ABB REX 521 Technical Reference Manual, General

Type
Technical Reference Manual, General
REX 521
Protection Relay
Technical Reference Manual, General
3
Protection Relay
Technical Reference Manual,
General
REX 521
1MRS 751108-MUM
Issued: 27.6.2001
Version: B/05.07.2002
Checked: ML
Approved: MK
We reserve the right to change data without prior notice.
Contents
1. Safety information .....................................................................5
2. Introduction ...............................................................................6
2.1. General .........................................................................................6
2.2. Application .....................................................................................7
2.3. Hardware versions ........................................................................7
3. Requirements ............................................................................8
4. Technical description ...............................................................9
4.1. Functional description ...................................................................9
4.1.1. Parametrization ..................................................................9
4.1.1.1. Local parametrization ...........................................9
4.1.1.2. External parametrization ......................................9
4.1.1.3. Relay Setting Tool view ......................................10
4.1.2. Non-volatile memory ........................................................10
4.1.3. Real-time clock (RTC) ......................................................11
4.1.4. Auxiliary voltage ...............................................................11
4.1.4.1. Power supply versions .......................................11
4.1.4.2. Low auxiliary voltage indication ..........................12
4.1.5. Overtemperature indication ..............................................12
4.1.6. Analogue channels ..........................................................12
4.1.6.1. Setting the rated values for the protected unit ...12
4.1.6.2. Technical data of the measuring devices ...........13
4.1.7. Digital inputs ....................................................................15
4.1.7.1. Filtering of digital inputs .....................................15
4.1.7.2. Inversion of digital inputs ....................................16
4.1.8. Outputs ............................................................................16
4.1.8.1. High-speed power output (HSPO) .....................16
4.1.8.2. Single-pole power outputs (PO) .........................17
4.1.8.3. Signalling outputs (SO) ......................................18
4.1.9. Testing inputs and outputs ...............................................18
4.1.10.Trip-circuit supervision .....................................................19
4.1.11.Self-supervision ...............................................................20
4.1.11.1.Fault indication ...................................................22
4.1.11.2.Fault indication texts ..........................................22
4.1.12.Serial communication .......................................................23
4.1.12.1.Optical communication port on the rear panel ...23
4.1.12.2.Front panel optical connection for a PC .............24
4.1.12.3.The service pin located on the rear panel ..........24
4
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
4.1.12.4.SPA bus .............................................................25
4.1.12.5.LON bus ............................................................26
4.1.12.6.IEC 60870-5-103 bus ........................................28
4.1.13.Time synchronization .......................................................29
4.1.14.Display panel (HMI) .........................................................29
4.1.15.Indication LEDs ...............................................................30
4.2. Design description ......................................................................30
4.2.1. Technical data .................................................................30
4.2.2. Terminal diagram of the REX 521: Basic .........................34
4.2.3. Terminal diagram of the REX 521: Medium .....................35
4.2.4. Terminal diagram of the REX 521: High ..........................36
4.2.5. Terminal diagram of the REX 521: Sensor ......................37
4.2.6. Terminal connections ......................................................38
5. Service ..................................................................................... 40
6. Ordering information ............................................................. 41
7. Revision history of the REX 521 ........................................... 42
7.1. Revision identification .................................................................42
7.2. Changes and additions to earlier released revision A ................42
7.3. Configuration, setting and SA system tools ................................42
8. References .............................................................................. 43
9. Index ........................................................................................ 44
10.Customer feedback ............................................................... 46
11.Appendix A: The IEC 60870-5-103 bus ................................ 48
11.1.Functions supported by the REX 521 ........................................48
11.2.The general principle of application data mapping .....................48
11.3.The principle of the protection functions mapping ......................49
11.4.Class 2 data ...............................................................................49
11.5.Default mappings .......................................................................50
12.Appendix B: Parameters visible only in the relay .............. 57
13.Appendix C: Parameters which cause reset ....................... 58
14.Appendix D: Parameters which require test mode ............ 60
5HYLVLRQKLVWRU\
Version B/5.7.2002:
- changes in chapters “General”, “Hardware versions”, “Analogue channels”, “Setting the rated values
for the protected unit”, “Technical data of the measuring devices”, “Single-pole power outputs (PO)”,
“Trip-circuit supervision”, “Technical data”, “Ordering information”
- new terminal diagrams and terminal connections (High and Sensor)
- new chapters: “Revision history”, “Revision history of the REX 521”, “Index” and “Appendix D”
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
5
1. Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage is disconnected
National and local electrical safety regulations must always be
followed
The device contains components that are sensitive to electrostatic
discharge
The frame of the device has to be carefully earthed
Only a competent electrician is allowed to carry out the electrical
installation
Non-observance can result in death, personal injury or substantial
property damage
Breaking the sealing tape on the rear panel of the device will result in
loss of warranty and a proper operation will no longer be guaranteed
!
