8
Safetyinstructions
Beforecommencementofanyworksonthe
electricalequipment,makesurethatthevoltage
iscompletelyswitchedoff.Damaged,burned,
frayedcablesaswellaslooseanduntightcable
connectionsmustbeimmediatelyreplacedbya
skilledelectrician.
Intheeventofadefectivefuse,theymustbe
replacedonlywiththeoriginalfuseswithprescri-
bedamperage.
3.5 Safety installations
ThecommissioningoftheFullyCondensing
Boilerwithoutaproperlyfunctioningsafety
installation(orwithanimproperlyfunctioning
safetyinstallation),isnotpermitted.
Attention
3.5.1 Water-side safety installations
SafetyinstallationspursuanttoDIN12828such
asthesafetyvalve,safetytemperaturelimiter
andtemperaturecontrolleraredescribedin
detail.
3.5.2 Gas-side safety installations
Tothesesafetyinstallationsbelongstheuegas
safetytemperaturelimiter(STL).
3.5.3 Labelandoperatinginstructions
ThelabelmustnotberemovedfromtheBK
FullyCondensingBoiler;itshouldbekeptina
wellreadablecondition.(Theoperatinginstruc-
tionsmustbeplacedvisiblyinthesameroom
wheretheboilerislocated).
3.5.4 Additional safety installations
Thesesafetyinstallationsinclude,amongother
equipment.
• Furnaceemergencyswitch
• Heatingoillockingdeviceinthefurnace
• Impermeablecovers/grillsinconformity
withDINEN294ontheuegassystem
(uponarrangementasanoutdoorchimney)
andontheairsupplyconnectionshould
beinstalledbyatechnician,underhisown
responsibility,incompliancewithlocalregu-
lationsandguidelines(FeuAO).
TheBKFullyCondensingBoilerservesexclu-
sivelyforheatgenerationandalsoforwater
heatingpursuanttoDIN12828.Theowtem-
peratureismaximum80°C,thetechnicaldata
ofvariousboilertypesareindicatedonthecor-
respondinglabels.Onlythoseliquidorgaseous
fuelsthatareindicatedintheorderconr-
mationmaybeusedasworkingmaterials.
functionsandtocheckthetightnessoftheFully
CondensingBoileranditsconnections.
Intheeventofunusualoperatingperformance
inthefunctioningoftheFullyCondensing
Boiler,forexample,malfunctionsorfaultsin
energysupply,theunitmustbeimmediately
shutoff.
Attention
Determinethecauseoftheproblemorfault
andxitinasafeandsecuremanner.Startre-
commissioningonlyaftercompleteeliminationof
faults.
3.4.1 Burner faults/remote unlocking
Incaseofaburnerdefectorfault,theredpush
buttoninthecontrolpanelwillash.Pressthe
buttonshortlytounlocktheburner.Shouldthe
burnerfaultreappear,callaqualiedspecialist.
Fig. 2: Donotpressthepushbuttonduringnormal
burneroperation!
Pushbuttonofremoteunlocking
3.4.2 Maintenance (servicing)
Itisstronglyrecommendedtoconsider,during
eachinspectionand/orscheduledmaintenance
works,suggestionswithrespecttocausesof
faultsduetosuperuousmeasuresand,inparti-
cular,toboileropening,mostlyunnecessary.
AllconnectionsattheFullyCondensingBoi-
ler,burner,controlpaneletc.arepluggableor
screwable.
Whenreplacingsafetyinstallationsmakesure
thatthenewcomponentscorrespondtothe
originalpartsandaretestedinconformitywith
DINEN14597orDIN12828.
Use only genuine components and parts deli-
veredbythe company.
Duringanyoperations,refrainfromusingexces-
siveforce–ifitgoesbeyondwhatisnecessary
toconnectordisconnectboltedconnections–
thereisariskofmaterialdamage!
Itisnotallowedtomoistentheplasticcompo-
nents(secondaryheatexchanger,uegas
system,hoses,sealsetc.)withoils,solvents,
cleaningagentsorotherchemicalsubstances.
Allworksontheelectricalequipmentshouldbe
performedonlyafterhavingdisconnecteditfrom
thepowersupplyandonlybyaskilledelectri-
cian.