APG MPXI-F User manual

Type
User manual
APG
R
Doc #9006317
Part #200749
Rev A2, 05/2021
MPXI Magnetostrictive Level Sensors
User Manual
For the Series MPXI-F
Explosion Proof, Flexible, Stainless Steel and PVDF Stems
ii
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Table of Contents
Introduction ................................................................................................................ iii
Warranty and Warranty Restrictions .................................................................... iv
Chapter 1: Specications and Options..................................................................... 1
Dimensions ....................................................................................................................................1-3
MPXI-F/K Shipping Box Contents ................................................................................................ 4
Specications ................................................................................................................................... 5
Model Number Congurator ...................................................................................................... 6-7
System Wiring Diagrams ........................................................................................................... 8-9
Chapter 2: Installation and Removal Procedures and Notes ............................10
Tools Needed ................................................................................................................................... 10
ATEX Stated Conditions of Use ................................................................................................... 10
Physical Installation Notes ..........................................................................................................11
PVDF Installation Temperature Requirements ....................................................................... 12
Physical Installation Instructions ............................................................................................. 13
Electrical Installation ................................................................................................................... 14
Removal Instructions ....................................................................................................................15
Chapter 3: Programming ..........................................................................................16
Modbus Programming .................................................................................................................. 16
Modbus Programming with RST-6001 and APG Modbus Software .................................... 16
4-20 mA Programming with RST-4100 and APG Modbus Software .................................... 17
Modbus Register Lists for MPXI-F8......................................................................................17-18
MPXI-F8 Modbus Sensor Parameters ..................................................................................19-23
Modbus Register Lists for MPXI-F6 and MPXI-F7 ........................................................... 24-25
MPXI-F6 and MPXI-F7 Modbus Sensor Parameters ........................................................ 26-30
MPXI-F Application Type Parameters .................................................................................31-35
Chapter 4: Maintenance ...........................................................................................36
General Care .................................................................................................................................... 36
Repair and Returns ........................................................................................................................36
Chapter 5: Hazardous Location Installation and Certication .........................37
Installation Drawing For MPXI ................................................................................................... 37
CSA Certicate of Compliance ...............................................................................................38-41
IECEx Certicate of Conformity ........................................................................................... 42-45
EU Declaration of Conformity ..................................................................................................... 45
iii
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Introduction
Thank you for purchasing an MPXI-F series magnetostrictive level sensor from APG. We appreciate your
business and your trust. Please take a few minutes to familiarize yourself with your MPXI-F and this manual.
MPXI-F Series Explosion Proof, Flexible Stainless Steel and PVDF Stem Magnetostrictive Probe Level Sensors’
exible stem allows for installation in tanks up to 50 feet tall, without needing a crane or an extra-long truck
and trailer for delivery. It provides highly accurate and repeatable level readings in a wide variety of liquid
level measurement applications. APG’s proprietary-PVDF-formulation stem provides increased exibility and
impact resistance during cold-weather installation, along with compatibility in a wider range of corrosive
media--including H
2
S--in larger tanks. The housing is certied for installtion in Class I, Division 1 and Class I,
Zone 1 hazardous areas, while the stem is certied for installation in Class I, Division 1, and Class I, Zone 0
hazardous areas in the US and Canada by CSA and ATEX and IECEx for Europe and the rest of the world.
Reading your label
Every APG instrument comes with a label that includes the instrument’s model number, part number,
and serial number. Please ensure that the part number on your label matches your order. The following
electrical ratings and approvals are also listed on the label. Please refer to the CSA Certicate of Compliance
at the back of this manual for further details.