6
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
2. Introduction
This document provides a general description of the protection relay REX 521
Revision B. For more information about the earlier revisions, please refer to section
Revision history of the REX 521 on page 42.
For detailed information about the separate functions, please refer to REX 521
Technical Reference Manual, Standard Configurations (1MRS 751802-MUM).
2.1. General
The protection relay REX 521 is designed for protection, control, measuring and
supervision in medium voltage networks. Typical applications include incoming and
outgoing feeders as well as substation protection. The protection relay is provided
with energizing inputs for conventional current and voltage transformers. Also a
hardware version with inputs for current and voltage sensors is available.
The protection relay is based on a multiprocessor environment. The HMI
1
including
an LCD display with different views makes the local use easy and informs the user
via indication messages. Modern technology is applied both in hardware and
software solutions.
The REX 521 is part of the substation automation concept for Distribution
Automation and extends the functionality and flexibility of the concept further.
)LJ 5(;SURWHFWLRQUHOD\
1. HMI is referred to as MMI in the relay and in the Relay Setting Tool.
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
7
2.2. Application
The REX 521 is designed for protection of incoming and outgoing feeders in
medium voltage distribution substations. Further, the relay can, e.g., be applied to
back-up protection of power transformers and back-up for high voltage line
protection relays.
Several standard configurations are available for the protection relay. Please, refer to
REX 521 Technical Reference Manual, Standard Configurations
(1MRS 751802-MUM).
2.3. Hardware versions
Table 2.3.-1 Hardware versions of the REX 521
Relay type REX 521
Version name Basic Medium High Sensor
REX521xBxxx
REX521xMxxx
REX521xHxxx
REX521xSxxx
Transformer modules (MIM)
1111
Transformers
Current transformers 1/5 A 4441
• Current transformers 0.2/1 A 1 1 1
• Voltage transformers 100 V 1 4 1
Sensor channels
• Current sensor inputs 3
• Voltage sensor inputs 3
Main CPU modules
1111
CPU_SP (SPA/ IEC plastic)
CPU_SG (SPA/ IEC glass)
CPU_LP (SPA/ IEC/ LON plastic)
CPU_LG (SPA/ IEC/ LON glass)
Power supply modules
1111
PS_87H (DItresh.=80 Vdc)
PS_87L (DItresh.=18 Vdc)
Display module
1111
2 x 16 character display
Digital inputs
9
High-speed power outputs
1
Power outputs (PO)
3
Signalling outputs (SO)
2
IRF outputs
1
Trip-circuit supervision (TCS)
1
8
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
3. Requirements
If the environmental conditions differ from those specified in section Technical
data, as to temperature and humidity, or if the environmental conditions around the
protection relay contains chemically active gases or dust, the relay should be
visually inspected in association with the secondary testing. The visual inspection
should focus on:
Signs of mechanical damage to the relay case and terminals.
Signs of corrosion on terminals or on the case.
For information about the maintenance of relays, refer to section Service on
page 40.
Protection relays are measuring instruments and should be handled with
care and protected against moisture and mechanical stress, especially
during transport.
!
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
9
4. Technical description
4.1. Functional description
4.1.1. Parametrization
To ensure that a protection function block protects the feeder in the desired manner,
the default values of parameters must be checked and set before taking the function
block into use.
