Refrigerant Charge (lbs.)
Liquid Line Connecon (in., O.D.)
Vapor Line Connecon (in., O.D.)
Maximum Total Piping² (.)
Min. / Max. ODU to IDU Piping (.)
Piping Length (no add’l refrigerant, .)
Maximum Elevaon between ODU and IDU (.)
Maximum Elevaon between IDU and IDU (.)
For: File Resubmit
Approval Other
Job Name/Locaon:
Date:
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
Tag No:
Features:
For a complete list of available accessories, contact your LG representave.
For connual product development, LG reserves the right to change specicaons without noce.
© LG Electronics U.S.A., Inc., Englewood Clis, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Oponal Accessories:
Performance:
Cooling Capacity (Min.‐Rated‐Max., Btu/h)
Heang Capacity (Min.‐Rated‐Max., Btu/h)
Max. Heang Capacity at 5°F (Btu/h)
Max. Heang Capacity at 0°F (Btu/h)
Max. Heang Capacity at ‐4°F (Btu/h)
EER2
SEER2
COP
HSPF2
Electrical:
Power Supply (V/Hz/Ø)1
MOP (A)
MCA (A)
Recommended Fuse Size (A)
Cooling Rated Amps (A)
Heang Rated Amps (A)
Compressor (A)
Fan Motor (A)
Locked Rotor Amps (A)
208‐230V, 60, 1
Page 1 of 2
Cooling (°F DB)
Heang (°F WB)
14 to 118
‐4 to +64
Operang Range:
Unit Data:
Type
Quanty
Oil / Type
Twin Rotary
1
FVC68D
Compressor:
PI‐485 ‐ PMNFP14A1
MulSITE Comm. Mgr. ‐
PBACNBTR0A
AC Smart 5 ‐ PACS5A000
ACP 5 ‐ PACP5A000
Power Distribuon Indicator (PDI)
Premium ‐ PQNUD1S41
Mobile LGMV ‐ PLGMVW100
Piping:
• Auto operaon
• Auto restart
• Inverter (variable speed
compressor)
• Defrost / Deicing
• Restart delay (three [3] minutes)
• Self diagnosis
• So start
• Low ambient cooling down to 14°F
Cooling Nominal Test Condions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Heang Nominal Test Condions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
Notes:
1. Acceptable operang voltage: 187V ‐ 253V.
2. Piping lengths are equivalent.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
4. All power / communicaon cable to be minimum 14 AWG, 4‐conductor, stranded,
shielded or unshielded wire, and must comply with applicable local and naonal
codes. If shielded, the wire must be grounded to the chassis at the outdoor unit
only.
5. Power wiring size must comply with the applicable local and naonal codes.
6. This data is rated 0 . above sea level, with 0 . level dierence between outdoor
and indoor units, and the following refrigerant pipe lengths:
LMU183HV: 16.4 . x 2 = 32.8 .
LMU243HV: 16.4 . x 3 = 49.2 .
LMU303HV: 16.4 . x 4 = 65.6 .
LMU363HV: 16.4 . x 4 = 65.6 .
All capacies are net with a combinaon rao between 95 ‐ 105%.
7. Must follow installaon instrucons in the applicable LG installaon manual.
8. Refer to the Combinon Data Manual for combinaon capacity tables.
9. See the Performance Data Manual for sensible and latent capacies.
Refrigerant Type
Refrigerant Control
Sound Pressure (Cool / Heat) ±1 dB(A)3
Net / Shipping Weight (lbs.)
Heat Exchanger Coang
Minimum No. of Indoor Units
Maximum No. of Indoor Units
Type
Quanty
Motor / Drive
Max. Airow Rate (CFM)
Propeller
1
Brushless Digitally Controlled/Direct
Fan:
9.8 / 82.0
49.2
24.6
MOP ‐ Maximum Overcurrent Protecon MCA ‐ Minimum Circuit Ampacity
ODU = Outdoor Unit IDU = Indoor Unit
R410A
EEV
Gold Fin™
2
Multi F Inverter Heat Pump Outdoor Unit
Drain Pan Heater - PQSH1203
Low Ambient Baffle Kit (Cooling
operation to -4°F) - ZLABGP03A
SB_MultiF_LMU243HV_2022_07_18_084711