cCSAus Certicate CSA19CA70219727
Rated 12-24 VDC, Um 250 V, 4-20 mA, or 80 mA
Class I, Division 1, Groups C, D T4; IP66
Class I, Zone 0/1
AEX ia/db IIB T4 Ga/Gb
Ex ia/db IIB T4 Ga/Gb, IP66
Ta = -40°C to 85°C
ATEX Certicate Number: Sira 19ATEX2072X
II 1/2G
Ex ia/db IIB T4 Ga/Gb
Ta: -40°C to 85°C
IECEx Certicate IECEx SIR 19.0026X
Ex ia/db IIB T4 Ga/Gb
Ta: -40°C to 85°C
US
C
237484
CARE SHOULD BE TAKEN TO ENSURE THAT THE ENCLOSURE OF THE MPXI IS INSTALLED IN ZONE 1. ONLY THE
PORTION OF THE UNIT AS SPECIFIED IN DOCUMENT 9006113 SHALL BE INSTALLED IN ZONE 0. ENSURE SEPA-
RATION BETWEEN ZONES DURING INSTALLATION TO AVOID INTRODUCTION TO EXPLOSIVE ATMOSPHERES.
iv
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Warranty and Warranty Restrictions
This product is covered by APG’s warranty to be free from defects in material and workmanship under
normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit
https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to receive a Return
Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
DANGER: WARNING -- EXPLOSION HAZARD -- SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC
SAFETY;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- LA SUBSTITUTION DE COMPOSANT PEUT AMELIORER LA
SECURITE INTRINSIQUE.
DANGER: WARNING -- EXPLOSION HAZARD -- DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS
BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- AVANT DE DECONNECTER L’EQUIPEMENT, COUPER LE COURANT
OU S’ASSURER QUE L’EMPLACEMENT EST DESIGNE NON DANGEREUX.
DANGER: OPEN CIRCUIT BEFORE REMOVING COVER or KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE;
AVERTISSEMENT -- COUPER LE COURANT AVANT D’ENLEVER LE COUVERCLE, ou GARDER LE COUVERCLE
FERME TANT QUE LES CIRCUITS SONT SOUS TENSION.
IMPORTANT: MPXI-F level sensor MUST be installed according to drawing 9006113
(Installation Drawing For MPXI) on page 37 to meet listed approvals. Faulty installation will
invalidate all safety approvals and ratings.
DANGER: WARNING -- DO NOT OPEN COVER WHEN ENERGIZED.
AVERTISSEMENT - NE PAS OUVRIR QUAND ÉNERGISÉ.
1
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Chapter 1: Specications and Options
MPXI-F/B (SS Stem) Sensor Dimensions with 2ӯ Stem Weights
Dimensions
5.00”
5.10”
5.88”4.98”
3.03”
3.00”
5.50”
3.08”
2.80”
3.07”
MPXI-F/B Float Options
Y & Z / L & M
W & X
S & T
U & V / I & J
I & J U & V
2.00”
Y & Z
L & M
U & V
I & J
Probe Length
in Inches
S1 Top
Deadband
Length
Number & Total
Height of 2ӯ
Stem Weights
Length
of 1ӯ
Tubing
L ≤ 96” 6” 1 4.75” 8”
97” ≤ L ≤ 144” 6” 2 9.5” 8”
145” ≤ L ≤ 192” 8” 2 9.5” 8”
193” ≤ L ≤ 300” 8” 3 14.25” 14”
301” ≤ L 10” 3 14.25” 14”
14.0"
[355.6mm]
1"Ø RIGID TUBE
LENGTH PER NO. OF WEIGHTS
S1 MEASURABLE LENGTH S2
4.75"
[120.7mm]
1.99"
[50.5mm]
TOTAL LENGTH
7.03"
[178.6mm]
4.13"
[105.0mm]
4.25"
[108.0mm]
3.71"
[94.3mm]
MPX-F STEM
ASSEMBLY
FLOAT(S) 2 in DIA
MOUNTING OPTIONS
FLOAT WEIGHT #1
WEIGHT #2
(AS NEEDED, PER LENGTH)
~
OPTIONAL
SMALL
HOUSING
GROUND SCREW
Measureable Length = Total Length - S1 - S2
S1 = Top Deadband
S2 = 1 Float Height + Weight(s) Height + 0.5”
2
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
MPXI-F/B (SS Stem) Sensor Dimensions with 3ӯ Stem Weights
5.00”
5.10”
5.88”4.98”
3.03”
3.00”
5.50”
3.08”
2.80”
3.07”
MPXI-F/B Float Options
Y & Z / L & M
W & X
S & T
U & V / I & J
I & J U & V
2.00”
Y & Z
L & M
U & V
I & J
14.0"
[355.6mm]
8.00"
[203.2mm]
S1 MEASURABLE LENGTH S2
2.99"
[75.9mm]
3.00"
[76.2mm]
TOTAL LENGTH
4.34"
[110.2mm]
7.03"
[178.6mm]
4.49"
[114.0mm]
5.00"
[127.0mm]
FLOAT(S) 3 in DIAMOUNTING OPTIONS
MPX-F STEM
ASSEMBLY
FLOAT
WEIGHT #2
(AS NEEDED,
PER LENGTH)
WEIGHT #1
~
OPTIONAL
LARGE
HOUSING
GROUND SCREW
Probe Length
in Inches
S1 Top
Deadband
Length
Number & Total
Height of 3ӯ
Stem Weights
L ≤ 144” 6” 1 3”
145” ≤ L ≤ 192” 8” 1 3”
193” ≤ L ≤ 300” 8” 2 6”
301” ≤ L 10” 2 6”
Measureable Length = Total Length - S1 - S2
S1 = Top Deadband
S2 = 1 Float Height + Weight(s) Height + 0.5”
3
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
4.98”
3.00”
MPXI-F/K Float Options
I & J
3.50”
H & K
2.00”
MPXI-F/K (PVDF Stem) Sensor Dimensions
3.54"
[90.0 mm]
4.25"
[108.0 mm]
4.92"
[125.0 mm]
2x Ø.27"
[6.9 mm]
THRU
1/2" NPT
CONDUIT
OPENING
HOUSING CONNECTION
LOCATION
3.7"
[94.0 mm]
4.17"
[106.0 mm]
OPTIONAL
SMALL
HOUSING
Probe Length
in Inches
S1 Top
Deadband
Length
Number & Total
Height of Stem
Weights
L ≤ 144” 6” 1 5”
145” ≤ L ≤ 300” 8” 2 10”
301” ≤ L ≤ 330” 10” 2 10”
331” ≤ L ≤ 516” 10” 3 15”
517” ≤ L 10” 4 20”
Note: S1 Top Deadband for all probes with High Level
Switch is 23.5”.
Measureable Length = Total Length - S1 - S2
S1 = Top Deadband
S2 = 1 Float Height + Weight(s) Height + 0.8625”
4.33"
[110.0mm]
5.71"
[145.0mm]
5.00"
[127.0mm]
2x Ø.27
THRU
3/4" NPT
CONDUIT
OPENING
HOUSING CONNECTION
LOCATION
GROUND
SCREW
MOUNTING OPTION
FLOAT(S)
FLOAT STOP (OPTIONAL)
WEIGHT(S)
HIGH-HIGH SWITCH
FLOAT (OPTIONAL)
WEIGHT RETENTION
MEASURABLE LENGTH (PER ORDER)
S2
4.96"
[126.0mm]
7.46"
[189.5mm]
S1
TOTAL LENGTH
4.29"
[109.0mm]
HOUSING
ADAPTER
HOUSING
4
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
MPXI-F/K Shipping Box Contents
PROBE HOUSING
(TYP 2)
PROBE MOUNTING
OPTION
(TYP 2)
FLOAT STOP FOR
HIGH LEVEL SWITCH
(TYP 2)
STEM WEIGHT(S)
AND DOWEL PIN(S)
PER ORDER
FLOATS
PER ORDER
(TYP 4)
HIGH LEVEL SWITCH
(TYP 2)
MPXI-F/K Shipping Box
10” (254 mm)
MINIMUM
BEND RADIUS
5
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Performance
Resolution 4-20 mA: 14 bit DAC (1 mm)
Modbus: 0.04 in. (1 mm)
Accuracy 4-20 mA: Greater of ±0.05% of FS or 1 mm
Modbus: ±0.04 in. (±1 mm)
Digital Temp Sensor Accuracy: ±1°C
API 18.2 Temp Sensor Accuracy: ±0.25°C over -40° to 85° C
±0.13°C over +20° to 70° C
High Level Switch Actuation Point 0.6” (15 mm) travel above oat stop
Stem Bend Radius (minimum) PVDF: 10” (254 mm)
Environmental
Operating Temperature -40° to 185° F (-40° to 85° C)
Enclosure Protection NEMA 4X, IP66
Maximum Pressure PVDF stem: 300 psi
PVDF oat: 50 psi
Electrical
Supply Voltage Modbus (RS-485): 12-24 VDC on sensor
4-20 mA: 24 VDC on sensor
High Level Switch: 5-24 VDC
Current Draw Modbus (RS-485): 15 mA (typical)
4-20 mA: 22 mA single / 44 mA dual (max)
HIgh Level Switch: 7 - 9 mA (closed)
0 -1 mA (open)
Protection Reverse Polarity and CE compliant to EN 61326
Materials of Construction
Housing Cast aluminum, epoxy coated
Stem
Stainless Steel: 7/8ӯ 316L SS Flexible Tubing with Braid
PVDF: 5/8ӯ proprietary formulation PVDF Flexible Tubing
Mounting (slide) 316L SS
Compression Fitting (slide) Aluminum with Neoprene bushing
Stem Weights 316L SS
Connectivity
Output Modbus RTU (RS-485), optional temperature sensors
2-wire, loop-powered 4-20 mA
4-wire, loop-powered dual 4-20 mA
Programming
RS-485 Optional RST-6001 USB-to-RS-485 converter
4-20 mA Optional RST-4100 programming module
Specications
6
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Model Number Congurators
Model Number: MPXI - _F_ _____ _____ - _____ _____ - _____ _____ _____ _B_ - _____ - _____ - _N_ _2_ _____ _____
A B C D E F G H I J K L M N O
A. Stem Type
F Flexible Tubing
B. Output
6 Single oat, loop-powered 4-20 mA, 2-wire
7 Dual oat, loop-powered 4-20 mA, 4-wire
8 Modbus RTU, with optional temperature sensors
C. Housing Type
All Housing Die-cast Aluminum, NEMA 4X, IP66, Blue
__
Large Housing
A Small Housing
D. Float 1 (Top Float)
Z/Y 5.5h x 3d in. Red Polyurethane (0.65 SG / 0.94 SG)
X/W 5 in. Round 316L SS (0.52 SG / 0.92 SG)
V/U 6h x 3d in. Oval 316L SS (0.58 SG / 0.94 SG)
T/S 3 in. Round 316L SS (0.60 SG / 0.94 SG)
M/L 5.5h x 2d in. Red Polyurethane (0.57 SG / 0.94 SG)
J/I 5h x 3d in. Oval Titanium 2 (0.60 SG / 0.94 SG)
N None
E. Float 2 (optional)
N None
Y 5.5h x 3d in. Blue Polyurethane (0.94 SG)
W 5 in. Round 316L SS (0.92 SG)
U 6h x 3d in. Oval 316L SS (0.94 SG)
S 3 in. Round 316L SS (0.94 SG)
L 5.5h x 2d in. Blue Polyurethane (0.94 SG)
I 5h x 3d in. Oval Titanium 2 (0.94 SG)
F. Mounting Type
P
NPT Plug 150#
N None
G. Mounting Size
2
2 in. (welded or slide connection)
3 3 in. (slide connection)
N None
H. Mounting Connection
W Welded (xed)
S
Slide with Compression Fitting (adjustable)
Note:
This option is standard.
I. Stem Material
B 316L SS
J. Total Stem Length in Inches
__ Min. 48 in. - Max. 384 in.
K. Temperature Sensor Options
MPXI-F8
N None
1D
Digital Temperature Sensor A, 12 in. from bottom of
probe
2D Digital Temperature Sensors A, B
3D Digital Temperature Sensors A, B, C
4D Digital Temperature Sensors A, B, C, D
5D Digital Temperature Sensors A, B, C, D, E
6D Digital Temperature Sensors A, B, C, D, E, F
7D Digital Temperature Sensors A, B, C, D, E, F, G
AP Sensor Quanity and Placement per API 18.2 Standard
Note: Temperature sensors B - G are spaced evenly between A
and probe’s zero reference.
L. Custom Housing/Electrical Connection
N
None
M. End Plug
2
Keyhole for weight locking pin
N. Float Stop
A3
1-piece top oat stop, held with set screw
F3 2-piece clamp top oat stop
N None
O. Stem Weights
W7 316L SS, 3 lb, 2”Ø x 4.75”H; modular
W8 316L SS, 5 lb, 3”Ø x 3”H; modular
7
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Model Number: MPXI - _F_ _____ _____ - _____ _____ - _____ _____ _____ _K_ - _____ - _____ - _N_ _2_ _____ _____ - _____
A B C D E F G H I J K L M N O P
A. Stem Type
F Flexible Tubing
B. Output
6 Single oat, loop-powered 4-20 mA, 2-wire
7 Dual oat, loop-powered 4-20 mA, 4-wire
8 Modbus RTU, with optional temperature sensors
C. Housing Type
All Housing Die-cast Aluminum, NEMA 4X, IP66, Blue
__
Large Housing
A Small Housing
D. Float 1 (Top Float)
K/H
3.5h x 2d in. PVDF (0.58 SG / 0.94 SG)
J/I 5h x 3d in. Oval Titanium 2 (0.60 SG / 0.94 SG)
N None
E. Float 2 (optional)
N
None
H 3.5h x 2d in. PVDF (0.94 SG)
I 5h x 3d in. Oval Titanium 2 (0.94 SG)
F. Mounting Type
P
NPT Plug 150#
N None
G. Mounting Size
2
2 in. (welded or slide connection)
N None
H. Mounting Connection
W Welded (xed)
S
Slide with Compression Fitting (adjustable)
Note:
This option is standard.
I. Stem Material
K Proprietary PVDF formulation
J. Total Stem Length in Inches
__ Min. 120 in. - Max. 600 in.
K. Temperature Sensor Options
MPXI-F8
N None
1D
Digital Temperature Sensor A, 12 in. from bottom of
probe
2D Digital Temperature Sensors A, B
3D Digital Temperature Sensors A, B, C
4D Digital Temperature Sensors A, B, C, D
5D Digital Temperature Sensors A, B, C, D, E
6D Digital Temperature Sensors A, B, C, D, E, F
7D Digital Temperature Sensors A, B, C, D, E, F, G
AP Sensor Quanity and Placement per API 18.2 Standard
Note: Temperature sensors B - G are spaced evenly between A
and probe’s zero reference.
L. Custom Housing/Electrical Connection
N
None
M. End Plug
2
Keyhole for dowel pin
N. Float Stop
E3 1-piece clamp, top oat stop only
N
None
O. Stem Weights
W6
316L SS, 3.75 lb, 2”Ø x 5”H; modular
P. High Level Switch
N None
H Normally Closed Switch, xed distance from probe zero
reference
8
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
System Wiring Diagrams
IMPORTANT: Refer to Chapter 5 for Installation Drawing For MPXI.
Modbus System Wiring For MPXI-F Sensors
Modbus System Wiring with RST-6001 For MPXI-F Sensors
Power
Supply
+12-24 Vdc
GND
Use Shielded Cable
120 Ω
terminating
resistor
120 Ω
terminating
resistor at
last sensor
V+
B
A
Sensor 1
GND
V+
B
A
Sensor 2
GND
V+
B
A
Sensor 3
GND
Modbus
Server
Device
RS-485 A
RS-485 B
MPXI-F Modbus
series sensor
MPXI-F Modbus
series sensor
MPXI-F Modbus
series sensor
EARTH
GND
Note: Earth Ground terminal is factory
connected to internal housing ground
lug.
EARTH
GND
EARTH
GND
Power
Supply
+12-24 Vdc
GND
Use Shielded Cable
Equivalent 120 Ω
terminating resistor
internal to RST-6001
120 Ω
terminating
resistor at
last sensor
USB to computer
with APG Modbus
software
RST-6001
Modbus
Controller
V+
B
A
Sensor 1
GND
V+
B
A
Sensor 2
GND
V+
B
A
Sensor 3
GND
A
B
-5V
MPXI-F Modbus
series sensor
+5V
MPXI-F Modbus
series sensor
MPXI-F Modbus
series sensor
Note: An independent +12-24 Vdc
power supply is required when
using an RST-6001 Modbus Controller.
The RST-6001 can only supply ±5 Vdc,
not the +12-24 Vdc required by the MPXI-F.
EARTH
GND
EARTH
GND
EARTH
GND
Note: Earth Ground terminal is factory
connected to internal housing ground lug.
IMPORTANT: For EMI protection, see installation instructions on drawing 9006113
(Installation Drawing For MPXI) on page 37.
9
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
4-20 mA Loop Wiring
V 1
Out 1
Power
Source
(24 VDC)
Sensor
Out 24V
RST-4100
Load Resistor
(150 Ω to 200 Ω)
Wired in series for
programming.
+
Note: 24 VDC is
required to establish
communications
with the MPXI-F6 or
MPXI-F7.
Programming Module
and APG Modbus software
required for programming
MPXI-F6 and MPXI-F7
series sensors.
USB to computer
with APG Modbus
software
V 2
MPXI-F6 or
MPXI-F7 series
sensor.
Programming configuration is
for programming ONLY. After
programming, sensor must be
reintegrated to 4-20 mA loop
for proper system operation.
Out 2
4-20 mA Programming Wiring
NOTE: For MPXI-F7 series sensors, - VDC from power source must
be connected to Out1 on sensor for correct sensor programming.
IMPORTANT: Refer to Chapter 5 for Installation Drawing For MPXI.
Out1
V1
MPXI-F6
4-20 mA Output
+24 VDC
Process
Controller
4-20 mA
Out1
V1
MPXI-F7
4-20 mA Output
Out2
V2
+24 VDC
4-20 mA
+24 VDC
Process
Controller
4-20 mA
HH-
HH+
MPXI-F
High Level Switch
Normally Closed
+5-24 VDC
Process
Controller
DigitaI Input
Note: 5-24 VDC required on HH+ terminal
for High Level Switch operation.
High Level Switch Wiring
10
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Chapter 2: Installation and Removal Procedures and Notes
You will need the following tools to install your MPXI-F level sensor:
Wrench sized appropriately for MPXI-F mounting
Wrench sized appropriately for conduit connections
Flat-head screwdriver for wire terminals
Channel lock pliers for tightening compression tting
1/8” Hex Allen wrench for set screws
Tools Needed
Under certain extreme circumstances, the non-metalic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of electrostatic charge. Therefore the equipment
shall not be installed in a location where the external conditions are conducive to the build-up of
electrostatic charge on such surfaces. In addition, the equipment shall only be cleaned with a damp
cloth.
The enclosure is manufactured from Aluminum. In rare cases, ignition sources due to impact and
friction sparks could occur. This shall be considered during installation.
Unused conduit entries shall be closed with blanking elements maintaining explosion-proof properties
and ingress protection rating of the enclosure and are removable only with the use of a tool.
Wiring used for external connections shall be rated at least 20°C higher than the maximum ambient
temperature.
Conduit seal shall be installed within 18” of enclosure.
MPXI shall be supplied by Class 2 or limited energy source according to C22.2 NO 61010-1 and UL
61010-1.
ATEX Stated Conditions of Use
IMPORTANT: MPXI-F level sensor MUST be installed according to drawing 9006113
(Installation Drawing For MPXI) on page 37 to meet listed approvals. Faulty installation will
invalidate all safety approvals and ratings.
11
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
The MPXI-F should be installed in an area--indoors or outdoors--which meets the following conditions:
Ambient temperature between -40°C and 85°C (-40°F to +185°F)
Relative humidity up to 100%
Altitude up to 2000 meters (6560 feet)
IEC-664-1 Conductive Pollution Degree 1 or 2
IEC 61010-1 Measurement Category II
No chemicals corrosive to stainless steel (such as NH
3
, SO
2
, Cl
2
). (Not applicable to plastic-type stem
options)
Ample space for maintenance and inspection
Additional care must be taken to ensure:
The probe is located away from strong magnetic elds, such as those produced by motors, transform-
ers, solenoid valves, etc.
The medium is free from metallic substances and other foreign matter.
The probe is not exposed to excessive vibration.
The oat(s) t through the mounting hole. If the oat(s) does/do not t, it/they must be mounted on
the stem from inside the vessel being monitored.
The oat(s) is/are oriented properly on the stem (See Figure 2.2). MPXI-F oats are installed by custom-
er.
Physical Installation Notes
CARE SHOULD BE TAKEN TO ENSURE THAT THE ENCLOSURE OF THE MPXI IS INSTALLED IN ZONE 1. ONLY THE
PORTION OF THE UNIT AS SPECIFIED IN DOCUMENT 9006113 SHALL BE INSTALLED IN ZONE 0. ENSURE SEPA-
RATION BETWEEN ZONES DURING INSTALLATION TO AVOID INTRODUCTION TO EXPLOSIVE ATMOSPHERES.
12
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Figure 2.1
Prior to installing a PVDF-stem MPXI-F, the interior, mid-column temperature of the tank must be meas-
ured to determine the amount clearance needed at the bottom of the probe for thermal expansion. See
Figure 2.1
1. Determine interior, mid-column temperature in °F.
2. Determine interior tank height from top of probe mounting to tank interior bottom, in inches.
3. Use formula in Figure 2.1 to determine necessary clearance from bottom of probe to interior tank
bottom.
4. If necessary, adjust placement of slide mount on probe to accomodate required clearance.
Contact factory with any PVDF-stem thermal expansion requirement questions.
PVDF Installation Temperature Requirements
PROBE CLEARANCE = .000108 * (185 - INSTALL TEMPERATURE) * INTERNAL TANK HEIGHT
† TEMPERATURE IN DEG. F
LENGTH IN INCHES
INTERNAL TANK HEIGHT (IN)
(MOUNTING TOP TO TANK BOTTOM)
PROBE CLEARANCE (IN)
TANK
MOUNTING OPTION
13
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Ensure that all components have been received, including:
MPXI-F sensor (head and stem, slide mount if purchased)
Float or oats, if oat(s) purchased from APG
Stem Weight(s); Weight-Locking Pin and Set Screw for SS; Top Weight Retention Ring (with two screws),
Dowel Pin for PVDF
Assembly drawing
Assemble sensor mounting, oat(s), weight and pins at installation location, if possible.
If not already attached, slide mounting option onto stem. Loosen compression cap so it will slide easily
on stem. For probes with PVDF stems, be sure to account for thermal expansion clearance (see page
10) when placing slide mount on stem.
For SS sensors with oat stops, refer to the assembly drawing included with the sensor for oat stop
installation locations. PVDF oat stops are installed at the factory.
Note: If the oats do not t through the tank/vessel mounting hole, mount them on the stem from
inside the vessel being monitored. Then secure the sensor to the vessel.
Slide oats onto stem. If using two oats, slide the lighter oat on rst. Tops of oats will be indicated
by sticker, taper, or etching on oat. (See Figure 2.2) After ensuring top of oat is toward MPXI-F sensor
head, remove sticker(s).
For PVDF stem:
- Slide weight retention ring onto stem and then insert weight(s) on end of stem
- Secure dowel pin in end of stem (use hammer/mallet if necessary)
- Slide weight(s) down onto dowel pin
- Lock weight(s) in place by sliding weight retention ring down to top weight and tighten
For SS stem:
- Insert weight(s) on end of stem
- Insert weight-locking pin into end plug hole
- Lock into place with set screw, using 1/8” allen wrench
Install MPXI-F sensor on tank
When lifting and installing the sensor be sure to minimize the bending angle between the rigid stem at
the top and bottom of the sensor and the exible stem in-between. Sharp bends at those points could
damage the sensor. The 10” bend radius of the PVDF probe’s shipping box can be used as a guide for
the smallest allowable bend for the PVDF stem (see MPXI-F/K Shipping Box Contents on page 4).
If your sensor’s stem and oat(s) t through the mounting hole, insert the weight and the oats into
the mount opening.
Carefully unroll and feed the MPXI-F sensor stem into the tank, being careful to not let the oat(s) drop
uncontrolled on the stem. Slide the mount up to the top of the stem.
For PVDF stem:
- When the weight is on the bottom of the tank, secure the mounting option to the vessel
- Take any slack out of the exible stem, raising bottom of stem to previously calculated clearance
height (see page 12).
- Tighten the compression tting to hold stem in place.
For SS stem:
- When the weight is on the bottom of the tank, secure the mounting option to the vessel.
- Take any slack out of the exible stem.
- Tighten the compression tting to hold stem in place.
Physical Installation Instructions
14
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Figure 2.2
UP
Taper
IMPORTANT: Floats must be oriented
properly on the stem, or sensor readings will
be inaccurate and unreliable. Untapered oats
will have a sticker or etching indicating the top
of the oat. Remove sticker prior to use.
NOTE: Damage due to oats dropped on stem may not be be covered by warranty.
Connect approved electrical conduit to MPXI-F housing. Any ttings used must be UL/CSA Listed for
CSA installation.
Remove the housing cover of your MPXI-F.
Feed system wires into MPXI-F through conduit opening.
Connect wires to MPXI-F terminals. Use crimped ferrules on wires, if possible.
Replace the housing cover.
For EMI protection, see installation instructions on drawing 9006113 (Installation Drawing For MPXI) on
page 37.
See System Wiring Diagrams (pages 8 - 9) for wiring examples.
Electrical Installation
IMPORTANT: WARNING -- A CONDUIT SEAL SHALL BE INSTALLED WITHIN 18 inches OF THE ENCLOSURE;
AVERTISSEMENT -- UN SCELLEMENT DOIT ÊTRE INSTALLÉ À MOINS DE 18 inches DU BOÎTIER.
15
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Removing your MPXI-F level sensor from service should be done with care.
Ensure that all circuits are turned o and hazardous atmosphere around sensor head has been
cleared.
Remove housing cover and disconnect wires. Replace housing cover.
Disconnect conduit from sensor housing.
If the oats on your sensor t through the mounting hole, carefully lift the entire sensor assembly out
of and away from the vessel.
If the oats on your sensor do not t through the mounting hole, they will need to be removed from
the stem before the sensor can be removed. Be sure to drain the vessel being monitored to allow ac-
cess to the oats and stem for removal.
Clean the stem and oats of any build up or debris and inspect for damage.
Store your sensor in a dry place, at a temperature between -40° F and 180° F.
Removal Instructions
IMPORTANT: Contact factory for shipping instructions prior to returning probe for any
reason.
16
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
MPXI-F8 series sensors use standard Modbus RTU protocol (RS-485). The sensors can only operate as client
devices. Sensor default transmission settings are 9600 Baud, 8 Bits, 1 Stop Bit, No Parity, and require a
minimum delay of 300 ms between transactions. See MPXI-F8 Modbus Register Lists on pages 17 and 18.
Chapter 3: Programming
Modbus Programming
NOTE: For more information about Modbus RTU, please visit www.modbus.org.
An APG RST-6001 Modbus Controller can be used in tandem with APG Modbus software to program and
control up to 20 MPXI-F8 series sensors. Through APG Modbus, you can monitor the raw readings from the
sensor, congure the data for distance, level, volume, or weight, and enter measurements for a strapping
chart. See MPXI-F8 Modbus Register Lists on pages 17 and 18.
Modbus Programming with RST-6001 and APG Modbus Software
NOTE: For APG Modbus programming instructions, or to download APG Modbus soft-
ware, please visit www.apgsensors.com/suppport.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52