The parameters can be set either locally over the HMI or externally via the serial
communication using Relay Setting Tool. See Serial communication on page 23.
4.1.1.1. Local parametrization
The parameter to be changed is entered by navigating in the menu structure. For
detailed instructions, refer to Operators Manual (1MRS751107-MUM).
4.1.1.2. External parametrization
The Relay Setting Tool is used for external parametrization of the protection relay.
The parameters can be set by using a PC and downloaded to the protection relay over
a communication port. The menu structure of the setting tool, including views
relating to parametrization and settings, is the same as the menu structure of the
protection relay
1
. The use of the tool is instructed in Tools for Relays and
Terminals, Users Guide (refer to section References on page 43).
)LJ 0DLQGLDORJXHER[RIWKH5HOD\6HWWLQJ7RRO
1. A few parameters are visible only in the relay, see list on page 57.
10
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
4.1.1.3. Relay Setting Tool view
To improve usability, a REX 521 specific pull-down menu, View, with three views
has been created to the Relay Setting Tool.
)LJ 5HOD\6HWWLQJ7RROYLHZV
The Settings view includes the parameters for setting of all the function blocks. The
Configuration view includes signalling and hardware related settings. The
parameters in the Configuration view are advised to be set during commissioning
and service because some of the parameters cause resetting of the device. Please
refer to Appendix C: Parameters which cause reset on page 58 for a list of these
parameters. Measured values and registered data, e.g. current, digital input states,
can be uploaded by means of the Measurements & Registered Data view.
4.1.2. Non-volatile memory
The protection relay is equipped with a non-volatile memory for preserving
important data during auxiliary supply breaks. For example, when a setting value is
changed, the new value is stored in the memory at the moment of sending it to the
relay, without additional store commands. The memory does not need batteries, and
a lifelong service is guaranteed.
Following data is stored in the non-volatile memory:
Setting values
Display state
Lockout state
Recorded values
1
Last 50 events
When the relay is restarted, the same LED indication and text as before the auxiliary
supply break are restored on the display.
1. Because the storing of the recorded values is a background task, it might be affected
by a sudden auxiliary power failure.
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
11
Recorded values are stored from start, trip and other important events. After an
auxiliary power break, time and date and fault currents for the three last events can
be viewed by navigating to the Recorded values section of the function block that
caused an indication.
The last 50 events that occurred before the auxiliary power supply break can be
viewed in the HMI event buffer. Time and date for the events are also restored.
4.1.3. Real-time clock (RTC)
The RTC is used for time stamping of events. It is also running during auxiliary
power breaks. When the supply is re-established, the relay sets the right time and
new events are stamped accordingly.
The protection relay is provided with a 1-week capacitor back-up protection
1
that
enables the internal clock to keep time in case of an auxiliary power failure.
4.1.4. Auxiliary voltage
For its operation, the protection relay requires a secured auxiliary voltage supply.
The protection relays internal power supply module forms the voltages required by
the protection relay electronics. The power supply module is a galvanically isolated
(flyback-type) DC/DC converter. A green LED indicator on the front panel is lit
when the power supply module is in operation.
4.1.4.1. Power supply versions
There are two basic versions of power supply modules available for the REX 521
protection relays: type PS_87H and type PS_87L.
The input voltage range of the power supply module is marked on the front panel of
the REX 521 unit. The power supply version is specified by a letter in the order
number of the protection relay (refer to section Ordering information on page 41).
The voltage range of the digital inputs is tied to the selected power supply. If a power
supply version with the higher rated input voltage is selected, the protection relays
will be delivered with digital inputs that also have the higher rated input voltage. The
digital input, DI9, on the CPU module has always lower rated input voltage.
The auxiliary voltages of power supply modules and the corresponding rated input
voltages of digital inputs are:
For further technical data of the power supply, refer to Table 4.2.1-2 on page 30.
1. Capacitor ageing may decrease the back-up time.
Power supply module
Rated input voltage
of power supply
Rated input voltage
of digital inputs
PS_87H 110/120/220/240 V ac
or 110/125/220 V dc
110/125/220 V dc
PS_87L 24/48/60 V dc 24/48/60/110/125/220 V dc
12
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
4.1.4.2. Low auxiliary voltage indication
The relay is provided with a low auxiliary voltage indication feature. The power
supply module issues an internal alarm signal when a drop in the power supply
voltage is detected. The alarm signal is activated if the power supply voltage falls
about 10% below the lowest rated dc input voltage of the power supply module, see
the table below:
The indication of a low auxiliary voltage (ACFail) can be seen as an event via serial
communication.
4.1.5. Overtemperature indication
The REX protection relay includes an internal temperature supervision function.
The CPU module issues an internal alarm signal when overtemperature has been
detected inside the relay enclosure. The alarm signal will be activated once the
temperature inside the relay enclosure increases approximately to +78
o
C. The
overtemperature indication can be seen on the HMI or as an event via serial
communication. The relay will go to the IRF state. See Table 4.1.11.2-1, Fault
indications, on page 22.
4.1.6. Analogue channels
The protection relay measures the analogue signals needed for protection,
measuring, etc. via galvanically separated matching transformers. In addition,
current sensors (Rogowski coil) and voltage dividers developed by ABB can be used
with the REX 521.
The different versions of the REX 521 are provided with the following matching
transformers and sensor inputs:
A letter in the order number specifies whether the protection relay is equipped with
basic, medium, high or sensor measuring input modules. (Refer to section Ordering
information on page 41).
4.1.6.1. Setting the rated values for the protected unit
A separate scaling factor can be set for each analogue channel. The factors enable
differences between the ratings of the protected unit and those of the measuring
device (CTs, VTs etc.) The setting value 1.00 means that the rated value of the
protected unit is exactly the same as that of the measuring device.
Rated input voltage Low indication level
PS_87H
Rated input voltage 110/125/ 220 V dc 99 V dc
Rated input voltage 110/120/220/ 240 V ac 88 V ac
PS_87L
Rated input voltage 24/48/60 V dc 21.6 V dc
Version Matching transformers Sensor inputs
Basic CT1, CT2, CT3, CT4 -
Medium CT1, CT2, CT3, CT4, CT5, VT1 -
High CT1, CT2, CT3, CT4, CT5, VT1, VT2, VT3, VT4 -
Sensor CT4, CT5, VT1 RS1, RS2, RS3, VD1, VD2, VD3
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
13
When scaling factors are used, it should be noted that they affect the operation
accuracy of the relay. The accuracies stated in the description of each function block
(in the CD-ROM Technical Descriptions of Functions) only apply with the default
values of the scaling factors. For example, a high factor affects the operation of
sensitive protection functions such as the directional earth-fault protection.
The scaling factor is calculated channel by channel as follows:
Scaling factor = I
nmd
/ I
np,
where
Example:
The scaling factors for the analogue channels can be set via the HMI of the
protection relay or with the Relay Setting Tool. The HMI path for the scaling factors
is: Configuration\Protected unit\IL1: scaling, IL2:
scaling...
4.1.6.2. Technical data of the measuring devices
The technical data of the measuring devices is set using the Relay Setting Tool or
via HMI. The set values (Configuration\Meas.devices\) will affect the
measurements carried out by the REX 521.
9DOXHVWREHVHWIRUDFXUUHQWWUDQVIRUPHU
rated primary current (0...6000 A) of the current transformer
rated secondary current (5 A, 2 A, 1 A, 0.2 A) of the current transformer
rated current (5 A, 1 A, 0.2 A) of the current measuring input (= rated current of
the matching transformer of the protection relay)
amplitude correction factor (0.9000...1.1000) of the current transformer at rated
current
correction parameter for the phase displacement error of the current transformer
at rated current (-5.00°...0.00°)
amplitude correction factor of the current transformer at a signal level of 1% of
the rated current (0.9000...1.1000)
correction parameter for the phase displacement error of the current transformer
at a signal level of 1% of the rated current (-10.00°...0.00°)
I
nmd
Rated primary current [A] of the measuring device
I
np
Rated primary current [A] of the protected unit connected to the
channel
Rated primary current of current trafo = 500 A: I
nmd
= 500 A
Rated current of the protected unit = 250 A: I
np
= 250 A
Scaling factor for current channels: 500 A / 250 A = 2.00
14
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
9DOXHVWREHVHWIRUDYROWDJHWUDQVIRUPHU
rated voltage of primary voltage transformer (0...440 kV)
rated voltage of voltage input (same as the secondary rated voltage of the primary
voltage transformer connected to the voltage input, 100 V, 110 V, 115 V, 120 V)
amplitude correction factor of the primary voltage transformer voltage at rated
voltage (0.9000...1.1000)
correction parameter for the primary transformer phase displacement error at
rated voltage (-2.00°... 2.00°)
9DOXHVWREHVHWIRUDFXUUHQWVHQVRU5RJRZVNLFRLO
secondary rated voltage of the current sensor used at the preset primary rated
current (0...300 mV)
primary rated current of the current sensor used (0...6000 A)
amplitude correction factor of the current sensor used at rated current
(0.9000...1.1000)
correction parameter for the phase displacement error of the current sensor
(-1.0000°...1.0000°)
9DOXHVWREHVHWIRUDYROWDJHGLYLGHU
division ratio of the voltage divider primary and secondary voltage (0...20000)
rated value of primary phase-to-phase voltage (0...440 kV)
amplitude correction factor of the voltage divider (0.9000...1.1000)
correction parameter for the phase displacement error of the voltage divider
(-1.0000°...1.0000°)
&DOFXODWLRQRIFRUUHFWLRQSDUDPHWHUVDQGIDFWRUV
The measurement values stated by the manufacturer of the measuring device are
used for calculating the correction parameters and factors according to the following
formulas:
&XUUHQWWUDQVIRUPHUV
9ROWDJHWUDQVIRUPHUV
Amplitude error at current I
n
(p = error in per cent)
Amplitude correction factor 1
= 1 / (1+ p/100)
Amplitude error at current 0.01 x I
n
(p = error in per cent)
Amplitude correction factor 2
= 1 / (1+ p/100)
Phase displacement error at current I
n
(d = error in degrees)
Phase displacement error 1 = - d
Phase displacement error at current 0.01 x I
n
(d = error in degrees)
Phase displacement error 2 = - d
Amplitude error at voltage U
n
(p = error in per cent)
Amplitude correction factor
= 1 / (1+ p/100)
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
15
5RJRZVNLFRLO
9ROWDJHGLYLGHU
Primary values and measurement device settings
The conversion between primary and per unit values are based on the analogue
scales of the I
L1
(I
L1
pu-scale), I
0
(I
0
pu-scale), I
0b
(I
0b
pu-scale), U
12
(U
12
pu-scale)
and U
0
(U
0
pu-scale). To ensure proper operation, it must be checked that the
analogue scales of the phase currents I
L1
, I
L2
and I
L3
, and correspondingly, the
analogue scales of the phase-to-phase voltages U
12
, U
23
and U
31
are identical.
4.1.7. Digital inputs
The digital inputs of the protection relay are voltage-controlled and optically
isolated. For technical data of the digital inputs, refer to Table 4.2.1-3 on page 31.
4.1.7.1. Filtering of digital inputs
The filter time eliminates debounces and short disturbances on digital inputs. The
filter time may be set individually for each input.
)LJ )LOWHULQJRIDGLJLWDOLQSXW
Phase displacement error at voltage U
n
(d = error in degrees)
Phase displacement error = - d
Amplitude error at the whole measuring range
(e = error in per cent)
Amplitude correction factor
= 1/(1+ e/100)
Phase displacement error at the whole
measuring range
(e = error in degrees)
Phase displacement error = - e
Amplitude error at the whole measuring range
(e = error in per cent)
Amplitude correction factor
= 1/(1+ e/100)
Phase displacement error at the whole
measuring range
(e = error in degrees)
Phase displacement error = - e
16
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
The figure above illustrates the input filtering. At the beginning, the input signal is
at high state, the first low state is filtered and no input status change is detected. The
second low state is longer than the set filter time, thus detected as a change and
attached with the time tag t
0
.When the input signal returns to high state, after the
filter time, the state is accepted and attached with the time tag t
1
.
