Shinko SAxA series User manual

Type
User manual
ALARM DETECTOR
SA A SERIES
INSTRUCTION MANUAL
2
Preface
Thank you for purchasing the Alarm Detector SA A series.
This manual contains instructions for the mounting, functions, operations and notes when
operating the SA A series. To prevent accidents arising from the misuse of this instrument,
please ensure the operator receives this manual.
Notes
This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury
or malfunction may occur.
Specifications of the SA A series and the contents of this instruction manual are subject to
change without notice.
Care has been taken to ensure that the contents of this instruction manual are correct, but if there
are any doubts, mistakes or questions, please inform our sales department.
This instrument is designed to be installed on a DIN rail. If it is not, measures must be taken to
ensure that the operator does not touch power terminals or other high voltage sections.
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a
result of using this product, including any indirect damage.
SAFETY PRECAUTIONS (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on circumstances, procedures indicated by Caution may cause serious results,
so be sure to follow the directions for usage.
Warning
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
Safety precautions
To ensure safe and correct use, thoroughly read and understand this manual before using
this instrument.
This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after consulting purpose of use with our agency or main office.
(Never use this instrument for medical purposes with which human lives are involved.)
External protection devices such as protection equipment against excessive temperature rise, etc.
must be installed, as malfunction of this product could result in serious damage to the system or
injury to personnel. Also proper periodic maintenance is required.
This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring
due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture
of weapons of mass destruction (i.e. military applications, military equipment, etc.), please
investigate the end users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and
cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause
superficial to medium injury or physical damage or may degrade
or damage the product, if not carried out properly.
3
1
1
.
.
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of -5 to 55 (23 to 131 )
that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
When installing this unit within a control panel, take note that ambient temperature of
this unit must not exceed 55 (131 ). Otherwise the life of electronic components
(especially electrolytic capacitor) may be shortened.
Note Do not install this instrument on or near flammable material even though the case of
this instrument is made of flame-resistant resin.
2
2
.
.
W
W
i
i
r
r
i
i
n
n
g
g
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
• Do not leave bits of wire in the instrument, because they could cause a fire and malfunction.
• When wiring terminals, use ferrules with an insulation sleeve and crimping pliers made
by Phoenix Contact GMBH & CO. applicable to terminals.
• Tighten the terminal screw using the specified torque.
If excessive force is applied to the screw when tightening, the screw or case may be
damaged.
This instrument has no built-in power switch, circuit breaker or fuse. It is necessary to
install them near the instrument.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For wiring of AC power source, be sure to use exclusive terminals as described in this
manual. If AC power source is connected to incorrect terminals, the unit will burn out.
• For a 24V DC power source, do not confuse polarity when wiring.
Do not apply a commercial power source to the sensor connected to the input terminal nor
allow the power source to come into contact with the sensor, as the input circuit may burn out.
• Use a thermocouple, compensating lead wire and 3-wire system RTD according to the
sensor input specifications of this unit.
When using DC voltage and current input, do not confuse polarity when wiring.
Keep the input wire (TC, RTD, etc.), power line and load wire away from one another.
3
3
.
.
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
a
a
n
n
d
d
m
m
a
a
i
i
n
n
t
t
e
e
n
n
a
a
n
n
c
c
e
e
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
• Do not touch live terminals. This may cause electric shock or problems in operation.
Turn the power supply to the instrument OFF when retightening the terminal and
cleaning. Working or touching the terminal with the power switched ON may result in
severe injury or death due to Electric Shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
As the display section is vulnerable, do not strike or scratch it with a hard object or
press hard on it.
4
Characters used in this manual
Indication
Number, / -1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
means that no character is indicated (unlit) on the display.
--- CONTENTS ---
1. Model Page
1.1 Model ---------------------------------------------------------------------------- 5
1.2 How to read the model label ----------------------------------------------- 6
2. Name and functions of sections ----------------------------------- 6
3. Mounting
3.1 External dimensions (Scale: mm) ---------------------------------------- 7
3.2 Mounting to and removal from the DIN rail ----------------------------- 7
4. Wiring
4.1 Recommended ferrules ----------------------------------------------------- 8
4.2 Terminal arrangement and circuit configuration ---------------------- 9
4.3 Wiring of terminals ---------------------------------------------------------- 10
4.3.1 Power source wiring --------------------------------------------------- 10
4.3.2 Output wiring ------------------------------------------------------------- 10
4.3.3 Input wiring --------------------------------------------------------------- 10
5. Operation flowchart ---------------------------------------------------------- 11
6. Setup
6.1 Indication after power ON ------------------------------------------------- 12
6.2 Basic operation of setup --------------------------------------------------- 14
6.3 Setup of the unit ------------------------------------------------------------- 14
7. Alarm setting
7.1 Basic operation of alarm setting ----------------------------------------- 18
7.2 Alarm setting------------------------------------------------------------------ 19
8. Operation
8.1 Indication after power-on -------------------------------------------------- 19
8.2 Operation --------------------------------------------------------------------- 19
9. Specifications -------------------------------------------------------------- 20
10. Troubleshooting
10.1 Indication -------------------------------------------------------------------- 23
10.2 Key operation -------------------------------------------------------------- 23
10.3 Operation ------------------------------------------------------------------- 23
11. Character table ------------------------------------------------------------- 24
5
1. Model
1.1 Model
SA A series
(*1) For SAAA (DC current alarm detector), a shunt resistor (sold separately) is required.
See (Table 4.3.3-1) on page 10.
(*2) For the input, refer to Input codes (Table 1.1-1) to (Table 1.1-4).
(*3) Alarm 1 and 2 output types can be selected from No alarm action, High limit alarm,
Low limit alarm, High limit alarm with standby and Low limit alarm with standby by
keypad operation.
(e.g.) S A E A – 0 1 1 1-0 Alarm detector type: Thermocouple
Input : K, -200 to 1370
Alarm 1 : High limit alarm
Alarm 2 : High limit alarm
Power supply : 100 to 240V AC
(Table 1.1-1)
Input code [SAEA (Thermocouple)]
Thermocouple Scale range Thermocouple Scale range
01 K -200 to 1370 51 K -328 to 2498
02 K -199.9 to 400.0 52 K -199.9 to 752.0
03 J -200 to 1000 53 J -328 to 1832
04 R -50 to 1760 54 R -58 to 3200
05 S -50 to 1760 55 S -58 to 3200
06 B 0 to 1820 56 B 32 to 3308
07 E -200 to 800 57 E -328 to 1472
08 T -199.9 to 400.0 58 T -199.9 to 752.0
09 N -200 to 1300 59 N -328 to 2372
10 PL- 0 to 1390 60 PL- 32 to 2534
11 W5Re/W26Re 0 to 2315 61 W5Re/W26Re 32 to 4199
12 W3Re/W25Re 0 to 2315 62 W3Re/W25Re 32 to 4199
SA A Series name: SA A
E Thermocouple
R RTD
A DC current (*1)
Alarm
detector
type
V DC voltage
Input xx Input code (*2)
0 No alarm action
1 High limit alarm
2 Low limit alarm
3 High limit alarm with standby
Alarm 1 output (*3)
4 Low limit alarm with standby
0 No alarm action
1 High limit alarm
2 Low limit alarm
3 High limit alarm with standby
Alarm 2 output (*3)
4 Low limit alarm with standby
0 100 to 240V AC
Power supply
1 24V AC/DC
6
(Table 1.1-2)
Input code [SARA (RTD)]
RTD Scale range RTD Scale range
01 Pt100 -50.0 to 100.0 51 Pt100 -58.0 to 212.0
02 Pt100 -50.0 to 300.0 52 Pt100 -58.0 to 572.0
03 Pt100 -200 to 850 53 Pt100 -328 to 1562
04 JPt100 -50.0 to 100.0 54 JPt100 -58.0 to 212.0
05 JPt100 -50.0 to 300.0 55 JPt100 -58.0 to 572.0
06 JPt100 -200 to 500 56 JPt100 -328 to 932
(Table 1.1-3) (Table 1.1-4)
Input code [SAAA (DC current)] Input code [SAVA (DC voltage)]
DC current Scale range DC voltage Scale range
01 4 to 20mA DC 01 0 to 100mV DC
02 0 to 20mA DC 02 0 to 1V DC
03 2 to 10mA DC 03 0 to 5V DC
04 0 to 10mA DC 04 1 to 5V DC
05 0 to 16mA DC 05 0 to 10V DC
-1999 to 9999
06 1 to 5mA DC
07 0 to 1mA DC
-1999 to 9999
1.2 How to read the model label
The model label is attached to left side of the case.
Model
Input
Serial number
(Fig. 1.2-1)
2. Name and functions of sections
(Fig.2.1)
1
Power indicator (Green)
Lights when the power to the instrument is turned on.
2
Input display (Red)
Indicates the input value during Run mode.
Indicates setting characters during the Setup
and Alarm setting mode.
3
Set value display (Green)
During Run mode, indicates an indication type
(Alarm 1 or 2 value) selected during Display
selection.
Indicates the following characters for alarm output.
Alarm output Set value display
Alarm 1 output ON
Alarm 2 output ON
Alarm 1, 2 output ON
Indicates set values during the Setup and Alarm
setting mode.
1
2
4
5
6
7
3
7
4
Up key ( )
Increases the numeric value, or switches the selection items.
5
Down key ( )
Decreases the numeric value, or switches the selection items.
6
Mode key ( )
Switches the setting mode, and registers the set (or selected) value.
By holding down this key for approx. 3 seconds, the unit proceeds to the Alarm setting mode.
7
Sub-mode key (Unmarked)
If the Mode key is pressed while holding down this key, the unit proceeds to the Setup mode.
3. Mounting
3.1 External dimensions (Scale: mm)
(Fig. 3.1-1)
3.2 Mounting and removal to/from the DIN rail
Caution
• Mount the DIN rail horizontally.
• To remove this instrument, a flat blade screwdriver is required for pulling down
the lever.
Never turn the screwdriver when inserting it into the release lever.
If excessive power is applied to the lever, it may break.
• Be sure to use commercially available fastening plates at both ends of the unit
if it is in a position susceptible to vibration or shock.
Recommended fastening plate
Manufacturer Model
Omron Corporation End plate PFP-M
IDEC Corporation Fastening plate BNL6
Panasonic Electric Works Co., Ltd.
Fastening plate ATA4806
22.5
97
100 4
DIN rail
75
8
Mounting to the DIN rail (Fig. 3.2-1)
First, hook
1
of the instrument on the upper side of the DIN rail.
Second, making
1
part of the instrument as a support, fit the lower part
2
of the
instrument to the DIN rail.
The unit will be completely fixed to the DIN rail when a “Click” sound is heard.
Removal from the DIN rail (Fig.3.2-2)
First, insert a flat blade screwdriver into the release lever (
1
).
Second, remove the instrument from the DIN rail by pulling down the lever (
2
).
(Fig. 3.2-1) Mounting (Fig. 3.2-2) Removal
4. Wiring
Warning
Turn the power supply to the instrument off before wiring.
Working or touching the terminal with the power switched on may result in severe
injury or death due to Electric Shock.
4.1 Recommended ferrules
When using ferrules, use the following recommended ferrules and crimping pliers made by
Phoenix Contact GMBH &CO. See (Table 4.1-1).
Take note that screw size and tightening torque differ depending on the terminal number.
(Table 4.1-1)
Terminal
number
Terminal
screw
Ferrules with
insulation sleeve
Conductor
cross sections
Tightening
torque
Crimping pliers
AI 0.25-8 YE 0.2 to 0.25mm
2
AI 0.34-8 TQ 0.25 to 0.34mm
2
AI 0.5-8 WH 0.34 to 0.5mm
2
AI 0.75-8 GY 0.5 to 0.75mm
2
AI 1.0-8 RD 0.75 to 1.0mm
2
1 to 4 M2.6
AI 1.5-8 BK 1.0 to 1.5mm
2
0.5 to 0.6N•m
AI 0.25-8 YE 0.2 to 0.25mm
2
AI 0.34-8 TQ 0.25 to 0.34mm
2
5 to 9 M2.0
AI 0.5-8 WH 0.34 to 0.5mm
2
0.22 to 0.25N•m
CRIMPFOX
ZA 3
CRIMPFOX
UD 6
1
2
1
2
Release lever
9
+
5
6
7
8
9
1
2
3
4
Input circuit CPU
Thermocouple
Display/
Setting key
circuit
Power
circuit
Insulation circuit
+
Power supply
Alarm 2 output (Open collector)
Alarm 1 output (Relay contact, 1a)
5
6
7
8
9
1
2
3
4
CPU
RTD
Input circuit
Display/
Setting key
circuit
Insulation circuit
Power
circuit
Power supply
+
Alarm 2 output (Open collector)
Alarm 1 output (Relay contact, 1a)
5
6
7
8
9
1
2
3
4
CPU
Input
Input circuit
+
+
Power supply
Alarm 2 output (Open collector)
Alarm 1 output (Relay contact, 1a)
Insulation circuit
Power
circuit
Display/
Setting key
circuit
4.2 Terminal arrangement and circuit configuration
SAEA
(Fig. 4.2-1)
SARA
(Fig. 4.2-2)
SAAA, SAVA
(Fig. 4.2-3)
10
3
4
AC
Inductive load (coil)
Load
Varistor, CR circuit, etc.
3
4
DC
Load
Inductive load (coil)
Diode, varistor, CR circuit, etc.
8
9
+
DC
4.3 Wiring of terminals
Warning
• For 100 to 240V AC, if AC power source is connected to incorrect terminals,
this instrument will burn out.
• For a 24V DC power source, do not confuse polarity when wiring.
4.3.1 Power source wiring
Use terminals
1
(+) and
2
(-) for the power supply to the instrument.
4.3.2 Output wiring
Use terminals
3
(+) and
4
(-) for Alarm output 1.
Use terminals
8
(+) and
9
(-) for Alarm output 2.
Alarm 1 output: Take measures for relay protection and noise prevention
as shown below.
• AC power
(Fig. 4.3.2-1)
• DC power
(Fig. 4.3.2-2)
Alarm 2 open collector output connection example
(Fig. 4.3.2-3)
4.3.3 Input wiring
Terminals for wiring differs depending on the input specifications.
Refer to (Fig. 4.2-1), (Fig. 4.2-2) and (Fig. 4.2-3) on page 9.
SAAA: Use terminals
5
(+),
6
(-) for input wiring and shunt resistor (sold separately)
connection.
(Table 4.3.3-1)
Shunt resistor
Input
Model Specification
4 to 20mA DC, 0 to 20mA DC, 0 to 16mA DC RES-S02-050 50 0.1%
2 to 10mA DC, 0 to 10mA DC RES-S02-100 100 0.1%
1 to 5mA DC RES-S02-200 200 0.1%
0 to 1mA DC RES-S02-01K 1k 0.1%
11
5. Operation flowchart
Power ON
Warm-up indication
(Approx. 3sec.)
Press the key while holding
down the Sub-mode key.
[Setup mode]
IN
OUT
Set value lock
Press the key.
IN
OUT
Decimal point
place
IN
OUT
Alarm 2
Energized/
De-energized
Run mode
Press the key. Press the key.
Hold down the
for approx. 3sec
IN
OUT
Scaling low
limit
IN
OUT
Alarm 1
Hold function
[Alarm setting mode] Press the key. Press the key.
IN
OUT
Alarm 1 value
IN
OUT
Scaling high
limit
IN
OUT
Alarm 2
Hold function
Press the key. Press the key. Press the key.
IN
OUT
Alarm 2 value
IN
OUT
Filter time
constant
IN
OUT
Alarm 1
hysteresis
Press the key. Press the key. Press the key.
IN
OUT
Sensor
correction
IN
OUT
Alarm 2
hysteresis
Press the key. Press the key.
IN
OUT
Alarm 1 type
IN
OUT
Alarm 1 action
delay timer
Press the key. Press the key.
IN
OUT
Alarm 2 type
IN
OUT
Alarm 2 action
delay timer
Press the key. Press the key.
IN
OUT
Alarm 1
Energized/
De-energized
IN
OUT
Display selection
Press the key. Press the key.
IN
OUT
Indication time
Press the key.
The items
with dotted lines are not
indicated depending on
the specification.
• To return from Alarm
setting mode to Run
mode, press key
for approx. 3sec.
• By pressing the
key for approx. 3sec, the
unit reverts to the Run
mode from any mode.
12
6. Setup
Setup should occur before using this unit, to set the Alarm type, Alarm action Energized/
De-energized, Alarm action delay timer, etc. according to the users’ conditions.
If the users’ specifications are the same as the default value of the instrument, or if setup
has already been completed, it is not necessary to set up the instrument. Proceed to
Section “7. Alarm setting”.
(Table 6-1)
Setting item Default value
Set value lock Unlock
Decimal point place
No decimal point (Only for SAAA, SAVA)
Scaling high limit -1999 (Only for SAAA, SAVA)
Scaling low limit 9999 (Only for SAAA, SAVA)
Filter time constant
0.0sec
0.0 ( ) (SAEA, SARA)
Sensor correction
0 (SAAA, SAVA)
Alarm 1 type No alarm action
Alarm 2 type No alarm action
Alarm 1 action
Energized/De-energized
Energized
Alarm 2 action
Energized/De-energized
Energized
Alarm 1 Hold function Alarm Not holding
Alarm 2 Hold function Alarm Not holding
1.0 ( ) (SAEA, SARA)Alarm 1 hysteresis
1.0% (SAAA, SAVA)
1.0 ( ) (SAEA, SARA)Alarm 2 hysteresis
1.0% (SAAA, SAVA)
Alarm 1 action delay timer 0sec
Alarm 2 action delay timer 0sec
Display selection Input/Alarm 1 value indication
Indication time 00.00 (Continuous)
6.1 Indication after power-on
After power-on, warm-up status below (Fig. 6.1-1) is indicated for approx. 3sec.
(Fig. 6.1-1)
Lights when
power-on.
Indicates the input characters.
See (Table 6.1-1) on page 13.
Indicates for the SAEA (K: -200 to 1370 ).
Indicates the Input range high limit value (SAEA,
SARA) or Scaling high limit value (SAAA, SAVA).
Indicates for “K: -200 to 1370 .
13
(Table 6.1-1)
Input display
Input
K
K
J
R
S
B
E
T
N
PL-
W5Re/W26Re
W3Re/W25Re
: -200 to 1370
: -199.9 to 400.0
: -200 to 1000
: -50 to 1760
: -50 to 1760
: 0 to 1820
: -200 to 800
: -199.9 to 400.0
: -200 to 1300
: 0 to 1390
: 0 to 2315
: 0 to 2315
: -328 to 2498
: -199.9 to 752.0
: -328 to 1832
: -58 to 3200
: -58 to 3200
: 32 to 3308
: -328 to 1472
: -199.9 to 752.0
: -328 to 2372
: 32 to 2534
: 32 to 4199
: 32 to 4199
Pt100
Pt100
Pt100
JPt100
JPt100
JPt100
: -50.0 to 100.0
: -50.0 to 300.0
: -200 to 850
: -50.0 to 100.0
: -50.0 to 300.0
: -200 to 500
: -58.0 to 212.0
: -58.0 to 572.0
: -328 to 1562
: -58.0 to 212.0
: -58.0 to 572.0
: -328 to 932
4 to 20mA DC
0 to 20mA DC
2 to 10mA DC
0 to 10mA DC
0 to 16mA DC
1 to 5mA DC
0 to 1mA DC
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
0 to 100mV DC
0 to 1V DC
0 to 5V DC
1 to 5V DC
0 to 10V DC
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
: -1999 to 9999
After that, the unit proceeds to the Run mode as shown in (Fig. 6.1-2).
(Fig. 6.1-2)
Indicates the input value.
Indicates the input value from the
thermocouple for the SAEA (Default, K:
-200 to 1370 ).
Indicates when nothing is
connected to the input terminals.
Indicates Alarm 1 value.
Nothing is indicated as the default value
(No alarm) of Alarm 1 and Alarm 2.
14
6.2 Basic operation of setup
Setup is conducted in the Setup mode.
To enter the Setup mode, press the key while holding down the Sub-mode key in the
Run mode. (Fig. 6.2-1)
To set (select) each item, use the or key, and register the value with the key.
(Fig. 6.2-2)
(1) Run mode
(Fig. 6.2-1)
(2) Setup mode
(Fig. 6.2-2)
6.3 Setup of the unit
The following shows all setup items. Set up the unit referring to the explanation of each item.
Display Name, Function, Setting range Default value
Set value lock Unlock
IN
OUT
Locks the set values to prevent setting errors.
: Unlock
: Lock (None of the set values and adjusted values can be changed.)
Decimal point place
No decimal point
IN
OUT
• Selects the decimal point place.
• Available for the SAAA, SAVA.
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
Scaling low limit value
-1999
IN
OUT
Sets Scaling low limit value (A value indicated on the Input display when
rated low limit value is entered).
Available only for SAAA, SAVA.
Setting range: -1999 to Scaling high limit value
To set (or select)
each item, use
these keys.
To proceed to each setting item and
to register the set (selected) value,
use this key.
To enter the Setup mode, press the
key
2
while holding down the
Sub-mode key
1
in the Run mode.
1
2
15
Scaling high limit value
9999
IN
OUT
Sets Scaling high limit value (A value indicated on the Input display when
rated high limit value is entered).
Available only for SAAA, SAVA.
Setting range: Scaling low limit value to 9999
Filter time constant
0.0 seconds
IN
OUT
Sets the filter time constant.
Reduces input fluctuation caused by noise.
Setting range: 0.0 to 10.0 seconds
Sensor correction
0.0 ( ): SAEA, SARA
0 : SAAA, SAVA
IN
OUT
Sets the sensor correction value.
Input value = Current input value + (Sensor correction value)
Setting range: SAEA, SARA: -100.0 to 100.0 ( )
SAAA, SAVA : -1000 to 1000 (The placement of the decimal
point follows the selection.)
Alarm 1 type No alarm action
IN
OUT
Selects Alarm 1 type.
If alarm type is changed, Alarm 1 value reverts to 0 (0.0).
: No alarm action
: High limit alarm
: Low limit alarm
: High limit alarm with standby
: Low limit alarm with standby
Alarm 2 type No alarm action
IN
OUT
Selects Alarm 2 type.
If alarm type is changed, Alarm 2 value reverts to 0 (0.0).
: No alarm action
: High limit alarm
: Low limit alarm
: High limit alarm with standby
: Low limit alarm with standby
Alarm 1 action
Energized/De-energized
Energized
IN
OUT
Selects Alarm 1 action Energized/De-energized.
Not available if No alarm action is selected during Alarm 1 type selection.
Selection item:
: Energized
: De-energized
Alarm 2 action
Energized/De-energized
Energized
IN
OUT
Selects Alarm 2 action Energized/De-energized.
Not available if No alarm action is selected during Alarm 2 type selection.
Selection item:
: Energized
: De-energized
16
Alarm 1 Hold function Alarm Not holding
IN
OUT
Selects Alarm 1 Hold function “Holding” or “Not holding”.
If Alarm 1 Holding is selected, Alarm 1 output ON status is held until power
is turned off.
Not available if No alarm action is selected during A1 type selection.
Selection item:
: Alarm Not holding
: Alarm Holding
Alarm 2 Hold function Alarm Not holding
IN
OUT
Selects Alarm 2 Hold function “Holding” or “Not holding”.
If Alarm 2 Holding is selected, Alarm 2 output ON status is held until power
is turned off.
Not available if No alarm action is selected during A2 type selection.
Selection item:
: Alarm Not holding
: Alarm Holding
Alarm 1 hysteresis 1.0 ( ) (SAEA, SARA)
1.0% (SAAA, SAVA)
IN
OUT
Sets Alarm 1 hysteresis.
Not available if No alarm action is selected during A1 type selection.
Selection item:
SAEA, SARA: 0.1 to 100.0 ( )
SAAA, SAVA: 0.1 to 100.0%FS (The placement of the decimal point
follows the selection)
Alarm 2 hysteresis 1.0 ( ) (SAEA, SARA)
1.0% (SAAA, SAVA)
IN
OUT
Sets Alarm 2 hysteresis.
Not available if No alarm action is selected during A2 type selection.
Selection item:
SAEA, SARA: 0.1 to 100.0 ( )
SAAA, SAVA: 0.1 to 100.0%FS (The placement of the decimal point
follows the selection)
Alarm 1 action delay timer 0sec
IN
OUT
Sets Alarm 1 action delay timer.
When setting time has elapsed after the input enters the alarm output range,
Alarm 1 is activated.
Not available if No alarm action is selected during A1 type selection.
Setting range: 0 to 9999sec
Alarm 2 action delay timer 0sec
IN
OUT
Sets Alarm 2 action delay timer.
When setting time has elapsed after the input enters the alarm output range,
Alarm 2 is activated.
Not available if No alarm action is selected during A2 type selection.
Setting range: 0 to 9999sec
17
Display selection
Input/Alarm 1 value indication
IN
OUT
Selects an indication type on the display.
: Input/Alarm 1 value indication
: Input/Alarm 2 value indication
: Input indication
: No indication (Only the power indicator is lit.)
Indication time
00.00 (Continuous)
IN
OUT
Sets the indication time after the final key operation.
Not available if No indication (Only the power indicator is lit) is selected
during Display selection.
After the indication time has elapsed, the displays go off (Only the power
indicator is lit.).
If power is turned on again, or if any of the keys , , and the
Sub-mode key is pressed while displays are unlit, the displays will light again.
Setting range:
00.00: Continuous
00.01 (1 second) to 60.00 (60 minutes) [Minute.Second]
18
7. Alarm setting
7.1 Basic operation of alarm setting
Alarm setting is conducted in the Alarm setting mode.
To enter the Alarm setting mode, hold down the key for approx. 3 seconds in the Run
mode. (Fig. 7.1-1)
For alarm setting, use the or key, and register the value with the key.
(Fig. 7.1-2)
To revert to the Run mode, press the key again for approximately 3 seconds.
(1) Run mode
(Fig. 7.1-1)
(2) Alarm setting mode
(Fig. 7.1-2)
Please use these
keys for setting
alarm.
To proceed to each Alarm setting
item in the Alarm setting mode,
and to register the set value,
please use this key.
To enter Alarm setting mode,
please hold down the key for
approx. 3 seconds.
19
7.2 Alarm setting
The following shows all alarm setting items.
Set alarm values referring to explanation of each item below.
Display Name, Function, Setting range Default value
Alarm 1 value
0(0.0) ( )(SAEA, SARA)
0(SAAA, SAVA)
IN
OUT
Sets Alarm 1 action point.
Setting range:
SAEA, SARA : Input range low limit value to Input range high limit value
SAAA, SAVA : Scaling low limit value to Scaling high limit value
(The placement of the decimal point follows the selection)
Alarm 2 value
0(0.0) ( )(SAEA, SARA)
0(SAAA, SAVA)
IN
OUT
Sets Alarm 2 action point.
Setting range:
SAEA, SARA : Input range low limit value to Input range high limit value
SAAA, SAVA : Scaling low limit value to Scaling high limit value
(The placement of the decimal point follows the selection)
8. Operation
8.1 Indication after power-on
After power-on, the following warm-up status is indicated for 3 seconds (Fig. 8.1-1).
(Fig. 8.1-1)
8.2 Operation
The unit enters the Run mode after 3-second warm-up as shown in (Fig. 8.2-1).
(Fig. 8.2-1)
Lights after power-on.
Indicates the input characters.
See (Table 6.1-1) on page 13.
Indicates
for the SAEA (K:
-
).
Indicates the Input range high limit value (SAEA,
SARA) or Scaling high limit value (SAAA, SAVA).
Indicates
for SAEA (K:
-
200 t
o 1370
)
.
Indicates the input value.
For the SAEA (K: -200 to 1370 ), an input value from the
thermocouple is indicated.
If nothing is connected to the input terminals, will be
indicated.
Indicates the item selected during the Display selection (page 17).
20
Indication when alarm output is on
When alarm output is on, the following characters are indicated.
Alarm 1 output is ON : “ is indicated on the Set value display.
Alarm 2 output is ON : “ ” is indicated on the Set value display.
Alarm 1, 2 outputs are ON: “ is indicated on the Set value display.
Underrange, Overrange and Sensor burnout indication
Even if any selection is made during the Display selection, the following indications
appear.
Underrange: " " flashes on the Input display.
Overrange : " " flashes on the Input display.
Indication time setting
If indication time is set, the displays will go off (Only the power indicator is lit.) after the
indication time has elapsed.
If power is turned on again, or if any of the keys , , and the Sub-mode key
is pressed while displays are unlit, the displays will light again.
9. Specifications
Input specifications
SAEA
Input resistance: 1M or more
External resistance: 100 or less, However, B: 40 or less
Burnout: Upscale
Input: Thermocouple
Thermocouple Input range
K -200 to 1370 -328 to 2498
K -199.9 to 400.0 -199.9 to 752.0
J -200 to 1000 -328 to 1832
R -50 to 1760 -58 to 3200
S -50 to 1760 -58 to 3200
B 0 to 1820 32 to 3308
E -200 to 800 -328 to 1472
T -199.9 to 400.0 -199.9 to 752.0
N -200 to 1300 -328 to 2372
PL- 0 to 1390 32 to 2534
W5Re/W26Re 0 to 2315 32 to 4199
W3Re/W25Re 0 to 2315 32 to 4199
SARA
Input detection current: Approx. 0.2mA
Allowable lead wire resistance: 10 or less per wire
Burnout: Upscale
Input: RTD (3-wire system)
RTD Input range
Pt100 -50.0 to 100.0 -58.0 to 212.0
Pt100 -50.0 to 300.0 -58.0 to 572.0
Pt100 -200 to 850 -328 to 1562
JPt100 -50.0 to 100.0 -58.0 to 212.0
JPt100 -50.0 to 300.0 -58.0 to 572.0
JPt100 -200 to 500 -328 to 932
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Shinko SAxA series User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI