm)
25
⁄
(657mm)
37”
(939mm)
37”
(939mm)
30
¼
(768mm)
30¼
(768mm)
37”
(939mm)
37”
(939mm)
30”
(768mm)
Figure 2.2, Safety Barrier Dimensions
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING 11
3.0 FRAMING
3.1 Installation Planning
This appliance oers several design options for managing the heat
produced by this replace.
Read all documentation for your specic installation
and design options prior to appliance installation.
Heat Transfer Kit(s) allows you to transfer heat to a specic area
inside your home (interior) or directly outside (exterior). This
appliance can have (2) heat transfer kits installed at the same
time. It can be up to two of the same heat transfer kits, or a
combination of interior and exterior kits. See the HTK-EXT and/
or HTK-INT manuals for further information.
If you are planning an installation with the use of an exterior
and/or interior kit, the minimum dimensions listed in this
section will apply for your framing installation.
If you are planning a corner installation with use of an exterior
and/or interior kit, the requirements in Section 3.9 Heat
Transfer Kit Corner Installation Requirements on page 20
must be followed.
Kozy Power Vent is a fan-powered mechanical draft vent system
(horizontal terminations only) for use with any of the design
options listed above. It is easier to convert the replace for use
with the #KPV before framing in the replace. If you convert the
replace for use with the #KPV after replace installation, you will
have to remove the control board. See Section 8.5 Control Board
Removal and Installation on page 43 for access to the control
board before and after installation.
If planning to convert to propane, it is easier to complete the gas
conversion before framing in the replace. See the #LCK-SF36-S
manual for complete conversion instructions. If you convert the
replace to propane after replace installation, you will have
to remove the control board. See Section 8.5 Control Board
Removal and Installation on page 43 for access to the control
board before and after installation.
3.1.1 Appliance Placement Considerations
WARNING: Due to high temperatures, the appliance should be located
out of trac and away from furniture and draperies.
This appliance must be installed on a level surface capable of
supporting the replace and venting. Determine your vent
requirements before framing your appliance.
This replace may be installed in a bedroom.
Please be aware of the large amount of heat this replace will
produce when determining a location.
12 FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
Figure 3.1, Top Stand-o Brackets, Heat Shield, and Insulation Adjustment
BACK VIEW
BACK VIEW
STAND-OFF FLANGE
NAILING FLANGE INSTALLED
NAILING FLANGE
AS SHIPPED
3.2 Top Stand-o Brackets, Heat Shield,
and Insulation Adjustment
The top stand-o brackets, heat shield, and insulation piece provide
the 3-1/2” (89mm) minimum clearance to header and must be installed.
The top stand-o brackets, heat shield, and insulation piece are
shipped in the forward position to accommodate non-combustible
facing material that would overlap the face of the replace.
You may adjust these components back from the replace face to
allow the replace front to be ush with typical 1/2” (12mm) non-
combustible facing material. Follow instructions below.
1. Locate the (2) screws on each side securing the top stand-o
brackets to the heat shield, as shown below. Remove and save
screws.
2. Locate the (3) screws on the ange of the top heat shield, as
shown below. Remove and save screws.
3. Align the heat shield with the holes on the top of the replace
farther back from the front of the replace. Secure with screws
previously removed.
4. Align the holes in the stand-o brackets with the holes farther
back on heat shield. Secure with screws previously removed.
5. Insulation must be pushed tight against non-combustible facing
material.
3.3 Nailing Flange Installation
CAUTION: Never permanently remove these assemblies from the
replace—they must be secured regardless of nish material used.
6. Remove (2) nailing anges from the right and left side of the
replace.
7. Align nailing ange with holes on outside corners of replace,
with the stand-o anges on the nailing anges facing away
from the replace.
8. Secure the nailing anges to the replace with screws (provided)
through the slots in nailing anges.
9. Bend perforation on nailing ange until parallel with replace
face. Do not bend toward replace face.
UNTIL ALL FRAMING REQUIREMENTS ARE COMPLETED:
Position framing stud against the small stand-o (located on
backside of nailing ange). Secure with nails or screws.
When installed, the nailing anges provide the minimum 1/2”
(13mm) clearance from the sides of the replace to framing.
Figure 3.2, Nailing Flange Installation
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING 13
3.4 Clearances to Combustibles
Table 3.1, Minimum Appliance Clearances to Combustible Material
From appliance top stand-o brackets 0” 0mm
From appliance left and right stand-o brackets 0” 0mm
From appliance back stand-o brackets 0” 0mm
From appliance corners 1/2” 12mm
From appliance front 36” 914mm
From appliance top to ceiling 29-1/4” 743mm
A 45° projection from appliance sides 0” 0mm
Appliance sides to an adjacent parallel sidewall 6” 152mm
Fireplace enclosure oor to 3/4” (19mm) trim 35” 889mm
Fireplace enclosure oor to combustible mantel 4” (102mm) deep 37” 940mm
Appliance top to replace enclosure top 29-1/4” 743mm
Minimum height of replace enclosure 59-1/4” 1505mm
1¼
(31mm)
21”
(533mm)
36
¾
(933mm)
66
¼
(1683mm)
14
⁄
(361mm)
½
(12mm)
32
⁄
(829mm)
46
⁄
(1190mm)
1
¼
(31mm)
21”
(533mm)
36
¾
(933mm)
36
¾
(933mm)
TYPICAL VERTICAL INSTALLATION TYPICAL HORIZONTAL INSTALLATION
TYPICAL CORNER INSTALLATION*
*if installing with heat transfer kits, see section 3.8 on page 18
Figure 3.3, Typical Installation Options
14 FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
3.5 Rough Framing
WARNING: Provide adequate clearance in front of the replace for
barrier removal, component access, gas line installation, service
access, etc.
CAUTION: Cold air transfer area. The surround replace chase
must comply with all clearances as outlined in this manual, and be
constructed in compliance with local building codes. Outside walls
should be insulated to prevent cold air from entering room.
Rough framing dimensions should allow for wall covering
thickness and replace facing materials. Adjust rough opening
size as necessary to maintain minimum clearance requirements.
Floor protection in front of the replace is not required.
Combustible material may be used if installing a hearth
extension. Consider the thickness of the hearth extension
nishing material if building a replace platform. The bottom
of the replace must be level with nished hearth extension for
proper t of the safety barriers.
The bottom of the replace must be placed directly on a wood
or non-combustible surface (not linoleum or carpet). If this
appliance is to be installed directly on carpeting, tile, or other
combustible material other than wood ooring, this appliance
shall be installed on a metal or wood panel extending the full
width and depth of the appliance.
This replace may be elevated o the oor, provided it is
properly supported by framing materials and maintains ceiling
clearances. If installed above oor level, a solid, continuous
platform must be constructed below the replace.
If masonry (optional) is to be used, prepare the foundation
necessary for the full masonry load. .
3.5.1.1 TV Recess Construction
WARNING: All clearances to venting must be maintained.
Mounting a television above a replace has become a common
practice. Television surface temperatures are aected by mantel
depth, ceiling heights, and wall and mantel construction material.
Most television manufacturers specify in their instructions that a
television should not be installed on, near, or above a heat source.
Television location rests solely on the homeowner. It is the home
owner’s responsibility that the preferred TV mounting and mantel
design will not exceed the listed maximum operation temperature of
their electronic goods.
Tests performed determined that surface temperatures did not
exceed 150°F (66°C) when a 4¼” (108mm) deep recess is constructed
above the replace.
33½
(851mm)
36
¾
(933mm)
21”
(533mm)
33½
(851mm)
4
¼
(108mm)
59
¼
(1505mm)
21”
(533mm)
36
¾
(933mm)
TV Recess Construction
Single vertical header board
is required to maintain clearances
to combustibles
Figure 3.4, Framing Dimensions and TV Recess Construction
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING 15
3.6 Natural Draft Vent Termination
Rough Framing
The following information applies to all standard, KZK, and vented
options when venting with natural draft. If using Kozy Power Vent
#KPV, please reference the manual included with the kit.
3.6.1 Vent Termination Framing Requirements
This is a cold air transfer area. The replace enclosure must comply
with all clearances as outlined in this manual, and be constructed
in compliance with local building codes. Outside walls should be
insulated to prevent cold air from entering room.
Exterior vent termination location must be in compliance with
Section 6.2 Minimum Termination Clearances on page 28.
IMPORTANT - METAL FAB VENT SYSTEM : When installing Metal Fab
vent pipe, an adapter must be used. This will increase the minimum
height for the center of the vent pipe by 3-1/4” (83mm) when framing
the wall pass through for horizontal terminations.
3.6.1.1 Clearances
A minimum of 1” (25mm) clearance on all sides of the vertical
vent pipe must be maintained.
A minimum of 1” (25mm) clearance from the top surface on the
horizontal pipe must be maintained.
A minimum of 1” (25mm) clearance on the sides and bottom
surfaces on the horizontal pipe must be maintained.
3.6.2 Vertical Terminations
Follow vent pipe manufacturer’s installation instructions for
vertical terminations.
Attic insulation shields may be insulated using unfaced
insulation products listed as non-combustible per ASTM E 136.
3.6.3 Horizontal Terminations
WARNING: Do not recess the vent cap into wall or siding.
IMPORTANT: Horizontal vent sections require 1/4” (6mm) rise for every
12” (305mm) of travel for natural draft applications.
Kozy Heats #800-WPT3, or wall thimble products that comply with
the required 1” (25mm) clearance to combustibles must be installed
for all horizontal vent (rigid or exible) runs that pass through interior
or exterior walls. These wall thimble products may be insulated using
unfaced insulation products listed as noncombustible per ASTM E
136.
Elbows listed with approved vent systems for this appliance vary in
vertical length. Please consult the vent manufacturer’s instructions
to determine the elbow dimension used for installation. Adjust the
wall pass-through rough opening dimensions to maintain clearance
requirements.
3.6.4 Wall Pass Through Framing Instructions
Rigid pipe dimensions are tested with listed Simpson Duravent
pipe. Other manufacturers product dimensions may vary.
Flexible pipe framing dimensions are tested with Kozy Heat #800
Series Flexible Vent System. See the drawing on the following
page.
1. Measure from oor level of the replace to the center of where
the vent pipe will penetrate the wall.
2. Cut and frame an opening in the wall to allow the vent system
to run level through the wall pass-through. A minimum of 1”
(25mm) on all sides of the horizontal pipe at the wall pass-
through must be maintained.
3. Follow the vent pipe manufacturer’s installation instructions for
vent installation.
16 FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
Figure 3.5, Vent Termination Locations
21”
(533mm)
41”
(1041mm)
45”
(1143mm)
1”
(25mm)
1”
(25mm)
1”
(25mm)
1”
(25mm)
21”
(533mm)
NATURAL GAS AND PROPANE RIGID PIPE
MINIMUM HORIZONTAL TERMINATION FRAMING
NATURAL GAS AND PROPANE FLEX PIPE
MINIMUM HORIZONTAL TERMINATION FRAMING
10¾
(273mm)
11”
(279mm)
5
⁄ (138mm)
Required Wall Pass Through
Framing for 1” (25mm) Clearance
(shown with #800-WPT3)
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING 17
A
B
CC
The overhang (A) must be a minimum of 1/2 or
greater of the rooine elevation (B) above the base
of the replace.
The width of the overhang to each side of the
appliance (C) must be a minimum of 1/2 or
greater of the rooine elevation (B) above the
base of the replace.
EXAMPLE: If rooine (B) is 10’ above the base of replace, the overhang (A) must be 5’
or greater. The width of the overhang to EACH side of the replace (C) must be 5’ or greater.
SIDE OF
FIREPLACE
BACK OF
FIREPLACE
FRONT OF
FIREPLACE
ROOF OVERHANG
3.7 Outdoor Covered Fireplace Installation
An outdoor covered replace installation allows a replace to be
installed in an outdoor covered area, where the appliance is protected
from direct precipitation.
Follow the instructions and illustrations on this page and the
following page for installation procedures.
3.7.1 Safety Screen Barriers
Hussong Mfg. Co., Inc. highly recommends to use black painted
safety barriers in outdoor installations. Other screen barriers that
incorporate a plated or patina nish are highly susceptible to
oxidation and discoloration.
3.7.2 Requirements
The continuous insulated building envelope and weatherproof
membrane are not to be interrupted by replace installation. See
Figure 3.6 on the following page.
Fireplace operation is approved from 40°F to 110°F.
All wiring connections shall be in accordance with outdoor
requirements of NECA NFPA 70.
All clearances and requirements in your appliance manual must
be adhered to.
Figure 3.6, Outdoor Covered Fireplace Install
18 FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
Continuous insulated building
envelope and weatherproof
membrane are not interrupted by
replace installation
Free standing structure
(weatherproof enclosure)
Minimum weatherproof
overhang in front and sides
Minimum weatherproof
overhang in front and sides
Minimum weatherproof
overhang in front and sides
Minimum weatherproof
overhang in front and sides
INSIDE
OUTSIDE
INSIDE
Figure 3.7, Outdoor Covered Installation 2 (your replace may look dierent than the one shown)
3.7.3 Outdoor Covered Fireplace Installation (continued)
#SFD-36 R.4 February 2021 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING 19
3.8 Heat Transfer Kit(s) Cover Plate(s)
IMPORTANT: Only remove the cover plates that are required specically
for your application or installation.
3.8.1 Exterior and Interior Heat
Transfer Kit Cover Plate(s)
Figure 3.8 shows removal of the Heat Transfer Kit cover plates. There
are (2) square cover plates located on either side of the outer shell of
the appliance. This appliance can have (2) Heat Transfer Kits installed
at the same time. It can be up to two of the same heat transfer kit or a
combination of interior and exterior kits.
Figure 3.8, Cover Plate Removal
20 FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces #SFD-36 R.4 February 2021
3.9 Heat Transfer Kit Corner
Installation Requirements
You will not be able to install at minimum horizontal venting if you
are planning to install (2) heat transfer kits. The vertical vent height
length must be increased. See Figure 3.9. If using (1) heat transfer
kit, the vent termination must be on the opposite side of the heat
transfer kit air chute. See Figure 3.10.
Corner installations have dierent minimum requirements to allow
space for the installation of the SFD-HTK air chute. See Figure 3.10.
Figure 3.9, Corner Installation Vertical Vent Height with (2) Heat Transfer Air Chutes
Figure 3.10, Typical Corner Installation Minimum Dimensions with (1) Air Chute
71⁄
(1807mm)
36
¾
(933mm)
35”
(890mm)
50
¼
(1277mm)
½
(12mm)
15
⁄
(403mm)
Typical Corner Installation with (1) Air Chute Installed
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Kozyheat Springfield 36 Owner's manual

Category
Fireplaces
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI