RMK400 Recessed Mounting Kit for use
with 100 and 200 Photoelectronic or 400
and 500 Series Plug-in Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The RMK400 Recessed Mounting Kit is designed for use
with System Sensor 100 and 200 photoelectronic or 400 and
500 Series plug-in detectors. As indicated in Figure 1, this
mounting kit provides for the recessed mounting of these
detectors on a junction box with flexible conduit on dry-
wall, suspended ceilings, and other similar surfaces.
Note: All System Sensor smoke detectors can be made
tamper-resistant. However, the use of this capabil-
ity is NOT recommended with the RMK400 Mount-
ing Kit.
The kit consists of:
1 Plastic Recess Mounting Ring
1 Plastic Spacer Ring
1 Metal Mounting Bracket
2 Screws, Type B, No. 8
Mounting Instructions
1. Cut a 4-1/2-inch (115 mm) hole at the desired location
in the mounting surface.
2. Position a 4-1/2 inch junction box at the location of
the hole cut in step 1. Route all wiring to the box
through flexible conduit. Be sure to allow sufficient
conduit and wiring to permit the wired box/conduit
assembly to be pulled through the 4-1/2" hole.
3. Pull the wiring through the box and attach the conduit
to the junction box.
4. Pull the junction box as far as possible through the
hole that was cut in step 1.
5. Attach the Metal Mounting Bracket to the junction
box, using the screw supplied with the junction box.
6. Pull the electrical wiring around the Metal Bracket and
through the center holes in the Recess Mounting Ring,
Spacer Ring, and the Detector Mounting Base. See Fig-
ure 2. Align the holes in the B401 or B501 Detector
Mounting Base and the holes in the plastic Recess
Mounting Ring with the two small holes of the Metal
Mounting Bracket.
7. 100/200 Series photoelectronic detectors only. Snap
the Spacer Ring into place in the Recess Mounting
Ring.
8. Start the two Type B, No. 8 screws, supplied, into the
Figure 2. Top view of mounting bracket:
Figure 1:
Figure 3:
small holes in the Metal Mounting Bracket and tighten
them until the assembly is just snug. Do NOT tighten
the screws to the point where the Metal Mounting
Bracket begins to deform.
9. Insert this assembly into the mounting hole and hold
it in place while tightening the screws started in step 8
until the assembly is retained in the mounting surface.
10. Wire the detector base, following the instructions pro-
vided with the base.
11. Plug the detector into the base and rotate it clockwise
until it locks into the mounting base.
D450-07-00 1 I56-372-04
© System Sensor 1996