Fire Detection & Alarm System Control Panel V1.000
Engineering & Commissioning Instructions
(TO BE RETAINED BY THE COMMISSIONING ENGINEER)
26/10/09 #1
ZetaNET Control Panel Installation Instructions
GLT Exports Ltd Protection Limited
GLT Exports Ltd policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst
every care has been taken to ensure that the contents of this document are correct at time of publication, GLT Exports Ltd shall be under no
liability whatsoever in respect of such contents.
Due to the complexity and inherent importance of a life risk type system then training on this equipment is essential, and commissioning
should only be carried out by competent persons.
GLT Exports Ltd cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation.
E&OE.
GLT Exports Ltd equipment is protected by one or more of the following patent no’s: GB2426367, GB2370670, EP1158472, PT1035528T,
GB2346758, EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690
2
ZetaNET Control Panel Installation Instructions
Contents
Introduction . . . . . . . . . 5
System Design . . . . . . . 5
Equipment Guarantee . . . . . . 5
Anti Static Handling Guidelines . . . . 5
The ZetaNET System . . . . . . . . 6
Advantages of Addressable Systems . . . . . 6
Control Panel . . . . . . . . . 7
Mounting the Control Panel . . . . . 7
General Assembly . . . . . . 7
Physical Dimensions . . . . . . . 8
Topology and Cabling . . . . . . . 9
Loop Loading . . . . . . . 10
System Schematic . . . . . . . 11
Control Panel Main PCB. . . . . . 12
Control Panel Terminal . . . . . . . 14
Power Supply Unit . . . . . . . . 21
General Assembly . . . . . . . 21
Physical Dimensions . . . . . . . 22
Mains Supply & Batteries . . . . . . 23
PSU Termination Schematic . . . . . . 24
PSU Terminals . . . . . . . . 25
Network . . . . . . . . . 27
Topology and Cable Specification . . . . . 27
Network Connection Schematic . . . . . . 28
Network Terminals . . . . . . . 29
General Operation of Control Panel . . . . . . 30
Control Panel Front . . . . . . . 30
LED Indication . . . . . . . . 31
Fire Alarm Controls . . . . . . . 33
System Controls . . . . . . . 33
Access Levels and Codes . . . . . . 33
Access Level 1 (Normal) . . . . . . 34
Access Level 2A (User) . . . . . . . 34
Access Level 2B (Supervisor . . . . . . 35
Access Level 3 (Engineer) . . . . . . 39
Alarm Confirmation . . . . . . . . 45
Alarm Confirmation Delay . . . . . . 46
Selecting the Devices. . . . . . . . 46
Commissioning . . . . . . . . 47
Installation 1
st
Stage . . . . . . . 47
Installation 2
nd
Stage. . . . . . . . 47
Initialisation . . . . . . . . 47
Commissioning . . . . . . . . 48
Configuration Example . . . . . . . 49
End User Training . . . . . . . 49
3
ZetaNET Control Panel Installation Instructions
Good Practice . . . . . . . . 50
Number of Devices . . . . . . . 50
Label the Loop Ends . . . . . . . 50
Note the loop readings . . . . . . . 50
Configuration Printout and Drawings . . . . . 51
Initialisation . . . . . . . . 52
Loop Connections . . . . . . . 52
Normal Readings . . . . . . . 53
Initialisation . . . . . . . . 53
Initialisation faults . . . . . . . 54
Earth Faults . . . . . . . . 56
General Fault Finding . . . . . . . . 57
Common Faults . . . . . . . 57
Intermittent and Recurring Faults . . . . . 57
Summary of Faults . . . . . . . 59
Advanced Connections . . . . . . . 62
Monitored relays . . . . . . . 62
Technical Data . . . . . . . . 63
Control Panel . . . . . . . . 64
System Version Compatibility . . . . . . 64
Resistor Colour Codes . . . . . . . 64
Technical Support . . . . . . . 64
Battery Calculations . . . . . . . 65
Installation Checklist . . . . . . . 66
Commissioning Checklist . . . . . . 67
Loop Continuity and Insulation Test Results. . . . . 68
PSU Cable Continuity and Insulation Test Results . . . 69
Network Continuity and Insulation Test Results . . . . 70
Fire Alarm System Notice . . . . . . 71
Device Details . . . . . . . 73
Important Points . . . . . . . 76 – Back Page
4
ZetaNET Control Panel Installation Instructions
Introduction
This Manual is intended as a guide to the engineering and commissioning principles of the ZetaNET
Addressable Intelligent Fire Alarm and Detection system, and covers the system hardware information only.
Due to the complexity and inherent importance of a system covering a ‘Life Protection Risk’, training on this
equipment is essential, and commissioning should only be carried out by competent and approved persons.
For further details of the availability of commissioning services contact your supplier.
System Design
This document does not cover Fire Alarm system design, and a basic understanding is
assumed.
A knowledge of BS5839: Pt 1: 2002: Fire Detection and Alarm Systems for
Buildings is essential.
It is strongly recommended that a suitably qualified and competent person is consulted
in connection with the Fire Alarm System design and that the entire system is
commissioned in accordance with the current national standards and specifications.
Equipment Guarantee
The equipment carries no warranty unless the system is installed, commissioned and
serviced in accordance with this manual and the relevant standards by a suitably
qualified and competent person or organisation
Anti Static Handling Guidelines
Immediately prior to handling any PCBs or other static sensitive devices, it is essential
to ensure that a personal connection to earth is made with an anti-static wrist-
strap or similar apparatus.
Always handle PCBs by their sides and avoid touching any components. PCBs should
also be stored in a clean dry place, which is free from vibration, dust and excessive
heat, and protected from mechanical damage.
Warning
Do not attempt to install this equipment until you have fully read and
understood this manual.
Failure to do so may result in damage to the equipment and could invalidate the
warranty.
Technical support will not be available if the instruction manual has not been read and
understood. Please have this instruction manual available whenever you call for
technical support.
For further technical support please contact your distributor. Do not call the GLT
Exports Ltd Protection technical support department unless your distributor has first
given their advice and attempted to rectify the issue.
The ZetaNET System
5
!
!
!
!
ZetaNET Control Panel Installation Instructions
The ZetaNET system is an addressable intelligent detector system, with many advantages over the
traditional addressable analogue detector systems. In order to understand the benefits let us look more
closely at the terms Fire Detector and Fire Sensor. These terms are often used interchangeably but
actually have quite different meanings. A fire detector is the device (component as defined in EN54) which
automatically detects a fire. In the majority of addressable fire detection systems, the fire devices are in fact
fire sensors which only transfer data relating to smoke and heat levels to the control panel, and the fire
decision is made by the panel.
Nearly all current addressable systems are Addressable Analogue Detector Systems where the control
panel continually scans the fire sensors, processes the returned data, and makes decisions about fires and
faults.
The ZetaNET system is defined as an Addressable Intelligent Detector System, or an Addressable Fire
Detection and Alarm System with Independent Distributed Intelligence. Distributed intelligence
signifies that the signal processing is spread throughout the system, in order that the decisions about fires
and faults are taken within the detector itself. The detector is capable of being remotely programmed for
different modes of detection.
Thus the ZetaNET system is indeed an analogue addressable system, but with the processing power
distributed across the entire system. This dramatically reduces the complexity of the control panel and the
data traffic, and improves the efficiency of the system.
The system addressing is carried automatically upon initialisation from the control panel, and does not need
to be programmed manually at each device.
Advantages of Addressable Systems.
The nature of a microprocessor control system with individually identified devices means that the precise
location of fires and faults may be indicated, more complex actions may be implemented, system flexibility
is improved and installation and cabling costs are reduced.
In the ZetaNET system, very efficient communications mean that very low quiescent power consumption
maximises the standby capacity, high power transfer capabilities allow more sounders to be connected to
the loop, and a very fast response to events is achieved as the control panel does not have to poll every
device for status data.
6
ZetaNET Control Panel Installation Instructions
Control Panel
Mounting the Control Panel
Firstly identify the proposed location for the control panel. Ensure that the control panel will be easily
accessible, and that account is taken of any subsequent work that may affect access. It should be located
at the most likely point of access for the fire services.
The control panel should be mounted on a flat, vertical wall at a height where the indicators may be seen
without difficulty.
Like all electronic equipment, the control panel may be affected by extreme environmental conditions. The
position selected for its installation should therefore be clean and dry, not subjected to high levels of
vibration or shock and at least 2 meters away from any pager or radio transmitting equipment. Ambient
temperatures should be within the range given within the Technical Data section, i.e., not directly over a
radiator or heater.
In common with all microprocessor-controlled panels, the control panel may operate erratically or may be
damaged if subjected to lightening induced transients. Proper earth/ground connections will greatly reduce
susceptibility to this problem.
General Assembly
7
ZetaNET Control Panel Installation Instructions
Cabinet Installation
The four back plate holes should be used to secure the cabinet to a solid wall using suitable screws of at
least 50mm in length.
Physical Dimensions
8
50mm
50mm
ZetaNET Control Panel Installation Instructions
Topology & Cabling
All system wiring should be installed to comply with BS 5839: Pt 1: 2002 and BS 7671 (wiring regulations)
and any other standards relevant to the area or type of installation. A cable complying with the BS 5839: Pt
1: 2002 Category 1 (cables required to operate for prolonged periods during fire conditions) is required.
This must be a 2-core 1.5mm
2
screened fire resistant cable.
The addressable circuit must be installed as a loop with a maximum loop length of up to 2 km. Addressable
spur circuits (covering up to a maximum of one detection-zone only per spur circuit and up to a maximum
of 100m in length) may be connected at each Multipoint detector, as long as the combined addressable
circuit length does not exceed 2 km.
The network cable should generally be installed as a single ring, but due to the provision of four network
ports at each panel, sub rings may be installed if required. Whilst radial circuits may be implemented
successfully, they are generally not recommended as they are less fault tolerant and lack system integrity.
Network connections must be installed with a maximum length of 500m between network ports.
The Power Supply Unit requires both a data connection and dual power connections. Thus, one x 2 core
1.5 mm
2
screened fire resistant cable must be installed between the PSU and the Control Panel for data
connections, and 2 x 2.5 mm
2
screened fire resistant cable must be installed between the PSU and the
Control Panel for 24v DC power connections.
In order to protect against possible data corruption it is important ensure the following points are adhered
to:
1. The addressable circuit (loop) cable screen must be connected to earth/ground at the
control panel at each end using the terminals provided.
2. The addressable circuit (loop) cable screen must not be connected to earth/ground at any point
other than the control panel, ie, do not connect the screen to a device back box.
3. The cable screen continuity must be maintained at every point of the loop, using the
terminals provided or a suitable connection block.
4. Do not use a 4-core cable as a loop feed & return due to the possibility of data corruption. It is
essential that two 2-core cables are used if this is required.
5. The network connection cable screens must be connected to earth/ground at the control
panel at one end only using the terminals provided.
Refer to the following wiring schematics for further details.
9
ZetaNET Control Panel Installation Instructions
Loop Loading
In order to allow a method of calculating the maximum loop loading that the system will support, each
device has a rating assigned in Alarm Loading Units (ALUs). A maximum of 175 ALU are permissible on
the loop. This only relates to the load presented in alarm and does not necessarily affect an input device.
The ZetaNET OSP programming software automatically keeps control of the quantity and will provide
prompts if the limits are reached.
DESCRIPTION ALU RATING
Sounder Low 0.5
Sounder Medium 1
Sounder High 2
Beacon 1
Loop I/O Module 1
Conventional Zone Module: Powered from loop 10
Conventional Zone Module: Powered remotely 1
Note: Whilst the system will operate a maximum of 800 devices per control panel, for compliance with
EN54: Part 2: 1997 it is recommended that a limit of a maximum of 512 detection devices is adhered to.
This includes detectors and manual call points, but does not affect the number of sounders or other alarm
devices on the system.
10
ZetaNET Control Panel Installation Instructions
System Schematic
11
ZetaNET
CONTROL
PANEL
ZetaNET
PSU
1 X 2C1.5
2 X 2C2.5
ZetaNET
CONTROL
PANEL
ZetaNET
PSU
1 X 2C1.5
2 X 2C2.5
ZetaNET
CONTROL
PANEL
ZetaNET
PSU
1 X 2C1.5
2 X 2C2.5
ADDRESSABLE LOOPS
ALL 2C1.5
ADDRESSABLE LOOPS
ALL 2C1.5
ADDRESSABLE LOOPS
ALL 2C1.5
NETWORK
2C1.5
ZetaNET
PSU
(OPTIONAL
UP TO 4 MAX
PER PANEL)
ZetaNET
PSU
(OPTIONAL
UP TO 4 MAX
PER PANEL)
ZetaNET
PSU
(OPTIONAL
UP TO 4 MAX
PER PANEL)
1 X 2C1.5
2 X 2C2.5
1 X 2C1.5
2 X 2C2.5
1 X 2C1.5
2 X 2C2.5
ZetaNET Control Panel Installation Instructions
Control Panel Main PCB Located on the inside of the front left hand inner door.
12
USER FUNCTION
BUTTON
LED PANEL
ZONE LEDS
CON
TRAS
T
LCD BACKLIGHT
NOT USED
LCD
RIBBON
RIBBON A
TO
TERMINATIO
N PCB
RIBBON B
TO
TERMINATIO
N PCB
RIBBON C
TO
TERMINATIO
N PCB
RIBBON D
TO
TERMINATIO
N PCB
PRIINTE
R PORT
NETWO
RK
CARD
KEY
SWITCH
REMO
VE
LINKS
TO
PROG
RAM
EXTER
NAL
FLASH
PSU
CO
NTR
OL
COMMS
CONTROL
EXTERNAL
FLASH
EEPRO
M
EEPRO
M
EXTERNAL
FLASH
RAM
RAM
BUZZ
ER
KEYSWIT
CH
MAIN
PROCESS
OR
10-0049
Issue E
INTERNAL FLASH
SETUP
DO NOT CONNECT
PSU
CONTROL
SETUP
DO NOT
CONNECT
ZETANET CIE PCB
POWER
TEST
DISABLED
FAULT FIRE
10-0050 Issue
A
ZETANET LED PCB
ZETANET LCD
LCD
BACKLI
GHT
CONNE
CTION
LCD
RIB
BO
N
LED
RIB
BO
N
LED PCB
Display
Main Control Panel
Ribbon connectors
to Termination PCB
ZetaNET Control Panel Installation Instructions
Control Panel Firmware Upgrade Link Pins
The loop card firmware may be upgraded on site if required using the External Flash Upgrade software.
The two link pins MUST be left in position for correct field operation.
LCD Contrast
The LCD contrast may be adjusted by rotating the screw on the variable resistor located in the upper left
hand corner of the main PCB. This may require many (10 to 20) rotations if the contrast is particularly out of
adjustment.
13
LCD CONTRAST
VR1
Rotate clockwise to
increase the contrast
(darken text)
Rotate anticlockwise
to reduce the
contrast (lighten text)
ZetaNET Control Panel Installation Instructions
Control Panel Terminals
Located on the back plane at the rear of the main control panel back box.
14
RIBBON CABLE CONNECTIONS TO MAIN CONTROL PCB MOUNTED ON DOOR
BACK PLANE CONNECTION PCB
2 3
SCRN
B
A
SCRN
0V
+24V
SCRN
0V
+24V
SERIAL
10K EOL
10K EOL
3K3 EOL
680R
N/O
3K3 EOL
680R
N/O
3K3 EOL
680R
N/O
3K3 EOL
680R
N/O
Date
No
of
devices
Enginee
r
23/04/
04
96
J
William
s
31/04/
05
103
T
Robert
s
o o o o o o o o o o o
o o o o o o o o o o
o
o
o
o
o
o
o
o
o
BUFFER
MICRO
PROC
BUFFER
POWER
FET
POWER
FET
FIRMWARE UPGRADE
FACTORY USE ONLY
SERIAL PORT
BOTTOM EDGE
PRESS HERE ONLY
PRESS HERE ONLY
TOP EDGE
LOOP CARD
ZetaNET Control Panel Installation Instructions
Loop Card Serial Port
The serial port may be used for connection to a computer running the Diagnostic software in order
to interrogate the loop communications.
Loop Card Firmware Upgrade Link Pins
The loop card firmware may be upgraded at the factory only. The link pin should be left in the
position shown for correct field operation.
Outputs 1 and 2: SPR, COM, NC, NO, SCRN
Outputs 1 and 2 are derived from single pole change over ‘volt-free’ relay contacts which are not fault
monitored. The relay contacts are rated at 30vDC / 2A max.
The default setting for output 1 causes the relay to operate as a Common Fire output where the relay is
energised in the fire condition. The default setting for output 2 causes the relay to operate as a Common
Fault output where the relay is de-energised in the fault condition Various other states may also be set
using the ZetaNET OSP programming software.
Terminal Description
SPR Spare terminal for general use. Not connected internally.
COM Common contact
NC Normally closed contact
NO Normally open contact
SCRN Field cable screen connection
Outputs 3 and 4: COM, NC, NO, SCRN
Outputs 3 and 4 are single pole change over ‘volt-free’ relay contacts which are not fault monitored. The
relay contacts are rated at 30vDC / 2A max.
The default setting for output 3 causes the relay to operate as a Common Fault output where the relay is
de-energised in the fault condition. The default setting for output 4 causes the relay to operate as a
Common Fault output where the relay is de-energised in the fault condition. Various other states may also
be set using the ZetaNET OSP programming software.
Terminal Description
COM Common contact
NC Normally closed contact
NO Normally open contact
SCRN Field cable screen connection
15
NOT
CONNECTED
SPARE
COMMO
N
NORMALLY
OPEN
NORMALLY
CLOSED
SCREEN
ON BOARD PCB
FIELD
CONNECTIONS
COMMO
N
NORMALLY
OPEN
NORMALLY
CLOSED
SCREEN
ON BOARD PCB
FIELD
CONNECTIONS
Date
No
of
devices
Enginee
r
23/04/
04
96
J
William
s
31/04/
05
103
T
Robert
s
ZetaNET Control Panel Installation Instructions
Outputs 5 and 6: MO+, MO-, SCRN
Outputs 5 and 6 are monitored circuits which may be configured to monitor for open and short circuit faults
with a 10K EOL resistor, and to be activated with a stage 3 alarm.
The default setting for outputs 5 and 6 causes the circuits to operate as Common Fire Sounder Circuits,
where the outputs step up to 28V DC in the alarm condition. Various other states may also be set using the
ZetaNET OSP programming software.
These outputs are protected by the 315mA T fuses labelled F1 and F2.
Terminal Description
MO+ Monitored Output positive connection
MO- Monitored Output 0V connection
SCRN Field cable screen connection
Auxiliary Power: +12V, 0V, SCRN
An auxiliary 24v DC constant power supply is available to power ancillary devices requiring 24V DC. In
order to protect battery standby and alarm times, this output is limited to 315mA with the fuse labelled F3. It
is suggested that additional Power Supply Units be installed to provide power for additional loads.
Terminal Description
+24V Aux power positive connection
0V Aux Power 0V connection
SCRN Field cable screen connection
16
MO-
MO+
SCRE
EN
ON BOARD PCB
FIELD
CONNECTIONS
+
-
+
-
1
0
K
E
O
L
SCRE
EN
SCRE
EN
OV
+24V
SCRE
EN
ON BOARD PCB
FIELD
CONNECTIONS
SCRE
EN
24V DC
LOAD
ZetaNET Control Panel Installation Instructions
Inputs 1- 4: MI+, MI-, SCRN
Inputs 1-4 may be configured to monitor for open and short circuit faults using a 3K3 EOL resistor, and to
activate an alarm link using a 680R ‘firing’ resistor.
Terminal Description
MI+ Monitored Input positive connection
MI- Monitored Input 0V connection
SCRN Field cable screen connection
Fuses 1-3: F1, F2, F3
The fuses are located towards the top of the back plane PCB.
Blow fuses are easy to spot using the LED adjacent to each fuse. This will switch on if the output is
switched on (even in the passive state) and the fuse is blown.
Label Description Fuse
F1 Output 5 315 mA T
F2 Output 6 315 mA T
F3 Auxilliary Power 315 mA T
17
MI-
MI+
SCRE
EN
ON BOARD PCB
FIELD
CONNECTIONS
3
K
3
E
O
L
SCRE
EN
6
8
0
R
N/O
CONTACT
FIRE
RESISTOR
ZetaNET Control Panel Installation Instructions
Addressable Circuit Loops 1- 4: END1+, END 1-, SCRN, END2+, END2-, SCRN
18
END
1-
END
1+MI
+
SCRE
EN
ON BOARD PCB
FIELD
CONNECTIONS
SCRE
EN
END
2+MI
+
END
2-
SCRE
EN
SCRE
EN
ZetaNET Control Panel Installation Instructions
The Loop 1-4 addressable circuits may be connected to the appropriate End 1 and End 2 terminals.
Communications normally run from Circuit End 1, but in the event of a continuity fault both ends of the
circuit will operate.
It is important that the cable screen is connected to earth at each end at the control panel only, and that the
screen continuity is maintained at all times. We recommend against the use of a 4-core cable as a loop
Feed & Return due to the possibility of data corruption.
Addressable spur (radial) circuits may be connected from any multipoint detector, but not from any other
device. Devices covering a maximum of 1 zone per spur connection may be connected to each circuit in
order to ensure that no more than 1 zone may be lost in the event of a cable failure. Full functionality is
maintained for all spur devices.
Terminal Description
END1+ Circuit End 1 positive connection: +VE OUT
END 1 - Circuit End 1 0V connection : 0V OUT
SCRN Field cable screen connection: SCRN OUT
END2+ Circuit End 2 positive connection: +VE RETURN
END 2 - Circuit End 2 0V connection : OV RETURN
SCRN Field cable screen connection: SCRN RETURN
Network Ports 1-4: +12V, 0V, SCRN
The network ports allow multiple control panels to be connected together, up to a maximum of 32 panels.
Terminal Description
SCRN Field cable screen connection
B Data B connection
A Data A connection
19
B
SCREE
N
ON BOARD PCB
FIELD
CONNECTIONS
TO NETWORK PORT OF NEXT CONTROL PANEL
A
B
A
SCREE
N
ZetaNET Control Panel Installation Instructions
PSU: SCRN, B, A, SCRN, 0V, +24V,SCRN, 0V, +24V,
The PSU connections connect the control panel to the Power Supply Unit.
A 2-core 1.5mm
2
cable should be used for the Data connections (A and B), up to a maximum of 30m in
length.
Two 2-core 1.5mm
2
cables may be used for the +24V and 0V power connections, up to a maximum of 20m
in length. These cables should be connected to earth at each end at the terminals provided
If a greater distance is required between the main control panel and the PSU then two 2-core 2.5mm
2
cables should be used for the +24V and 0V power connections, up to a maximum of 30m in length. These
cables should be connected to earth at each end at the terminals provided
Terminal Description
A Serial Data connection
B Serial Clock connection
+24v Power Supply +24V connection
Ov Power Supply 0V connection
SCRN Cable Screen
USB Port: USB
The ZetaNET control panel may be programmed using the ZetaNET OSP programming software using a
USB lead to link to a computer. This allows the site specific data to be customised as required.
Serial Port: SERIAL
The ZetaNET control panel firmware (Control Panel Software stored in External Flash memory) may be
updated using the ZetaNET Firmware programming software using a serial lead to link to a computer. This
allows the control panel software version to be updated on site as required.
20
+24V
ON BOARD PCB
FIELD
CONNECTIONS
USB
PC USB PORT
ON BOARD PCB
FIELD
CONNECTIONS
SERIA
L
PC SERIAL PORT
+24V
B
ON BOARD PCB
FIELD
CONNECTIONS
TO ZETANET POWER SUPPLY
UNIT
A
SCR
N
SCR
N
OV
+24V
SCR
N
A
B
SCR
N
SCR
N
OV
+24VSCR
N
OV
OV
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77