Each digital input has a filter time parameter Input # filter
(Configuration\Digital inputs\Input filtering), where # is the
number of the input.
A risk for debounces and short disturbances on digital inputs grows if the input filter
time is changed to less than the default value.
4.1.7.2. Inversion of digital inputs
The status of digital inputs can be inverted with parameters accessible through the
HMI or the Relay Setting Tool (Configuration\Digital inputs\Input
inversion). When inverted, the status of a digital input is TRUE (1) when no
control voltage is applied to the terminals, and FALSE (0) when the control voltage
is applied.
4.1.8. Outputs
The outputs are categorized as follows:
HSPO: High speed power output, single or double pole contact, e.g. for tripping
purposes
PO: Power output, single pole contact
SO: Signal output, NO/NC (Normally open/Normally closed) contact
For detailed information about terminal connections, please refer to the terminal
diagrams. Technical data of the outputs is found in the section Technical Data on
page 30.
4.1.8.1. High-speed power output (HSPO)
The high-speed power output HSPO1 can be connected as a double-pole output
where the object to be controlled (e.g. a circuit breaker) is electrically connected
between the two relay contacts, see the figure below. The high-speed double-pole
power output is recommended to be used for tripping purposes.
Table 4.1.7.1-1 Filter time parameter
Parameter Values Default
Input # filter 1...65535 ms 5 ms
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
17
)LJ +LJKVSHHGGRXEOHSROHSRZHURXWSXW+632
The high-speed power output HSPO1 can also be connected as a single-pole power
output where the object to be controlled (e.g. a circuit breaker) is electrically
connected in series with the two relay contacts, see the figure below.
)LJ +LJKVSHHGVLQJOHSROHSRZHURXWSXW+632
4.1.8.2. Single-pole power outputs (PO)
The single-pole power outputs PO1...3 are outputs where the object to be controlled
is connected in series with two heavy-duty output relay contacts, see the figure
below. These outputs can be used for tripping purposes and for circuit breaker and
disconnector control. Two singe-pole outputs may be used to obtain another double-
pole output.
)LJ 6LQJOHSROHSRZHURXWSXWV32
+
-
cbcoilrex
HSPO1
CB
+
-
doubpolerex
CB
HSPO1
+
-
PO1connrex
CB
PO1...3
18
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
4.1.8.3. Signalling outputs (SO)
The signalling relay outputs (SO1 and SO2) are not heavy-duty outputs and thus
they cannot be used for controlling e.g. a circuit breaker. Available relay contacts
are Normally Open/Normally Closed type (NO/NC), see the figure below. These
outputs can be used for alarming and other signalling purposes.
)LJ 6LJQDOOLQJRXWSXW62
4.1.9. Testing inputs and outputs
The digital inputs and the output relays may be tested using the serial
communication or the HMI.
Generally, the relay has to be in the test mode before the inputs and outputs can be
activated. However, output relays may be activated through the serial
communication without entering the test mode. This is to enable the usage of output
relays for external purposes, not part of the protection and control in the host relay.
The test mode can be set with a parameter. The green READY LED indicator will
be blinking, to announce that the test mode has been entered. In this state, the relay
configuration is disconnected from the physical inputs so that changes on the digital
inputs will not be noticed. When the test mode is deactivated, all test parameters
requiring the test mode, will be reset.
The IRF relay may be tested by using the HMI. The IRF relay testing always requires
entering the test mode.
When testing the general output relays, the user should notice, that normal operation
of the relay cannot be disconnected. If an output relay is permanently activated by
the configuration, it cannot be deactivated for testing.
For further information, refer to Operators manual (see References on page 43).
noncrex
NO/NC
e.g.
SO1
Table 4.1.9-1 Testing of inputs and outputs
Test object Using
Requires
test mode?
Remarks
Digital inputs HMI Yes Physical inputs disconnected
Serial communication Yes
Output relays HMI Yes Normal operation still active
Serial communication No
IRF relay HMI Yes
Serial communication Yes
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
19
4.1.10. Trip-circuit supervision
The trip-circuit supervision consists of two functional units:
a current limiter including the necessary hardware elements
a software-based function block, named TCS
The supervision of the trip circuit is based on the constant current injection principle.
By applying an external voltage over the relays trip contacts, a constant current is
forced to flow through the external trip circuit. If the resistance of the trip circuit
exceeds a certain limit, for instance due to a bad contact or oxidation, the supervision
function will be activated and cause a trip-circuit supervision alarm signal after an
adjustable delay time.
Under normal operating conditions, the applied external voltage is divided between
the relays internal circuit and the external trip circuit so that at the minimum 20 V
(15...20 V) remains over the relays internal circuit. Should the external circuits
resistance be too high or the internal circuits too low, e.g. due to welded relay
contacts, the fault is detected.
Mathematically the operation condition can be expressed as:
where:
U
c
= operating voltage over the supervised trip circuit
I
c
= measuring current through the trip circuit, appr. 1.5 mA (0.99...1.72 mA)
R
ext
= external shunt resistance
R
int
= internal shunt resistance, 1k
R
s
= trip coil resistance
The external shunt resistance is used if the trip-circuit supervision, independent of
the circuit-breaker position, is desired. If the trip-circuit supervision is required only
in closed position, the external shunt resistance may be omitted.
Should the external shunt resistance be used, it has to be calculated not to interfere
with the functionality of the supervision or the trip coil. Too high a resistance will
cause too high a voltage drop, jeopardizing the requirement of at least 20 V over the
internal circuit, while a resistance too low may enable false operations of the trip
coil.
Following values are recommended for the external resistor R
ext
:
Table 4.1.10-1 Values recommended for R
ext
Operating voltage U
c
Shunt resistor R
ext
48 V dc
1.2 k
, 5 W
60 V dc
5.6 k
, 5 W
110 V dc
22 k
, 5 W
220 V dc
33 k
, 5 W
U
c
R
ext
R
int
R
s
++() I
c
20× Vac dc
20
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
)LJ 2SHUDWLQJSULQFLSOHRIWKHWULSFLUFXLWVXSHUYLVLRQZLWKRXWDQ
H[WHUQDOUHVLVWRU7KH7&6EORFNLQJVZLWFKLVVHWEORFNLQJWKH7&6
ZKHQWKHFLUFXLWEUHDNHULVRSHQ
)LJ 2SHUDWLQJSULQFLSOHRIWKHWULSFLUFXLWVXSHUYLVLRQZLWKDQH[WHUQDO
UHVLVWRU7KH7&6EORFNLQJVZLWFKLVRSHQHQDEOLQJWULSFLUFXLW
VXSHUYLVLRQLQGHSHQGHQWRIFLUFXLWEUHDNHUSRVLWLRQ
If there are more auxiliary contacts available, an opening contact can be series
connected with the R
ext
-resistor. The shunt-resistor circuit is opened when the CB is
closed. Therefore the supervision of the auxiliary contact is also possible.
4.1.11. Self-supervision
In order to avoid false operations due to relay faults and to maximize the overall
availability of the protection, a set of autodiagnostic circuit arrangements have been
implemented in the relay modules.
The different memory circuits, i.e. the RAM and the non-volatile memories, are
continuously tested with different methods.
+
-
Rs
TCS1
BS
TCSSTATE ALARM
HW
SW
TC
S
close
TCS
R
1
2
3
4
X4.2
CBPOS_open
TCS blocking
int
CBPOS_open
TCS gesperrt
TCSopen
+
-
R
Rs
TCS1
BS
TCSSTATE ALARM
HW
SW
TCS
1
2
3
4
X4.2
R
TCS blocking
CBPOS_open
int
ext
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

ABB REX 521 Technical Reference Manual, General

Type
Technical Reference Manual, General

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI