PHA2338700 00
10 - 2017
XB5EVp / XB5KSp
HAZARD OF ARC FLASH OR ELECTRIC SHOCK
p Hole diameter and tightening torques must comply
with the specifications provided in this document.
p The accessory ZB5AZ905 must be used to tighten
the nut.
p Do not remove the cap with voltage present.
Failure to follow these instructions will result in
death or serious injury.
DANGER
1
23
ZB5AZ905
2,2 Nm ± 0,2 / 19.5 lb-in ± 1.8
Maxi 0,8 Nm / 7.5 lb-in 3
2
Field Wiring : 22 16 AWG
Intermittent XB5KSp
X1
X2
S
-
Supply
+
z
z
Continuous XB5KSp
X1
X2
S
-
Supply
+
z
z
For use on flat surface of
a type 4, 4X, 12 and 13
enclosure.
30
1.18
mm
in
1...6
0.04...0.24
Ø22,3
0.88
40
1.57
+ 0,4
0
+ 0.02
0
  • Page 1 1