ELECTRICAL REQUIREMENTS
• This appliancemustbe properlyinstalledand groundedbya qualifiedtechnicianin
accordancewiththeNational Electrical Code ANSI/NFPA No.70 (latestedition)and
local electrical code requirements. IN CANADA: Electrical installation must be in
accordancewiththecurrentCSAC22.1CanadianElectricalCodesPart1and/orlocal
codes.
• This appliance may beconnected bymeans ofpermanent “HardWiring” or“Power
SupplyCordKit”.Powersupplycord isnotsupplied,but itisavailablethroughyour
localelectricsupplyhouse.
• Useonly3-conductoror4-conductorCSA/ULlistedrangecordratedat50ampswith
250Vminimumandprovidedwithringterminals.Thesecordsshouldbeprovidedwith
strainrelieforconduitconnector.
Warning:Framegroundedthroughneutrallead.Ifusedin,
-Newbranch-circuitinstallations(1996NEC),
-Mobilehomes,
-Recreationalvehicles,or
-Inanareawherelocalcodesprohibitgroundingthroughneutral,usea4conductor
cordorconduit.
• Therangemustbeconnectedtotheproperelectricalvoltageandfrequencyasspeci-
fiedontheratingplate.
• Therangecanbeconnecteddirectlytothefuseddisconnect(orcircuitbreakerbox)
through flexible, armoured or non-metallic sheathed, copper cable (with grounding
wire).Allowtwotothreefeetofslackinthelinesothatitcanbemovedifservicingis
evernecessary.
VoltageandPowerConsumption
240-208/120V60Hz
11416W(240V)8575W(208V)
47.6A(240V)41.22A(208V)
ELECTRICAL CONNECTION WITH POWER CORD
Usea3-wirepowersupplycordkitratedfor50amps-125/250voltswithclosedloop
terminalsandmarkedforusewithranges.Wherelocalcodesdonotpermitgrounding
throughneutral,usea4-wirepowersupplycordkit.
Thecordmustbesecuredtotherangewithasuitablestrainrelief.Theelectricalcon-
nectionismadeattheterminalblock,whichislocatedbehindtheterminalblockaccess
plateonthebackoftherange.
ELECTRICAL CONNECTION WITH CONDUIT
Use3/4”tradesizeCSA/UL-listedconduitwithaconduitclamp,10AWG/600voltcopper
conductorcoloredredforline1andblackforline2and12AWG/600voltcopperconduc-
tor(or10AWG/600Voltcopperconductorifgroundingthroughneutral)coloredwhitefor
neutralwithclosedloopterminalsmarkedforusewithranges.
Wherelocalcodesdonotpermitgroundingthroughneutral,useagreen10AWGcopper
conductorasdirectedinthe4-wireconnectordirections.Theconduitmustbesecuredto
therangewiththestrainreliefbracket.Theelectricalconnectionismadeattheterminal
blockwhichislocatedbehindtheterminalblockaccessplateonthebackoftherange.
Location of
Nameplate
2
electrical connection
WARNING
TO AVOID ELECTRICAL SHOCK
HAZARD, BEFORE INSTALLING
THEAPPLIANCE, SWITCH POWER
OFF AT THE SERVICE PANEL AND
LOCK THE PANEL TO PREVENT
THE POWER FROM BEING
SWITCHED ON ACCIDENTALLY.
Electrical Shock Hazard
Electrically ground range.Failure to
follow these instruc-tions can result
indeath,re,orelectricalshock.