Mitsubishi Electric FR-A8NP User manual

Type
User manual
INVERTER
Plug-in option
INSTRUCTION MANUAL
PRE-OPERATION INSTRUCTIONS
1
INSTALLATION
2
WIRING
3
INVERTER SETTING
4
FUNCTIONS
5
PROFIBUS DEVICE DATA
6
PPO TYPE SUPPORT
SPECIFICATION
7
PPO TYPE NON-SUPPORT
SPECIFICATION
8
TROUBLESHOOTING
9
INVERTER
FR-A8NP INSTRUCTION MANUAL
E
INVERTER
PROFIBUS-DP
communication function
IB(NA)-0600528ENG-E(1802)MEE Printed in Japan Specifications subject to change without notice.
FR-A8NP
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
1
Thank you for choosing this Mitsubishi Electric inverter plug-in option.
This Instruction Manual provides handling information and precautions for use of this product. Incorrect handling might cause an unexpected
fault. Before using this product, read all relevant instruction manuals carefully to ensure proper use.
Please forward this Instruction Manual to the end user.
Electric shock prevention
Injury prevention
Safety instructions
Do not attempt to install, operate, maintain or inspect this product until you have read this Instruction Manual and appended documents
carefully. Do not use this product until you have a full knowledge of this product mechanism, safety information and instructions. In this
Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only
material damage.
Note that even the level may lead to a serious consequence depending on conditions. Be sure to follow the
instructions of both levels as they are critical to personnel safety.
WARNING
Do not remove the front cover or the wiring cover of the inverter while the inverter power is ON. Do not operate the inverter with any cover or wiring cover removed,
as accidental contact with exposed high-voltage terminals and internal components may occur, resulting in an electrical shock.
Even if power is OFF, do not remove the front cover of the inverter except for wiring or periodic inspection as you may accidentally touch the charged circuits and
get an electric shock.
Before wiring or inspection, check that the display of the inverter operation panel is OFF. Any person who is involved in wiring or inspection shall wait for 10 minutes
or longer after power OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after
power OFF, and it is dangerous.
Any person who is involved in wiring or inspection of this product shall be fully competent to do the work.
This product must be installed before wiring. Otherwise you may get an electric shock or be injured.
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Doing so may cause an electric shock.
Do not touch this product or handle the cables with wet hands. Doing so may cause an electric shock.
CAUTION
The voltage applied to each terminal must be as specified in the Instruction Manual. Otherwise a burst, damage, etc. may occur.
The cables must be connected to the correct terminals. Otherwise a burst, damage, etc. may occur.
The polarity (+ and -) must be correct. Otherwise a burst, damage, etc. may occur.
While power is ON or for some time after power OFF, do not touch the inverter as it will be extremely hot. Doing so may cause a burn.
WARNING
CAUTION
CAUTION
2
Additional instructions
The following instructions must be also followed. If this product is handled incorrectly, it may cause unexpected fault, an injury, or an electric
shock.
CAUTION
Transportation and installation
Do not stand or place heavy objects on this product.
The installing orientation of this product must be correct.
Do not install or operate this product if it is damaged or has parts missing.
Foreign conductive objects must be prevented from entering the inverter. That includes screws and metal fragments or other flammable substance such as oil.
If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.), included in fumigants to sterilize or disinfect wooden packages, infiltrate into this product, the
product may be damaged. Prevent residual fumigant components from being infiltrated into the product when packaging, or use an alternative sterilization or
disinfection method (heat disinfection, etc.). Note that sterilization or disinfection of wooden package should also be performed before packing the product.
Test operation
Before starting operation, confirm or adjust the parameter settings. Failure to do so may cause some machines to make unexpected motions.
WARNING
Usage
Do not modify this product.
Do not remove any part which is not instructed to be removed in the Instruction Manuals. Doing so may lead to a failure or damage of this product.
CAUTION
Usage
As all parameters return to their initial values after Parameter clear or All parameter clear is performed, the needed parameters for operation of the inverter and this
product must be set again before the operation is started.
To avoid damage to this product due to static electricity, static electricity in your body must be discharged before you touch this product.
Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test.
Disposal
This product must be treated as industrial waste.
General instruction
For clarity purpose, illustrations in this Instruction Manual may be drawn with covers or safety guards removed. Ensure all covers and safety guards are properly
installed prior to starting operation.
3
CONTENTS
1 PRE-OPERATION INSTRUCTIONS 6
1.1 Unpacking and product confirmation............................................................................................................................6
1.1.1 Product confirmation ............................................................................................................................................................. 6
1.2 Component names ..........................................................................................................................................................7
1.3 Specifications ..................................................................................................................................................................8
1.3.1 Inverter option specifications ................................................................................................................................................ 8
1.3.2 Communication specifications .............................................................................................................................................. 8
2 INSTALLATION 9
2.1 Pre-installation instructions ...........................................................................................................................................9
2.2 Installation procedure ...................................................................................................................................................10
2.3 Node address switch setting ........................................................................................................................................14
3WIRING 15
3.1 Terminals........................................................................................................................................................................15
3.2 Wiring..............................................................................................................................................................................16
4 INVERTER SETTING 19
4.1 Parameter list .................................................................................................................................................................19
4.2 Operation mode setting ................................................................................................................................................21
4.2.1 Operation mode switching and communication startup mode (Pr.79, Pr.340).................................................................... 21
4.3 Operation at communication error occurrence ..........................................................................................................24
4.3.1 Operation selection at communication error occurrence (Pr.500 to Pr.502, Pr.779) .......................................................... 24
4.3.2 Fault and measures ............................................................................................................................................................ 29
4.4 Inverter reset ..................................................................................................................................................................30
5 FUNCTIONS 32
5.1 Output from the inverter to the network......................................................................................................................32
4
5.2 Input to the inverter from the network.........................................................................................................................33
6 PROFIBUS DEVICE DATA 34
6.1 Device data (GSD file) ...................................................................................................................................................34
6.2 Slave user parameter ....................................................................................................................................................39
7 PPO TYPE SUPPORT SPECIFICATION 40
7.1 PROFIBUS profiles ........................................................................................................................................................40
7.1.1 Setting the PROFIBUS format (Pr.1110) ............................................................................................................................ 40
7.2 ID definitions ..................................................................................................................................................................44
7.3 Buffer memory configuration .......................................................................................................................................45
7.4 Buffer memory details...................................................................................................................................................47
7.5 Outline of PNU ...............................................................................................................................................................56
7.6 PROFIBUS PNU..............................................................................................................................................................57
7.6.1 Real-time monitor................................................................................................................................................................ 57
7.6.2 Parameter clear .................................................................................................................................................................. 58
7.6.3 Operation mode read/write ................................................................................................................................................. 58
7.6.4 Set frequency read.............................................................................................................................................................. 58
7.6.5 Terminal input read ............................................................................................................................................................. 59
7.6.6 Inverter reset....................................................................................................................................................................... 59
7.6.7 REF command assignment (available only when the extended format is selected) (only for the FR-A800 series)............ 59
7.6.8 STS monitor function (available only when the extended format is selected) (only for the FR-A800 series)...................... 61
7.6.9 Node address read ............................................................................................................................................................. 61
7.6.10 Fault history read ................................................................................................................................................................ 62
7.6.11 PNU list read....................................................................................................................................................................... 66
7.7 Standard parameters.....................................................................................................................................................67
7.8 PROFIBUS-DP communication function setting ........................................................................................................70
7.8.1 PROFIBUS communication command source setting (Pr.1109) (only for the FR-A800 series) ......................................... 70
7.8.2 Torque command / torque limit via PROFIBUS communication (Pr.804) (only for the FR-A800 series) ............................71
7.8.3 Torque bias selection (Pr.840) (only for the FR-A800 series)............................................................................................. 72
7.8.4 Frequency command with sign (Pr.541) ............................................................................................................................. 73
5
8 PPO TYPE NON-SUPPORT SPECIFICATION 74
8.1 PROFIBUS profiles ........................................................................................................................................................74
8.2 ID definitions ..................................................................................................................................................................75
8.3 Buffer memory configuration .......................................................................................................................................76
8.4 Buffer memory details...................................................................................................................................................77
8.5 Outline of PNU ...............................................................................................................................................................81
8.6 PROFIBUS PNU (module type A5NP) ..........................................................................................................................82
8.6.1 Real-time monitor area (IND = H0000 (IND = H00, PP = H00)) ......................................................................................... 82
8.6.2 System environment variable (sev) area (IND = H01PP (IND = H01, PP = H00, H01)) ..................................................... 83
8.7 Standard parameters.....................................................................................................................................................87
8.7.1 Normal parameter area (IND = H0200 (IND = H02, PP = H00))......................................................................................... 87
8.7.2 Pr.900 to calibration parameter (frequency) area (IND = H0300 (IND = H03, PP = H00)) ................................................. 88
8.7.3 Pr.900 to calibration parameter (%) area (IND = H0400 (IND = H04, PP = H00)).............................................................. 89
9 TROUBLESHOOTING 90
APPENDIX 92
6
PRE-OPERATION INSTRUCTIONS
1 PRE-OPERATION INSTRUCTIONS
1.1 Unpacking and product confirmation
Take the plug-in option out of the package, check the product name, and confirm that the product is as you ordered and intact.
This product is a plug-in option for the FR-A800/F800 series inverter.
1.1.1 Product confirmation
Check the enclosed items.
NOTE
PROFIBUS is a trademark of PROFIBUS & PROFINET International.
Plug-in option
..............................................1
Mounting screw (M3 8 mm)
..................3 (Refer to page 11.)
Spacer
..................2 (Refer to page 11.)
Communication option LED
display cover
..................1 (Refer to page 10.)
Earth plate
..................1 (Refer to page 11.)
X16
X1
O
N
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
PRE-OPERATION INSTRUCTIONS
7
1
1.2 Component names
Symbol Name Description Refer to page
a Mounting hole Fixes the option to the inverter with screws, or installs spacers.
11
b Terminal block Connect the communication cable.
15
c Operation status (LED)
ON/OFF indicator of the LED indicates inverter operation status.
d Node address switch Set the inverter address within the range of H00 to H7D.
14
e Switch for manufacturer setting Do not change from initially-set status (SW1: OFF).
f Connector Connect to the inverter option connector.
11
Front view
Rear view
(b)
(e)
(c)
(f)
X1
N
O
(a)
(a)
(a)
(a)
(a)
(a)
(d)
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
Pin assignment
D+
D-
V-
D-
CNTR
FG
V+
D+
D-
D+
V-
FG
SW3
SW1
X16
SW2
LED status Description
OFF Inverter power OFF
Red (ON) A communication error with the master occurred
Green (ON) During communication with the master
8
PRE-OPERATION INSTRUCTIONS
1.3 Specifications
1.3.1 Inverter option specifications
1.3.2 Communication specifications
Type
Inverter plug-in option type
Number of nodes occupied
One inverter occupies one node.
Connection cable
Cable which supports 12.0 Mbps communication (EIA-485 (RS-485) standard)
Communication speed
Wiring length 1200 m or less
9600 bps, 19.2 Kbps, 93.75 Kbps
Wiring length 600 m or less
187.5 Kbps
Wiring length 200 m or less
500 Kbps, 1.5 Mbps
Wiring length 100 m or less
3.0 Mbps, 6.0 Mbps, 12.0 Mbps
INSTALLATION
9
2
2 INSTALLATION
2.1 Pre-installation instructions
Check that the inverter's input power and the control circuit power are both OFF.
CAUTION
With input power ON, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged.
To avoid damage due to static electricity, static electricity in your body must be discharged before you touch the product.
10
INSTALLATION
2.2 Installation procedure
Installing the communication option LED display cover
(1) Remove the inverter front cover. (Refer to Chapter 2 of the Instruction Manual (Detailed) of the inverter for details on how
to remove the front cover.)
Mount the cover for displaying the operation status indication LED for the communication option on the inverter front cover.
(2) Cut off hooks on the rear of the inverter front cover with nipper, etc. and
open the window for fitting the LED display cover.
(3) Fit the communication option LED display cover to the front side of the
front cover. Align the LED display cover with the LED position on the
circuit board of the option. Push the LED display cover until it is fixed with
the hooks.
CAUTION
Take care not to hurt your hand and such with portions left by cutting hooks of the rear of the front cover.
Communication option LED display cover
INSTALLATION
11
2
Installing the option
NOTE
When a communication option is installed to the FR-A800-E/FR-F800-E series inverter, use the earthing (grounding)
cable supplied with the inverter instead of the earth plate supplied with the communication option. (For details of the
installation method, refer to the Instruction Manual of the inverter.)
Always attach the earth plate. However, in the case of a malfunction caused by noises due to external factors,
removing the earth plate may mitigate the noises, decreasing frequency of malfunctions. When removing the earth
plate, take measures to reduce electric potential difference in earthing (grounding) between the inverter and other
devices.
(1) For the two mounting holes (as shown in the next page)
that will not be tightened with mounting screws, insert
spacers.
(2) Fit the connector of the plug-in option to the guide of the
connector on the inverter unit side, and insert the plug-in
option as far as it goes. (Insert it to the inverter option
connector 1.)
(3) Fit the one location on the left of the earth plate (as shown
in the next page) securely to the inverter unit by screwing
in the supplied mounting screw. (tightening torque 0.33
N·m to 0.40 N·m)
(4) Fit the one location on the left of the plug-in option
securely to the inverter unit and the right of the plug-in
option to the inverter unit together with the earth plate by
screwing in the supplied mounting screws. (tightening
torque 0.33 N·m to 0.40 N·m). If the screw holes do not
line up, the connector may not be inserted deep enough.
Check the connector.
Spacer
Spacer
Inverter side
option connector
Earth plate
Example of installation to connector 1
12
INSTALLATION
Spacer
Spacer
Mounting screw
Do not insert the plug-in option to connector 2 or 3.
Mounting screw
Connector 1Connector 2
Connector 3
Insertion positions for screws and spacers
Earth plate
Mounting screw
INSTALLATION
13
2
NOTE
When mounting/removing the plug-in option, hold the sides of the option. Do not press on the parts on the option
circuit board. Stress applied to the parts by pressing, etc. may cause a failure.
Caution must be applied to mounting screws falling off when removing and mounting the plug-in option.
When using this plug-in option, insert it to the inverter option connector 1. If it is inserted to the option connector 2 or 3,
the protective function (E.2 or E.3) is activated and the inverter will not operate.
Even if the option is inserted to the option connector 1, when the inverter cannot recognize that the option is mounted
due to improper installation, etc., the protective function (E.1) is activated.
When removing the plug-in option, remove the two screws on the left and right, then pull it straight out. Pressure
applied to the connector and to the option board may break the option.
For instructions to replace the FR-A8NP or to install the FR-A8NP additionally in the existing PROFIBUS network,
refer to the Technical News (MF-I-146).
Mounted position Fault indication
Option connector 1
Option connector 2
Option connector 3
14
INSTALLATION
2.3 Node address switch setting
Set the node address between "H00" and "H7D" using the node address switches on the FR-A8NP board. (Refer to page 7.)
The setting is applied at the next power-ON.
Set the arrow () of the corresponding switches to a number or an alphabet to set a desired address.
Setting example
NOTE
Set the inverter node address before switching ON the inverter and do not change the setting while power is ON.
Otherwise you may get an electric shock.
Set the node address switch to the switch number (alphabet) position correctly. If the switch is set between numbers,
normal data communication cannot be established.
When the node address switches are set to any of H7E to HFF, the node address is recognized as H7D.
The node addresses, H00, H01, H02, H7C, and H7D, may not be available for some master modules.
You cannot set the same node address to other devices on the network. (Doing so disables proper communication.)
Node address 1:
Set the "
" of X16 (SW3) to "0" and the " " of X1
(SW2) to "1".
Node address 38 (H26):
Set the " " of X16 (SW3) to "2" and the " " of X1
(SW2) to "6".
X16
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
X1
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
(SW3)
(SW2)
X16
X1
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
(SW3)
(SW2)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Good
example
Bad
example
WIRING
15
3
3 WIRING
3.1 Terminals
 When connecting a terminating resistor, connect the terminating resistor to these terminals. (Refer to page 18.)
 It may not be necessary depending on the master used.
Terminal no. Terminal name Definition
1-A V+ (VP)  Voltage output (approx. 5 V to V-)
1-B D+ (RXD/TXD-P) Sends and receives PROFIBUS signal+ (B-line)
2-A D+ (RXD/TXD-P)
 Sends and receives PROFIBUS signal+ (B-line)
2-B D- (RXD/TXD-N) Sends and receives PROFIBUS signal- (A-line)
3-A D- (RXD/TXD-N)
 Sends and receives PROFIBUS signal- (A-line)
3-B V- (DGND) GND of D+/D-
4-A D+ (RXD/TXD-P)
 (To connect a terminating resistor)
4-B D- (RXD/TXD-N)
 (To connect a terminating resistor)
5-A V- (DGND)
 GND of D+/D-
5-B CNTR
 Control signal (sending request from the inverter)
6-A FG (Connected to the earth of the inverter unit)
6-B FG (Connected to the earth of the inverter unit)
D+ D- V-
D-
CNTR
FG
V+ D+ D- D+ V- FG
123456A
123456B
16
WIRING
3.2 Wiring
Use the network connection cable which supports 12.0 Mbps communication.
(1) Strip off the sheath of the PROFIBUS communication dedicated cable and wind wires and shield
cables to use.
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit
may occur with neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Use a ferrule terminal as necessary.
When using the ferrule terminal, use care so that the twisted wires do not come out.
NOTE
Ferrule terminal commercially available (as of January 2017. The product may be changed without notice.)
Cable stripping length
Terminal
screw size
Wire size (mm
2
)
Ferrule terminal model
Manufacturer
Crimping tool
name
with insulation sleeve without insulation sleeve
M2
0.3 AI 0,34-6TQ A 0,34-7
Phoenix Contact
Co., Ltd.
CRIMPFOX 6
0.5 Al 0,5-6WH A 0,5-6
5 mm
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
WireWire
SleeveSleeve
0 to 0.5 mm0 to 0.5 mm
WIRING
17
3
(2) Loosen the terminal screw and insert the cable into the terminal.
Tighten each cable with fixing screws to the recommended tightening torque.
NOTE
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction
due to damage to the screw or unit.
Screw size Tightening torque Cable size Screwdriver
M2 0.22 N•m to 0.25 N•m
0.3 mm
2
to 0.75 mm
2
Small flat-blade screwdriver
(Tip thickness: 0.4 mm /tip width: 2.5 mm)
D+
D-
V-
<Cable connection example>
To next inverter
To master
D+
D-
V-
D+
D-
V-
<Connection example of multiple inverters>
18
WIRING
(3) Terminating resistor
Connect terminating resistors to the both ends of a network if the both ends are FR-A8NP-mounted inverters.
CAUTION
After wiring, wire offcuts must not be left in the inverter. They may cause an error, failure, or malfunction.
PROFIBUS communication cable
Inverter
Motor Motor
Power
supply
Inverter
Power
supply
Terminating
resistor
PLC etc.
Master station
V+ D+ D- D+
D-
V-
R1 R2
R1=390Ω 2% 1/4W
R2=220Ω 2% 1/4W
R3=390Ω 2% 1/4W
Connection example
To other inverter
(node)
R3
Terminating
resistor
INVERTER SETTING
19
4
4 INVERTER SETTING
4.1 Parameter list
The following parameters are used for the communication option (FR-A8NP).
Set the values according to need. For the parameter details, which depend on the applicable model of the inverter, refer to the
Instruction Manual (Detailed) of the inverter.
Pr.
Pr.
group
Name Setting range
Minimum setting
increments
Initial
value
Refer to
page
79 D000 Operation mode selection 0 to 4, 6, 7 1 0 21
338 D010 Communication operation command source 0, 1 1 0

339 D011 Communication speed command source 0, 1, 2 1 0 
340 D001 Communication startup mode selection 0, 1, 2, 10, 12 1 0 21
342 N001 Communication EEPROM write selection 0, 1 1 0

349 N010 Communication reset selection 0, 1 1 0 31
500
 N011 Communication error execution waiting time 0 to 999.8 s 0.1 s 0 s 24
501
 N012 Communication error occurrence count display 0 1 0 25
502 N013 Stop mode selection at communication error 0 to 4, 11, 12 1 0 25
541
 N100 Frequency command sign selection 0, 1 1 0 73
550
 D012 NET mode operation command source selection 0, 1, 9999 1 9999 
779 N014 Operation frequency during communication error 0 to 590 Hz, 9999 0.01 Hz 9999 25
804
 D400 Torque command source selection 0, 1, 3 to 6 1 0 71
840
 G230 Torque bias selection
0 to 3, 24, 25,
9999
1 9999 72
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Mitsubishi Electric FR-A8NP User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI