Danfoss KE04106 Valve Drive Amplifier Installation guide

Type
Installation guide
1
2
3
4
5
6
7
8
9
10
VALVE COILDIRECT OUTPUT
+12 VDC
SIGNAL COMMON
4 TO 20 mA SIGNAL
TRANSDUCER/
CONTROLLER
EDC
AB
1
2
2
1 INPUT IMPEDANCE IS 240 OHMS
DIRECT OUTPUT: 200 mA AT 10 VOLTS MAXIMUM
CURRENT
SOURCE
Unit Specification
3500 Annapolis Lane North, Minneapolis, MN 55447
Telephone: (763) 509-2084 Telefax: (763) 559-0108 ISSUE: 2 DATE: September 1996
KE04106
Valve Drive Amplifier
GENERAL DESCRIPTION
DIMENSIONS
OUTPUT CHARACTERISTICS
CONNECTION DIAGRAM
ny.
A
K14506 UNIT SPEC
1647 1650
The device is a free–standing amplifier mounted on 4 standoffs. Current or voltage signal from a transducer/controller, through
the amplifier, produces current to drive electrohydraulic actuators. Connections to the amplifier are via screw terminals.
SUPPLY VOLTAGE
12 Vdc (11 to 15 Volts)
INPUT IMPEDENCE
240 ohm
START CURRENT
4 mA nominal (1 Volt)
FULL STROKE CURRENT
20 mA (4.8 Volts)
MAXIMUM OUTPUT CURRENT
100 mA into a 25 ohm load
12,70
(0.50)
9,65
(0.38)
5,33 (0.21) INSIDE DIA.
76,20
(3.00)
57,15
(2.25)
6,35
(0.25)
114,30 (4.50)
101,60 (4.00)
KE04106
VALVE
DRIVE
AMPLIFIER
Dimensions of the KE04106 in Millimeters (Inches).
10
20
30
40
50
60
70
80
90
100
% MAXIMUM
OUTPUT VOLTAGE
% SUPPLY VOLTAGE
0 2 4 6 8 10 12 14 16 18 20
1651A
© Danfoss, 2013-09 K14506 UNIT SPEC 1
  • Page 1 1