— The cable is laid in equal spacing without being
overlapped. Laying pitch of the section is constant
and can be calculated by formula:
Pitch (cm) = (100 xS) / L,
where Sis the actual area in sq. m on which the
section is laid, and Lis the section length in m(that
is indicated in its Technical Certificate).
Reel out the heating cable rather that drop it down
from the reel to prevent cable twisting. Make sure
that the gage was located between two loops of the
heating cable.
Put the cable evenly without intercrossing. Strictly
adhere to cable spacing within heated area.
Maximum allowed spacing deviation is ±10 mm.
Minimum allowed distance between cable
loops is 60 mm (along no less than 0.5 m
stretch). Fix the ends of the cable loops with
assembly tape lugs taking care not to damage the
heating cable jacket. Loops shall bend evenly, with
out sharp turns or cable tension. Splicing and ter
minal boxes of the section shall be on the floor.
JCheck for damages of the heating section after it
has been installed. You will need to measure heat
ing section resistance between insulated wires of
the mounting cable. It shall correspond to the value
stated in the certificate of the heating section. After
that connect wires of the mounting cable in the
insulation and measure resistance between them
and a copper conductor without insulation. This