IB02602004E For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008 Page 17
Instructions for the FP-6000 Protective Relay
2.5.6 Default Settings
Please refer to the default settings as listed in Tables 27–37. The
default settings are those loaded into the program memory at
the factory. Restoration to default settings can only be
accomplished by deliberate user actions. No internal control
action can cause the FP-6000 to reset itself to default settings.
Restoring settings to factory defaults shown in Tables 27–37 once
alternative values are programmed involves one of three actions:
1. Manually input the default values for those changed through
the Settings mode.
2. Completely restore to default settings through the Default
Setting Control under the Status/Control mode function.
3. Execution of external communication commands. The user
may also reprogram individual settings or return all settings
to default by INCOM Command(s) through either the rear
INCOM port (J1), or through the front panel RS-232 Serial
port. This functionality is incorporated into the Eaton
software that operates through these ports, for instance
PowerNet or PowerPort.
The following section will discuss restoring the defaults utilizing
action No. 2 above, using the front panel capabilities of the
FP-6000.
2.5.7 Restoring Default Settings
To ensure a known starting point, unless you know that the
FP-6000 is pre-programmed to the required settings, return
the FP-6000 to its default programmed settings.
Press the Status/Control
pushbutton to access the
Default Setting Control.
After pressing Status/Control,
select “Default Setting Ctr,” and
press the Enter pushbutton.
Select “Load Default Setting”
and press Enter again. The
Password Window will appear
to verify your authorization to
make the desired change in the
settings. After password entry,
select “Load ALL Settings” and
press Enter. A final verification
display will enable you to accept
the change by pressing Enter or
cancel by using the Previous
pushbutton.
2.5.8 Programming
Programming consists of selecting “System Config” or
“Protection” from the “Setting Main” list. For the “System
Config” items, simply scroll to the item, select with Enter, vary
with Up/Down, and select with Enter. For “Protection,” select
“Setting Group 1” (the only default group enabled) and scroll to
select the functions to be changed as for “System Config.”
To save settings, press Previous until the screen requires Enter
to Save or Previous to Cancel.
Press the key desired and this operation is completed.
2.5.9 Active Alarm Status
The FP-6000 default settings provide connection and monitoring
of breaker state and the trip coil. When the FP-6000 is powered
up without these connections, an alarm indication is present.
Proceed to the Active Alarm Status display to view the active
alarms.
2.6 Startup
Startup consists of programming the necessary operational
parameters, verifying the operation of the FP-6000, checking the
wiring, and verifying the reasonable operation of the system
components before attempting to place the equipment into
continuous service.
The programming should already be done by the time the
FP-6000 is wired into a system and about to be Started Up and
placed into service. Follow Section 7 for start procedures and
refer to Section 6.3 for guidance in making connections during
startup.
2.6.1 Battery Installation
Beneath the front panel communications cover is a receptacle for
the lithium disc battery, (3 V Duracell DL 2032). Insert the battery
with the positive side up as shown on the communication cover.
The battery MUST be inserted with the power ON to eliminate
any unnecessary wear on the battery. It is possible for the
battery to remain in operation, until it expires, if the battery is
inserted while the power is off. This will cause the battery to
become useless when it is needed. For this reason, it is
recommended to insert the battery while the FP-6000’s power is
ON.
For additional information refer to Sections 4.5 and 11.4.
Note: If the battery is inserted with the FP-6000’s power off, you may
notice one or all of the LEDs flashing. The LEDs will be restored to their
proper state when the power is turned ON, and in turn, will discontinue
the use of the battery.
Update Settings?
ENTER to Save
Previous to Cancel
Reset to Exit Set