Go to line 4.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A low integration time constant will make the
controller react fast but with less stability.
Go to line 7.
Set the neutral zone to a high value if you can
accept a large variation in flow temperature.
When the actual flow temperature lies within the
neutral zone, the controller does not
activate the motorized valve.
Go to line 6.
Set the running time of the motorized valve
according to the example on opposite page. This
is the time it takes the valve to move from closed
to fully open position.
Set the proportional band.
A higher value will result in a stable, but slow
regulation of the flow temperature.
Setting to be adjusted
Line
indicator
Basic set-up
Basic set-up
Setting the PI-regulation
Line 4-7
(hot water service)
27a
Auto Tuning
The Auto Tuning function automatically determines the PI-
control parameters for domestic hot water control. Thus you
do not need to set the parameter lines 4, 5, 6, and 7 in
circuit II, as they are automatically set to the Auto Tuning
function.
Auto Tuning is typically used in connection with the
installation of the controller, but it can be activated when
needed, e.g. for an extra check of the control parameters.
Before starting the Auto Tuning, the tapping flow should be
adjusted to the relevant value (see table below).
If possible, any additional hot water consumption should
be avoided during the Auto Tuning process. Should the
tapping load vary too much, the Auto Tuning and controller
will return to the default settings.
Auto Tuning is set to ON/OFF by using the service
parameter line 173 in circuit II, press
(ON) and
(OFF). When the Auto Tuning is ended, the service
parameter is automatically set to OFF (default setting). This
will be indicated in the display.
Typically, the Auto Tuning process takes 7-14 minutes but
can sometimes take up to 25 minutes.
Important!
In order to meet the summer-/winter variations, the ECL
clock must be set to the correct date for an successful Auto
Tuning. The motor protection function (line 174) has to be
deactivated during Auto Tuning.
During tuning the circulation pump for tap water service
must be turned off. This is done automatically if the pump is
controlled by the ECL controller.
No. of Heat Constant tapping load
apartments transfer (kW) (l/min)
1-2 30-49 3
(or 1 tap 25% open)
3-9 50-79 6 (or 1 tap 50% open)
10-49 80-149 12 (or 1 tap 100% open)
50-129 150-249 18 (or 1 tap 100% + 1 tap 50% open)
130-210 250-350 24 (or 2 taps 100% open)
27b
Recommended tapping load
4 Proportional band
Circuit Setting range Factory setting
II 1 ... 250 K 80 K
5 Integration time constant
Circuit Setting range Factory setting
II 5 ... 999 sec. 20 sec.
6 Running time of the motorized valve
Circuit Setting range Factory setting
II 5 ... 250 sec. 15 sec.
7 Neutral zone
Circuit Setting range Factory setting
II 0 ... 9 K 3 K
Note!
Auto Tuning is only applicable in connection with valves
that are approved for Auto Tuning, i.e. the Danfoss types
VB 2 and VM 2 with split characteristic as well as
logarithmic valves such as VF and VFS.
The grey
side of the
ECL Card
The grey
side of the
ECL Card