Mega220VSingleZoneInverter
LS090HEV1
Performance:
Ca
p
acit
y
(
Min
/
Rated
/
Max
)
(
Btu
/
h
)
3,070~8,500~9,500
SEER
19.0
EER
12.5
Cooling:
Heating:
Capacity(Min/Rated/Max)(Btu/h)
3,070~9,000~10,500
HSPF
9.0
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB
Indoor:
70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB
Outdoor:
47°FDB/43°FWB
Electrical:
MCA(A)
10
MOP(A)
15
Compressor(A)
7.0
FanMotor(A)
0.5
OutdoorUnit:
CoolingRatedAmps(A) 7.5
HeatingRatedAmps(A)
7.5
CoolingPowerInput(kW)
0.68
HeatingPowerInput(kW)
0.78
Piping:
LiquidLine(in,OD)
1/4
AdditionalRefrigerant(oz/ft)
0.22
MaxElevation(ft)
22.9
PipingLength(noadd'lrefrigerant,ft)
24.6
ControlsFeatures:
Page1of3
SBSZMega220LS090HEV1415
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,En glewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com.
PowerSupply(V¹/Hz/Ø) 208230/60/1
208230/60/1
VaporLine(in,OD)
3/8
MaxPipeLength(Min/Max)(ft)²
9.8/49.2
OperatingRange:
OutdoorUnit:
Cooling(°FDB)
14118
Heating(°FWB)
1465
Cooling(°FWB)
5375
Heating(°FDB)
6086
IndoorUnit:
UnitData:
RefrigerantType
R410A
RefrigerantCharge(lbs)
1.87
Fan:
Notes:
1.Acceptableoperangvoltage:187V253V.
2.Pipinglengthsareequivalent.
3.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
4.Allpower/communicaoncabletobeminimum18AWG,4conductor,stranded,shielded
andmustcomplywithapplicablelocalandnationalcode.
5.SeeEngineeringManualforsensibleandlatentcapacies.
6.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
7.Theindoorunitcomeswithadryheliumcharge.
8.Thisdataisrated0abovesealevel,with24.6ofrefrigerantlineanda0leveldierence
betweenoutdoorandindoorunits.
9.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
ODUType
Propeller
IDUType
CrossFlow
Motor/Drive
BrushlessDigitallyControlled/Direct
Dehumidification(pts/hr)
2.12
RefrigerantControl
EEV
HeatExchangerCoating
GoldFin™
ODUSoundPressure(±3dB(A))³
47
ODUNetUnitWeight(lbs)
62
ODUShippingWeight(lbs)
67
IDUShippingWeight(lbs)
20
FanSpeeds(Fan/Cooling/Heating)
4/4/4
Quantity(ODU+IDU)
1+1
IDUAirFlowRateH/M/L(CFM)
276/226/177
ODUMaxAirFlowRate(CFM)
953
IndoorUnit(IDU)‐LSN090HEV1OutdoorUnit(ODU)‐LSU090HEV1
SEER‐SeasonalEnergyEfficiencyRatio EER‐EnergyEfficiencyRatio
HSPF‐HeatingSeasonalPerformanceFactor
MOP‐MaximumOvercurrentProtection MCA‐MinimumCircuitAmpacity
IDUSoundPressure±3(H/M/L/Sleep)dB(A)³
39/33/25/19
IDUNetUnitWeight(lbs)
17
•24Houron/offmer
•2Way(up/down)auto
swing
•Autochangeover
•Autorestart
•Condensatesensor
connection
•Energysaving
•Inverter(variablespeed
compressor)
•Jetcool/Jetheat
•Selfcleaningindoorcoil
•Sleepmode
•Ultraquietoperaon
TotalPowerInput:
JobName/Location:
Tag#:
Date:
PONo.:
Mega220VSingleZoneInverter
Page2of3
SBSZMega220LS090HEV1415
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,En glewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com.
OutdoorUnit(ODU)‐LSU090HEV1
JobName/Location:
Tag#:
Date:
PONo.:
Mega220VSingleZoneInverter
Page3of3
SBSZMega220LS090HEV1415
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,En glewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com.
IndoorUnit
(
IDU
)
‐LSN090HEV1
  • Page 1 1
  • Page 2 2
  • Page 3 3

LG LS090HEV1 LS090HEV1 Submittal

Category
Split-system air conditioners
Type
LS090HEV1 Submittal

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI